Page 14

2)Alarm Signals 2.1 Code Description

2.2 Alarm Recovery

Probe alarms P1”, start a few seconds after the fault in the related probe; they automatically stop a few seconds after the probe restarts normal operation. Check connections before replacing the probe. Temperature alarms “HA”, “LA” automatically stops as soon as the temperature returns to normal value. Alarm “CA” (with i1F=PAL) recovers only by switching off and on the instrument.

3)Temperature Set-Point3.1 How to see the set-point

1. Push and immediately release the SET key: the display will show the Set-point value;

2. Push and immediately release the SET key or wait for 5 seconds to display the probe value again.

3.2 How to change the set-point

1.Push the SET key for more than 3 seconds to change the Set point value;

-13 -

Image 14
Contents WINE-MATECooling Unit Important Safety Information Table of Contents Feature Description Feature DescriptionsDimensions Installation Instruction VINO1500-2500HZD Cabinet InstallationCabinet Cutout & Gasket LIP TOP Exhaust Gasket Cooling Unit VINO3500-8500HZD Through Wall Installation Through Wall Installation Cellar Construction Electrical CordTemperature Control & Humidity Adjustment Temperature SettingPage Humidity Adjustment Manual Defrost Moisture Removing Coil CleaningCare Guide Drain LineTroubleshooting Beeping HA alarmBlinking High or notTripping Water leakCircuit NoisyVINO1500-2500HZD Wiring Diagram VINO1500-2500HZD Calling Feature Wiring DiagramVINO3500-8500HZD Wiring Diagram Customer Support Service under Warranty WarrantyLimited Warranty Limitation of Implied Warranty