SPX Cooling Technologies 05-116E user manual Motor Relubrication Instructions

Page 27

Maintenance

additional cleaning. Refer to “Fluid Cooler Cleaning” section—page 21. Consult your water treatment expert as to prudent biological evaluation testing.

Geareducer models used on MH Fluid Coolers are designed for 5-year

Noteoil change intervals. To maintain five-year change intervals, use only oil designed specifically for these Geareducers. If, after five years, turbine-type mineral oil is used, the oil must be changed semiannu- ally. Refer to the Geareducer User Manual for oil recommendations and further instructions.

Annually: Relubricate motor(s) according to the manufacturer’s instruc- tions. See instructions on the next page for towers with the motor located outside the plenum option.

Check to see that all bolts are tight in the fan and mechanical equipment region, including the fan cylinder and fan guard. Refer to Component User Manuals for torque values.

Inspect the fluid cooler thoroughly, making maximum use of instructions given in the separate user manuals. Check structural bolted connections and tighten as required. Make preventive maintenance repairs as neces- sary.

Check to see that all bolts are tight in the fan and mechanical equipment region, including the fan cylinder and fan guard. Refer to Component User Manuals for torque values.

Every 5 Years: If equipped, change Geareducer oil. Refer to the Geareducer User Manual for instructions.

Motor Relubrication Instructions

Motor located outside plenum option. Double-flow models MHF706 and

MHF707 only.

Open and lock out disconnect switch to make certain motor cannot

be started.

1. Remove guard as shown in Figure 4. Opposite end motor bearing is accessible from outside the tower.

2. Remove grease fill and relief plugs at both shaft extension end and op-

posite end bearings and remove hardened grease, using clean wire.

27

Image 27
Contents Marley MH Fluid Cooler Page Contents Preparation Safety FirstFluid Cooler Location Hoisting Fluid Cooler InstallationFluid Cooler Shipment Receiving Fluid CoolerFluid Cooler Installation When using a starter Motor WiringWhen using a VFD When using a two-speedstarterInstallation Mechanical Equipment Installation Operation Fluid Cooler Start-UpWater System Operation General Fluid Cooler OperationFan acceleration time of 30 seconds per hour Wintertime OperationOperation Protection Against Coil Freezing Intermittent Wintertime OperationModel Coil Volume Maintaining Water Quality Water Treatment and BlowdownMaintenance Fluid Cooler CleaningBlowdown Belt Tensioning Jacking Screws Sheave Alignment FAN Shaft SheaveBushing Fastener Torque Values Fluid Cooler MaintenanceMaintenance Motor Relubrication Instructions Seasonal Shutdown Instructions Prolonged Shutdown SPX Cooling Technologies Services Maintenance Schedule Trouble Cause Remedy TroubleshootingTroubleshooting Additional Information Page Manual 05-116E

05-116E specifications

SPX Cooling Technologies 05-116E is a state-of-the-art cooling tower aimed at providing exceptional cooling efficiency for industrial and commercial applications. Known for its robust design and advanced features, the 05-116E model promises to deliver reliable performance under various operational conditions.

One of the most notable features of the 05-116E is its energy-efficient operation. The design incorporates advanced thermal performance technologies that allow this cooling tower to maximize heat exchange while minimizing energy consumption. This efficiency not only translates into cost savings for users but also reduces the environmental impact, making it a sustainable choice in today’s eco-conscious market.

The 05-116E utilizes a fiberglass-reinforced plastic construction, which contributes to its durability and resistance to corrosion. This is particularly advantageous for installations in harsh environments, where exposure to elements like chlorine or salt can significantly degrade the performance of traditional materials. The lightweight build facilitates easier installation and maintenance, further enhancing the operational effectiveness of the cooling tower.

Another key characteristic of the SPX Cooling Technologies 05-116E is its modular design. This feature allows for scalable configurations, enabling users to customize their cooling solution according to specific capacity requirements. Whether for a small facility or a large industrial operation, the modularity ensures that optimal cooling performance is maintained at all scales.

The cooling tower is also equipped with innovative fan technology that promotes quieter operation while simultaneously increasing airflow efficiency. This is particularly beneficial in urban or residential areas where noise reduction is a priority. Coupled with effective vibration dampening mechanisms, the 05-116E ensures a peaceful operating environment.

Moreover, the 05-116E model incorporates advanced water management systems, designed to minimize water usage and enhance water treatment practices. This not only conserves valuable resources but also ensures that the cooling processes remain hygienic and efficient throughout the operational lifespan.

In summary, the SPX Cooling Technologies 05-116E stands as a top-tier choice for those seeking a reliable, efficient, and durable cooling tower solution. With its energy-saving features, robust construction, modular capability, quiet operation, and advanced water management systems, it fulfills the demanding requirements of modern cooling applications across various industries.