1 cfm = 0.47189 l/s

21 l/s = 3.6 m3/hr

Sizing (Example) for maximum airflow normally required.

HRVs are typically sized to ventilate the whole house at a minimum of 0.35 air changes per hour. To calculate, simply take the square footage of the house (including basement) and multi- ply by the height of the ceiling to get cubic volume. Then, divide by 60 and multiply by 0.35.

Example:

SQFT of House

1100

 

Basement

1100

 

Total SQFT

 

2200

 

Height of ceiling

 

 

x

8

 

Cubic volume

17600

 

 

/

60

 

Maximum airflow required (CFM)

 

 

293

 

 

x 0.35

 

 

 

 

103

* Always consult your local code for sizing requirements in your area.

Alternate Method

 

Room classification

Number of rooms

CFM (L/s)

 

CFM Required

 

 

 

 

 

 

 

Master bedroom

 

x 20 cfm (10 l/s)

=

 

 

 

 

 

 

Basement

yes or no

if yes add 20 cfm / 10 l/s

=

 

 

 

if no = 0

 

 

 

Bedrooms

 

x 10 cfm

(5 l/s)

=

 

 

 

 

 

 

 

Living room

 

x 10 cfm

(5 l/s)

=

 

 

 

 

 

 

 

Others

 

x 10 cfm

(5 l/s)

=

 

 

 

 

 

 

 

Kitchen

 

x 10 cfm

(5 l/s)

=

 

 

 

 

 

 

 

Bathroom

 

x 10 cfm

(5 l/s)

=

 

 

 

 

 

 

 

Laundry room

 

x 10 cfm

(5 l/s)

=

 

 

 

 

 

 

 

Utility room

 

x 10 cfm

(5 l/s)

=

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total Ventilation Requirements (add last column )

=

Image 2
Contents Ventilators Table of Contents Optional Controls FeaturesSpecifications Air Quality SensorAirflow DimensionsFan Performance Performance Data TH port for recirculation defrost modelsDmfc Digital Multi-Function ControlHRV-200 Fan PerformanceHRV-150 HRV-300D 91 % Power Volts 120 VAC Amperage Amps Total Phase Single Phase5TH port for recirculation defrost Type models only Modes of Operation Outside. The heat recovery ventiOperation If the user wishes to stop the unit fromOperation Contd Optional Digital ControlOperation Contd Optional Digital Control DmfcMounting InstallationLocation Clothes dryer Range top Stovetop fan Central vacuum systemModel Installing Ducts Going to / from OutsideInstalling the Ducting To the Weatherhoods Direct Connection Installing Ducts to / from InsideSupply AIR Ducting From HRVExhaust Air Ducting Installing Ducts to / from Inside ContdDedicated Installation for Existing Home For new construction, the rigid ducts are run in the wallsInstallation Examples Ducting Fifth Port UnitsInstallation Examples Contd Partially Dedicated SystemBe interlocked with the furnace blower Simplified InstallationOption Return/Return Method Option Supply/Return Method AIR Flow Balancing Pitot Tube Balancing ProcedureAir as so to increase the supply air’s temperature Place pitot tube a minimum of 18 from blower elbowsAIR Flow Balancing Contd Electronic Balancing Motors HRV 150D & 200D onlyTo Install the Clean Core and Filters MaintenanceAny repairs or maintenance Filters need to be checked regularlyTroubleshooting Low Voltage Control Wiring Connections Electrical ConnectionsElectrical Connections Contd Page Page United States Canada