TROUBLESHOOTING & SERVICING REFRIGERATION SYSTEM

 

PROBLEM

 

POSSIBLE CAUSE

 

REMEDY

1.

Condensing unit fails to start - no

1.

Line disconnect switch open.

1.

Close start or disconnect switch.

 

hum.

2.

Fuse removed or blown.

2.

Replace fuse.

 

 

3.

Overload protector tripped.

3.

Determine reason and

 

 

4.

Control stuck in open position.

 

correct/replace control.

 

 

4.

Repair or replace control.

 

 

5.

Wiring improper or loose.

5.

Check wiring against diagram.

 

 

 

 

 

 

2.

Compressor fails to start -

1.

Improperly wired.

1.

Check wiring against diagram.

 

hums and trips on overload

2.

Low voltage to unit.

2.

Determine reason and correct.

 

protector.

3.

Starting capacitor defective.

3.

Determine reason and replace.

 

 

4.

Relay failing to close.

4.

Determine reason and

 

 

5.

Compressor motor has a winding

 

correct/replace if necessary.

 

 

5.

Replace compressor.

 

 

 

open or shorted.

6.

Replace compressor.

 

 

6.

Internal mechanical trouble in

 

 

 

compressor.

 

 

 

 

 

 

 

 

3.

Compressor starts, but fails

1.

Improperly wired.

1.

Check wiring against diagram.

 

to switch off of “start” winding.

2.

Low voltage to unit.

2.

Determine reason and correct.

 

 

3.

Relay failing to open.

3.

Determine reason and

 

 

4.

Run capacitor defective.

 

correct/replace if necessary.

 

 

4.

Determine reason and replace.

 

 

5.

Excessively high discharge

5.

Check discharge shut-off valve,

 

 

 

pressure.

 

possible overcharge, or

 

 

6.

Compressor motor has a winding

 

insufficient cooling on condenser.

 

 

6.

Replace compressor.

 

 

 

open or shorted.

 

 

 

 

7.

Internal mechanical trouble in

7.

Replace compressor.

 

 

 

compressor.

 

 

 

 

 

 

 

 

4.

Compressor starts and runs,

1.

Additional current passing through

1.

Check wiring diagram.

 

but short cycles on overload

 

overload protector.

 

 

 

protector.

2.

Low voltage to unit (or

2.

Determine reason and correct.

 

 

 

unbalanced if three phase.)

 

 

 

 

 

 

 

3.

Overload protector defective.

3.

Check current , replace protector.

 

 

4.

Run capacitor defective.

4.

Determine reason and replace.

 

 

5.

Excessive discharge pressure.

5.

Check ventilation, restrictions in

 

 

 

 

 

cooling medium, restrictions in

 

 

6.

Suction pressure too high.

 

refrigeration system.

 

 

6.

For salad models, temperature

 

 

 

 

 

control differential set to close-

 

 

 

 

 

increase differential.

 

 

7.

Compressor too hot - return gas.

7.

Check refrigerant charge (fix leak)

 

 

 

 

 

add if necessary.

 

 

8.

Compressor motor has a winding

8.

Replace compressor.

 

 

 

shorted.

 

 

 

 

 

 

 

 

5.

Compressor runs but short

1.

Overload protector.

1.

See (4) above.

 

cycles on...

2.

Thermostat.

2.

Differential set too close - widen.

 

 

3.

High pressure cut-out due to:

3.

a. Check air or water supply to

 

 

 

a. Insufficient air or water supply.

 

 

 

 

b. Overcharge.

 

condenser-correct.

 

 

 

 

b. Recover refrigerant and recharge.

 

 

 

c. Air in system.

4.

 

 

 

4.

Low pressure cut-out due to:

a. Replace.

 

 

 

a. Liquid line solenoid leaking.

 

 

 

 

b. Compressor valve leak.

 

b. Replace.

 

 

 

c. Undercharge.

 

c. Fix leak, add refrigerant.

 

 

 

d. Restriction in expansion

 

d. Replace device.

 

 

 

device.

 

 

 

 

 

 

 

 

6.

Condensing unit operates for

1.

Shortage of refrigerant.

1.

Fix leak, add charge.

 

prolonged periods or

2.

Control contacts stuck or frozen

2.

Clean contacts or replace control.

 

continuously.

 

closed.

3.

Allow unit sufficient time for

 

 

3.

Excessive heat load placed into

 

 

 

cabinet.

 

removal of latent heat.

 

 

4.

Prolonged or too frequent door

4.

Plan or organize schedule to

 

 

 

openings.

 

correct condition.

 

 

5.

Evaporator coil iced.

5.

Defrost.

 

 

6.

Restriction in refrigeration

6.

Determine location and remove.

 

 

 

system.

 

 

 

 

7.

Dirty condenser.

7.

Clean condenser.

 

 

8.

Filter dirty.

8.

Clean or replace.

 

 

 

 

 

 

18

Image 24
Contents Series Reach-In Refrigerators and Freezers Limited Warranty General Conditions Procedure for Obtaining Replacement Compressors in Warranty Retain this Manual for Future Reference Table of Contents Section Description Control and Component Location Component Function Description Dimensions End Of Section, Click Here For Table Of Contents Section Installation Unpackaging ProcedureReceiving Shipment Removing DoorsHinges and Lock Keeper Rehingeability One & Two Section Long Door CabinetLock Keeper Installing Legs or Casters Locating Your New Storage Refrigerator or FreezerCleaning Cabinet Installing ShelvesLeveling Initial Cabinet Set-UpSteel Rod Type Pan Slide Racks Refer to Figure Angle Type Pan SlidesElectric Supply Installation Checklist Temperature Control Section OperationThermometer Operation Loading ProductSection Maintenance Initial Cleaning of CabinetPeriodic Cleaning Daily Exterior Surface Cleaning Cleaning and sanitizingWeekly Interior Accessory Cleaning Once Every Three Months, Condenser MaintenanceLubrication Use of Proper Tools and Cleaning Methods Treat Hard WaterSection Troubleshooting Troubleshooting & Servicing Refrigeration System End Of Section, Click Here For Table Of Contents Section Parts List Click Here to Return to Main Table of ContentsCabinet & Hinged Metal Door Parts Hinged Vision Panel Door Parts Thermometer & Grill Electrical Box Assembly One Section Refrigerator ComponentsTwo & Three Section Refrigerator Components One Section Freezer Components Two & Three Section Freezer Components Shelves & Pilasters Number of SectionsUpright Part Number Type Part Number Steel Rod Pan Slide Racks and Upright Parts Number of Sections Upright Part Number OneSection Wiring Diagrams 3 Section Refrigerator Section Freezer End Of Section, Click Here For Table Of Contents Victory Refrigeration Phone 856 428-4200 Fax 856