Operation

Fluid Cooler Operation

General:

The cold process fluid temperature obtained from an operating fluid cooler will vary with the following influences:

1.Heat load: With the fan in full operation, if the heat load increases, the cold process fluid temperature will rise. If the heat load reduces, the cold process fluid temperature will reduce.

Heat Load (Btu/hr)

Range – °F =

GPM x 500

Note that the number of degrees (“range”) through which the fluid cooler cools the process fluid is established by the system heat load and the amount of fluid being circulated, in accordance with the follow- ing formula—formula is only valid for 100% water as process fluid:

The fluid cooler establishes only the cold process fluid temperature attainable under any operating circumstance.

2.Air wet-bulb temperature: Cold process fluid temperature will also vary with the wet-bulb temperature of the air entering the louvered faces of the fluid cooler. Reduced wet-bulb temperatures will result in colder process fluid temperatures. However, the cold process fluid temperature will not vary to the same extent as the wet-bulb. For example, a 20°F reduction in wet-bulb may result in only a 15°F reduction in cold process fluid temperature.

3.Fluid flow rate: Increasing the process fluid flow rate (GPM) will cause a slight elevation in cold process fluid temperature, while reducing the fluid flow rate will cause the cold process fluid temperature to decrease slightly. However, at a given heat load (see formula above), process fluid flow reductions also cause an increase in the incoming hot process fluid temperature and thermal range.

Under no circumstances should the recirculation water pump(s) be

Notecycled to control process fluid temperature. It is recommenced that while process fluid is being circulated through the coil the fluid cooler recirculation water system always be in operation.

15

Image 15
Contents Marley MH Fluid Cooler Page Contents Preparation Safety FirstFluid Cooler Location Hoisting Fluid Cooler InstallationFluid Cooler Shipment Receiving Fluid CoolerFluid Cooler Installation When using a starter Motor WiringWhen using a VFD When using a two-speedstarterInstallation Mechanical Equipment Installation Operation Fluid Cooler Start-UpWater System Operation General Fluid Cooler OperationFan acceleration time of 30 seconds per hour Wintertime OperationOperation Protection Against Coil Freezing Intermittent Wintertime OperationModel Coil Volume Maintaining Water Quality Water Treatment and BlowdownMaintenance Fluid Cooler CleaningBlowdown Belt Tensioning Jacking Screws Sheave Alignment FAN Shaft SheaveBushing Fastener Torque Values Fluid Cooler MaintenanceMaintenance Motor Relubrication Instructions Seasonal Shutdown Instructions Prolonged Shutdown SPX Cooling Technologies Services Maintenance Schedule Trouble Cause Remedy TroubleshootingTroubleshooting Additional Information Page Manual 05-116E

05-116E specifications

SPX Cooling Technologies 05-116E is a state-of-the-art cooling tower aimed at providing exceptional cooling efficiency for industrial and commercial applications. Known for its robust design and advanced features, the 05-116E model promises to deliver reliable performance under various operational conditions.

One of the most notable features of the 05-116E is its energy-efficient operation. The design incorporates advanced thermal performance technologies that allow this cooling tower to maximize heat exchange while minimizing energy consumption. This efficiency not only translates into cost savings for users but also reduces the environmental impact, making it a sustainable choice in today’s eco-conscious market.

The 05-116E utilizes a fiberglass-reinforced plastic construction, which contributes to its durability and resistance to corrosion. This is particularly advantageous for installations in harsh environments, where exposure to elements like chlorine or salt can significantly degrade the performance of traditional materials. The lightweight build facilitates easier installation and maintenance, further enhancing the operational effectiveness of the cooling tower.

Another key characteristic of the SPX Cooling Technologies 05-116E is its modular design. This feature allows for scalable configurations, enabling users to customize their cooling solution according to specific capacity requirements. Whether for a small facility or a large industrial operation, the modularity ensures that optimal cooling performance is maintained at all scales.

The cooling tower is also equipped with innovative fan technology that promotes quieter operation while simultaneously increasing airflow efficiency. This is particularly beneficial in urban or residential areas where noise reduction is a priority. Coupled with effective vibration dampening mechanisms, the 05-116E ensures a peaceful operating environment.

Moreover, the 05-116E model incorporates advanced water management systems, designed to minimize water usage and enhance water treatment practices. This not only conserves valuable resources but also ensures that the cooling processes remain hygienic and efficient throughout the operational lifespan.

In summary, the SPX Cooling Technologies 05-116E stands as a top-tier choice for those seeking a reliable, efficient, and durable cooling tower solution. With its energy-saving features, robust construction, modular capability, quiet operation, and advanced water management systems, it fulfills the demanding requirements of modern cooling applications across various industries.