Troubleshooting

Trouble

Cause

Remedy

 

 

 

 

 

If new, see if noise disappears after one week of operation. Drain flush,

Geareducer noise. (If

Geareducer bearings

and refill Geareducer oil. See Geareducer User Manual. If still noisy,

 

replace.

equipped).

 

 

 

Gears

Correct tooth engagement. Replace badly worn gears. Replace gears

 

 

with broken or damaged teeth.

 

 

 

 

 

 

Loose bolts and cap screws

Tighten all bolts and cap screws on all mechanical equipment and

 

supports.

 

 

 

 

 

 

 

Make sure motor and Geareducer shafts are in proper alignment and

 

Unbalanced drive shaft or worn couplings. (If

"match marks" properly matched. Repair or replace worn couplings.

 

equipped)

Rebalance drive shaft by adding or removing weights from balancing

 

 

cap screws. See Driveshaft User Manual

 

 

 

 

 

Make certain all blades are as far from center of fan as safety devices

Unusual fan drive vibration

Fan

permit. All blades must be pitched the same. See Fan User Manual.

 

 

Clean off deposit build-up on blades

 

 

 

 

Worn Geareducer bearings. (If equipped)

Check fan and pinion shaft endplay. Replace bearings as necessary.

 

 

 

 

Worn fan shaft bearings. (Belt drive).

Check fan shaft endplay. Replace bearings as necessary.

 

 

 

 

Unbalanced motor

Disconnect load and operate motor. If motor still vibrates, rebalance

 

rotor.

 

 

 

 

 

 

Bent Geareducer shaft. (If equipped).

Check fan and pinion shaft with dial indicator. Replace if necessary.

 

 

 

 

Blade rubbing inside of fan cylinder

Adjust cylinder to provide blade tip clearance

 

 

 

Fan noise

Loose bolts in blade clamps

Check and tighten if necessary.

 

 

 

 

Fan shaft bearing. (Belt drive).

Grease bearings.

 

 

 

Scale or foreign substance in

Insufficient blowdown

See "Water Treatment" section of this manual.

 

 

 

Consult competent water treating specialist. See "Water Treatment"

circulating water system

Water treatment deficiency

section of this manual

 

 

 

 

 

 

 

Check to see if local heat sources are affecting fluid cooler. See if

 

Entering wet bulb temperature is above design

surrounding structures are causing recirculation of tower discharge air.

 

 

Discuss remedy with Marley representative.

 

 

 

 

Design wet bulb temperature was too low.

May have to increase fluid cooler size. Discuss remedy with Marley

 

representative

 

 

Cold water temperature too

 

 

Actual process load greater than design

May have to increase fluid cooler size. Discuss remedy with Marley

warm.

representative

 

 

 

 

 

See "Tower Operation."

Overpumping

Reduce water flow rate over fluid cooler to design conditions.

 

 

 

 

 

Check motor current and voltage to be sure of correct contract

 

 

horsepower. Repitch fan blades if necessary. Clean louvers, fill and

 

Fluid cooler starved for air

eliminators. Check to see if nearby structures or enclosing walls are

 

 

obstructing normal airflow to fluid cooler. Discuss remedy with Marley

 

 

representative.

 

 

 

 

Distribution basins overflowing

Reduce water flow rate over fluid cooler to design conditions. Be sure

 

distribution water basin nozzles are in place and not plugged.

 

 

Excessive drift exiting fluid

cooler

Faulty drift elimination

Check to see that integral fill. Louvers and eliminators are clean, free of debris and installed correctly. If drift eliminators are separate from fill, make sure they are correctly installed and in place. Clean if necessary. Replace damaged or worn out components

33

Image 33
Contents Marley MH Fluid Cooler Page Contents Preparation Safety FirstFluid Cooler Location Fluid Cooler Shipment InstallationReceiving Fluid Cooler Hoisting Fluid CoolerFluid Cooler Installation When using a starter Motor WiringWhen using a VFD When using a two-speedstarterInstallation Mechanical Equipment Installation Operation Fluid Cooler Start-UpWater System Operation General Fluid Cooler OperationFan acceleration time of 30 seconds per hour Wintertime OperationOperation Protection Against Coil Freezing Intermittent Wintertime OperationModel Coil Volume Maintaining Water Quality Water Treatment and BlowdownMaintenance Fluid Cooler CleaningBlowdown Belt Tensioning Jacking Screws Sheave Alignment FAN Shaft SheaveBushing Fastener Torque Values Fluid Cooler MaintenanceMaintenance Motor Relubrication Instructions Seasonal Shutdown Instructions Prolonged Shutdown SPX Cooling Technologies Services Maintenance Schedule Trouble Cause Remedy TroubleshootingTroubleshooting Additional Information Page Manual 05-116E

05-116E specifications

SPX Cooling Technologies 05-116E is a state-of-the-art cooling tower aimed at providing exceptional cooling efficiency for industrial and commercial applications. Known for its robust design and advanced features, the 05-116E model promises to deliver reliable performance under various operational conditions.

One of the most notable features of the 05-116E is its energy-efficient operation. The design incorporates advanced thermal performance technologies that allow this cooling tower to maximize heat exchange while minimizing energy consumption. This efficiency not only translates into cost savings for users but also reduces the environmental impact, making it a sustainable choice in today’s eco-conscious market.

The 05-116E utilizes a fiberglass-reinforced plastic construction, which contributes to its durability and resistance to corrosion. This is particularly advantageous for installations in harsh environments, where exposure to elements like chlorine or salt can significantly degrade the performance of traditional materials. The lightweight build facilitates easier installation and maintenance, further enhancing the operational effectiveness of the cooling tower.

Another key characteristic of the SPX Cooling Technologies 05-116E is its modular design. This feature allows for scalable configurations, enabling users to customize their cooling solution according to specific capacity requirements. Whether for a small facility or a large industrial operation, the modularity ensures that optimal cooling performance is maintained at all scales.

The cooling tower is also equipped with innovative fan technology that promotes quieter operation while simultaneously increasing airflow efficiency. This is particularly beneficial in urban or residential areas where noise reduction is a priority. Coupled with effective vibration dampening mechanisms, the 05-116E ensures a peaceful operating environment.

Moreover, the 05-116E model incorporates advanced water management systems, designed to minimize water usage and enhance water treatment practices. This not only conserves valuable resources but also ensures that the cooling processes remain hygienic and efficient throughout the operational lifespan.

In summary, the SPX Cooling Technologies 05-116E stands as a top-tier choice for those seeking a reliable, efficient, and durable cooling tower solution. With its energy-saving features, robust construction, modular capability, quiet operation, and advanced water management systems, it fulfills the demanding requirements of modern cooling applications across various industries.