Acme Kitchenettes PP-32 manual Vent Doors Operation, Vent Door Settings

Page 23

PP-32

5.5.2 Vent Door Settings

If a static pressure sensor is used, the PP-32 can control the static pressure in the room by opening and closing vent doors. When the pressure drops below the low pressure set point, the vent doors close according to a timer. Likewise, when the static pressure increases above the high pressure set point, the vent doors open according to a timer. It is also possible to define a stage level above which the vent doors will always remain closed. Refer to sec. 5.15.3 to activate the static pressure sensor.

 

 

VENT DOORS OPERATION

 

STATIC

 

 

 

PRESSURE

 

 

 

VENTDOORS

OPEN

 

STATIC PRESSURE

VENT DOORS STOP

 

EXCEEDS

OPENING

 

HI SET POINT:

 

STATIC PRESSURE

VENT DOORS OPEN IN

 

 

 

DROPS BELOW

 

 

 

TIMER CYCLE

 

 

 

LO SET POINT:

 

 

 

(OPEN TIME/ OFF TIME)

 

 

 

 

 

 

 

VENT DOORS CLOSE IN

 

 

HIGH SET POINT

 

TIMER CYCLE

 

 

 

(CLOSE TIME/ OFF TIME)

 

 

(OPEN AT)

 

 

 

 

VENT DOORS

STAY STILL

 

VENT DOORS STOP

 

 

CLOSING

 

LOW SET POINT

 

 

 

 

(CLOSE AT)

 

 

 

 

VENT DOORS

CLOSE

 

 

 

 

 

 

 

TIME

In minimum ventilation, the vent doors open during the pre-opening delay before fans start running. The same delay is used to close the vent doors when the stage 1 fans return to a stop.

Static Pressure Alarm: alarms can be set off if the static pressure remains below or exceeds a certain level for a too long period of time. In this case, a delay is set in order to activate the alarm: the alarm condition must maintained during this delay before the alarm is set off. Refer to section 5.13.2 to set the static pressure alarm settings.

KOOLMASTER PP-32 REV.01 23

Image 23
Contents PP-32 Page Table of Contents History Alarm SettingsInstallation Auxiliary Outputs Animal AGE Clock OutputsPP-32 Do not Spray Water on the Controller PrecautionsFeatures Password Protection Front Panel Location of the ControlsShortcut Keys Destination Connection Mounting InstructionsNot ground the shielding AlarmDWR-F-1A Communication Hookup DIP Switch Table Setting the DIP SwitchesStatic Pressure current static pressure in the barn Room Set Point this is the target temperature in the barnCurrent Conditions Selecting a Season Controller ProgramsSelecting a Program PP-32 Adjusting the Room SET Point Minimum Ventilation Minimum Ventilation TimerAdjusting Minimum Ventilations On-Time Adjusting Minimum Ventilations Cycle Time Setting DWR-F-1As ID numbers Inlet / Vent Door SettingsInlet Settings Potentiometer Feedback from Inlets Adjusting the Air Inlet Compensation Vent Doors Operation Vent Door SettingsGroups of Static Pressure SET Points Influenced by Ventilation StagesInfluenced by the Outside Temperature Adjusting Vent Doors Open / Close / Off Times Adjusting Static Pressure Set PointsVent Doors Timer 2.4 2nd Group of Pressure Set Points at Stage Adjusting Stage Level for the Closing of Vent Doors2.5 2nd Group of Pressure Set Points at Outside T PP-32 Tunnel Curtain Tunnel Curtain Timer ModeTunnel Curtain Controlled by the Static Pressure Tunnel to Vent Doors Vent Doors to TunnelSelecting the First Tunnel Stage Adjusting Minimum Age for Tunnel VentilationAdjusting Curtains Operating Times Adjusting Curtains Timer Cycle Adjusting Static Pressure Hi and Lo Set PointsCurtains Timer Operation of FAN Stages FAN Stages SettingsAdjusting Fans Stages Timer FAN Stages TimerAdjusting Fan Stages Start/Stop Temperatures PP-32 Operation of Heater Stages Heater SettingsAuxiliary Outputs Auxiliary Outputs in Heating ModeAuxiliary Outputs in Cooling Mode Adjusting Start/Stop Temperatures of Auxiliary Outputs Animal AGE Setting the Animal AgeOperation of Clock Outputs Clock OutputsStart Time / Stop Time Definition Operation of Clock Outputs 1Adjusting Clock Output Start and Stop Times Adjusting Starting Day of Clock Programs History Resetting HistoriesAverage Temperature History Relative Humidity History Individual Temperature Sensors HistoryOutside Temperature Sensor History Heater Run Time History Water Consumption HistoryPP-32 Alarm Log Alarm SettingsOustide Temperature Influence on Alarms Regular Temperature Alarm DetectionSetting Alarm Limits Adjusting Hi/ Lo Temperature Alarms Alarm Detection with Outside T InfluenceAdjusting the Outside Temperature Influence Adjusting Critical TemperatureHI Static Pressure Alarm Adjusting Static Pressure AlarmsLO Static Pressure Alarm Set the Lo Alarm Limit to Off to deactivate this featureAdjusting High/Low Delays Adjusting the Open-Time for the Hi Static Pressure Alarm Resetting the Alam LogStep-by-Step Installation Guide InstallationPP-32 Entering the Installers Password Password SettingsModifying the Installers Password Installation Setup 10.# of Inlets Auxiliary Output ModeUse Static Pressure ? Static Pressure Set17.# of Clock Programs for Clock Outputs 1 Use Outside Temperature Sensor ?Installer Password 16.# of Clock OutputsAssigning Sensors to the Room T and Fan Stages Sensor AssignmentAssigning Sensors to Air Inlets Assigning Sensors to Heater StagesAssigning Sensors to Auxiliary Outputs √√√ Relay Assignment Setting Time and DateAn empty template is available at the end of this manual Relay Assignment ExampleAssigning Fan Stages Relays Timer Relays on FAN StagesTo .7.2 to set the timers on and OFF time settings Assigning Vent Doors Open / Close Relays Assigning Heater Stages RelaysAssigning Relays to Vent Doors Assigning Curtains Open / Close Relays Assigning Relays to the Tunnel CurtainAssigning Relays to Auxiliary Outputs Assigning Relays to Clock OutputsAssigning Relays for the Lo Static Pressure Alarm Calibrating the Water Counter Setting the Temperature Curve Advanced SettingsTemperature Curve PP-32 Minimum Ventilation Curve Setting the Minimum Ventilation CurvePP-32 Humidity Control Adjusting Relative Humidity Set PointRH Compensation on Minimum Ventilation Humidity Compensation on MIN. VentilationHumidity Compensation on Heaters Adjusting Mist or Kool-Cel ShutoffAdjusting Heater Timer Cycle PP-32 Calibrating the Relative Humidity Sensor Calibrating SensorsCalibrating Room and Outside T Sensors Select 8.Vents/Static P from Calibrating the Static Pressure LevelTest Mode Technical Specifications Factory Settings Using the Configuration Module Start Configuration Press +/- to startContact Information Sensor Assignement Sensor Assignment Template see secInstallation Setup Template see sec Installation SetupRelay Assignment Template see sec ProcedureOUTPUT/ Relay # Index Installer password Keys see also buttons Setup

PP-32 specifications

The Acme Kitchenettes PP-32 is a versatile and compact solution for modern living spaces, ideal for those seeking functionality without sacrificing style. This kitchenette is perfect for apartments, studios, and locations with limited space, offering a blend of convenience and elegance.

One of the standout features of the PP-32 is its efficient layout. The kitchenette is designed with a compact footprint that maximizes usability while fitting easily into small areas. It includes essential components such as a sink, cooking surface, and storage, all seamlessly integrated to provide a fully functional cooking experience. The PP-32 comes equipped with a two-burner electric cooktop, allowing you to prepare meals with ease. This cooking surface is engineered for quick heating and energy efficiency, making it perfect for busy lifestyles.

The stainless steel sink is another significant aspect of the PP-32, designed to resist tarnishing and scratches while maintaining a sleek appearance. Its integrated faucet ensures that you have the water access needed for cooking or cleaning up. Additionally, the cabinetry includes ample storage space, featuring cabinets and drawers designed to hold cooking essentials, utensils, and pantry items. This storage solution is both functional and aesthetically pleasing, with a modern finish that complements any décor.

In terms of technology, the PP-32 incorporates advanced features that enhance its usability. The kitchenette is equipped with energy-efficient lighting that brightens the workspace while keeping energy consumption low. Additionally, the inclusion of easy-to-clean surfaces ensures that maintenance is simple, allowing for a tidy living environment.

The Acme Kitchenettes PP-32 also boasts a straightforward setup process, making it easy to install even in tight areas. With its thoughtful design and modern features, this kitchenette represents an ideal solution for those who value both efficiency and style in their living spaces.

In conclusion, the Acme Kitchenettes PP-32 provides a seamless blend of functionality, technology, and contemporary design. It caters to the needs of urban dwellers and those in smaller living setups, ensuring that cooking and meal preparation becomes an enjoyable experience. Whether for personal use or in rental properties, the PP-32 stands out as a reliable and attractive kitchenette option.