Amana HRV-150D, HRV-200D, HRV-300D manual Option Supply/Return Method

Page 19

INSTALLATION EXAMPLES (CONT'D)

Example diagram only-duct configuration may change depending on model

DIRECT CONNECTION of both the HRV SUPPLY AIR STREAM &

EXHAUST AIR STREAM to the FURNACE COLD AIR RETURN & SUPPLY AIR SIDE

Simplified Installation

Option 2

(Supply/Return Method)

• HRV must be balanced

• It is recommended that the furnace blower run continuously or HRV operation

be interlocked with the furnace blower

• Check local codes /authority having jurisdiction for acceptance

Note: Option 1 is the pre- ferred/recommended method when doing a simplified installation

* Ducts connection may

Return Air

 

 

 

 

 

vary depending on model

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1m

Outdoors

 

 

 

 

 

(3’-3”) min.

 

 

 

 

 

 

 

 

 

recommended

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cool Air

Return

NOTES:

1.Furnace blower may be required to operate when ventilation from HRV/ERV is required. The furnace should be set to run continuously or interlocked with HRV/ERV.

2.The exhaust air connection should be upstream of the supply air connection to prevent exhausting any fresh air.

3.Weatherhood arrangement is for drawing purposes only. Six feet (2m) minimum separation recommended. Eighteen inches (460 mm) above grade minimum.

4.Due to the differences in pressure between the HRV/ERV and the equipment it is being connected to, the HR/ERV’s airflow must be confirmed on site, using the balancing procedure found in the installation manual.

1 m

(3’-3”) min.

recom-

mended

* Unit is

normally

balanced

on HIGH

speed

with

furnace

blower

ON.

19

Image 19
Contents Ventilators Table of Contents Air Quality Sensor FeaturesSpecifications Optional ControlsTH port for recirculation defrost models DimensionsFan Performance Performance Data AirflowDigital Multi-Function Control DmfcHRV-150 Fan PerformanceHRV-200 HRV-300D 5TH port for recirculation defrost Type models only Power Volts 120 VAC Amperage Amps Total Phase Single Phase91 % If the user wishes to stop the unit from Outside. The heat recovery ventiOperation Modes of OperationOptional Digital Control Operation ContdDmfc Operation Contd Optional Digital ControlClothes dryer Range top Stovetop fan Central vacuum system InstallationLocation MountingInstalling the Ducting To the Weatherhoods Installing Ducts Going to / from OutsideModel From HRV Installing Ducts to / from InsideSupply AIR Ducting Direct ConnectionFor new construction, the rigid ducts are run in the walls Installing Ducts to / from Inside ContdDedicated Installation for Existing Home Exhaust Air DuctingDucting Fifth Port Units Installation ExamplesPartially Dedicated System Installation Examples ContdOption Return/Return Method Simplified InstallationBe interlocked with the furnace blower Option Supply/Return Method Place pitot tube a minimum of 18 from blower elbows Pitot Tube Balancing ProcedureAir as so to increase the supply air’s temperature AIR Flow BalancingElectronic Balancing Motors HRV 150D & 200D only AIR Flow Balancing ContdFilters need to be checked regularly MaintenanceAny repairs or maintenance To Install the Clean Core and FiltersTroubleshooting Electrical Connections Low Voltage Control Wiring ConnectionsElectrical Connections Contd Page Page Canada United States