VII. MICROPROCESSOR CONTROL (continued)
VII. n - SETTING THE DEFROST LOCKOUTS:
The defrost lockout parameters allow the customer to prevent the unit from going into a defrost cycle for two hours during a set timeframe. Customers can set up to four defrost lockout parameters. They are all programmed the same way. The parameters will be set for the time the lockout is to start. The controller automatically calculates 2 hours from that setting. The options are similar to the
OFF | OFF | OFF | OFF | ||
020 = 2:00 a.m. | 080 | = 8:00 a.m. | 140 = 2:00 p.m. | 200 | = 8:00 p.m. |
023 = 2:30 a.m. | 083 | = 8:30 a.m. | 143 = 2:30 p.m. | 203 | = 8:30 p.m. |
030 = 3:00 a.m. | 090 | = 9:00 a.m. | 150 = 3:00 p.m. | 210 | = 9:00 p.m. |
033 = 3:30 a.m. | 093 | = 9:30 a.m. | 153 = 3:30 p.m. | 213 | = 9:30 p.m. |
040 = 4:00 a.m. | 100 | = 10:00 a.m. | 160 = 4:00 p.m. | 220 | = 10:00 p.m. |
043 = 4:30 a.m. | 103 | = 10:30 a.m. | 163 = 4:30 p.m. | 223 | = 10:30 p.m. |
050 = 5:00 a.m. | 110 = 11:00 a.m. | 170 = 5:00 p.m. | 230 | = 11:00 p.m. | |
053 = 5:30 a.m. | 113 = 11:30 a.m. | 173 = 5:30 p.m. | 233 | = 11:30 p.m. | |
060 = 6:00 a.m. | 120 | = 12:00 p.m. | 180 = 6:00 p.m. | 240* = 12:00 a.m. | |
063 = 6:30 a.m. | 123 | = 12:30 p.m. | 183 = 6:30 p.m. | 243* = 12:30 a.m. | |
070 = 7:00 a.m. | 130 | = 1:00 p.m. | 190 = 7:00 p.m. | 010 | = 1:00 a.m. |
073 = 7:30 a.m. | 133 | = 1:30 p.m. | 193 = 7:30 p.m. | 013 | = 1:30 a.m. |
080 = 8:00 a.m. | 140 | = 2:00 p.m. | 200 = 8:00 p.m. | 020 | = 2:00 a.m. |
|
|
| * Denotes not available. |
A lockout cannot be programmed to start at 12:00 a.m. or 12:30 a.m. due to conflicts with other internal programs. The defrost lockouts cannot be programmed to run
Follow the instructions to enter the customer access code on page 7. When the control
displays Thermostat Set High, press the down arrow keyuntil the control the
control display reads
or
. Press the set button SET .
The display will show
Off. Press the arrow keys to set the start time.
When the correct time is displayed, press the set button SET .
The display will then read Thermostat Set Point High.
You can press the up or down arrow keys to scroll to the next parameter
or wait 30 seconds for the control to return to normal operation.