Acme Kitchenettes PP-32 manual Adjusting Start/Stop Temperatures of Auxiliary Outputs

Page 43

PP-32

Refer to the installation setup to activate the auxiliary outputs and to select either if they operate in heating or cooling mode (sec. 5.14.3).

Adjusting Start/Stop Temperatures of Auxiliary Outputs

-In heating mode, the stop temperature (Off Temp) must be at least 0.5°F (0.3°C) greater than the start temperature (On Temp).

-In cooling mode, the start temperature (OnTemp) must be at least 0.5°F (0.3°C) greater than the stop temperature (OffTemp).

Set the function to "10. Temp. Settings" from the main menu using the navigation buttons the. The current set point is displayed.

Press the down-arrow key to select the start temperature of the first auxiliary output (On T°). Note that this menu only appears if auxiliary outputs have been enabled during the installation setup (see sec. 5.14.3).

Set Point: 80.0°F

Start / Stop Temp

Aux. 1 On 80.0°F

Aux. 1 Off 80.5°F

Use the adjustment buttons to set start temperature to the desired value.

Press the down-arrow key once. The stop temperature is selected (Off Temp.).

Use the adjustment buttons to set stop temperature to the desired value.

Proceed in similar fashion for the other auxiliary output (if applicable).

KOOLMASTER PP-32 REV.01 43

Image 43
Contents PP-32 Page Table of Contents History Alarm SettingsInstallation Auxiliary Outputs Animal AGE Clock OutputsPP-32 Do not Spray Water on the Controller PrecautionsFeatures Password Protection Front Panel Location of the ControlsShortcut Keys Destination Connection Mounting InstructionsNot ground the shielding AlarmDWR-F-1A Communication Hookup DIP Switch Table Setting the DIP SwitchesCurrent Conditions Room Set Point this is the target temperature in the barnStatic Pressure current static pressure in the barn Selecting a Program Controller ProgramsSelecting a Season PP-32 Adjusting the Room SET Point Adjusting Minimum Ventilations On-Time Minimum Ventilation TimerMinimum Ventilation Adjusting Minimum Ventilations Cycle Time Inlet Settings Potentiometer Feedback from Inlets Inlet / Vent Door SettingsSetting DWR-F-1As ID numbers Adjusting the Air Inlet Compensation Vent Doors Operation Vent Door SettingsGroups of Static Pressure SET Points Influenced by Ventilation StagesInfluenced by the Outside Temperature Adjusting Vent Doors Open / Close / Off Times Adjusting Static Pressure Set PointsVent Doors Timer 2.4 2nd Group of Pressure Set Points at Stage Adjusting Stage Level for the Closing of Vent Doors2.5 2nd Group of Pressure Set Points at Outside T PP-32 Tunnel Curtain Tunnel Curtain Timer ModeTunnel Curtain Controlled by the Static Pressure Tunnel to Vent Doors Vent Doors to TunnelSelecting the First Tunnel Stage Adjusting Minimum Age for Tunnel VentilationAdjusting Curtains Operating Times Adjusting Curtains Timer Cycle Adjusting Static Pressure Hi and Lo Set PointsCurtains Timer Operation of FAN Stages FAN Stages SettingsAdjusting Fan Stages Start/Stop Temperatures FAN Stages TimerAdjusting Fans Stages Timer PP-32 Operation of Heater Stages Heater SettingsAuxiliary Outputs in Cooling Mode Auxiliary Outputs in Heating ModeAuxiliary Outputs Adjusting Start/Stop Temperatures of Auxiliary Outputs Animal AGE Setting the Animal AgeOperation of Clock Outputs Clock OutputsStart Time / Stop Time Definition Operation of Clock Outputs 1Adjusting Clock Output Start and Stop Times Adjusting Starting Day of Clock Programs Average Temperature History Resetting HistoriesHistory Outside Temperature Sensor History Individual Temperature Sensors HistoryRelative Humidity History Heater Run Time History Water Consumption HistoryPP-32 Alarm Log Alarm SettingsSetting Alarm Limits Regular Temperature Alarm DetectionOustide Temperature Influence on Alarms Adjusting Hi/ Lo Temperature Alarms Alarm Detection with Outside T InfluenceAdjusting the Outside Temperature Influence Adjusting Critical TemperatureHI Static Pressure Alarm Adjusting Static Pressure AlarmsLO Static Pressure Alarm Set the Lo Alarm Limit to Off to deactivate this featureAdjusting High/Low Delays Adjusting the Open-Time for the Hi Static Pressure Alarm Resetting the Alam LogStep-by-Step Installation Guide InstallationPP-32 Entering the Installers Password Password SettingsModifying the Installers Password Installation Setup 10.# of Inlets Auxiliary Output ModeUse Static Pressure ? Static Pressure Set17.# of Clock Programs for Clock Outputs 1 Use Outside Temperature Sensor ?Installer Password 16.# of Clock OutputsAssigning Sensors to the Room T and Fan Stages Sensor AssignmentAssigning Sensors to Air Inlets Assigning Sensors to Heater StagesAssigning Sensors to Auxiliary Outputs √√√ Relay Assignment Setting Time and DateAn empty template is available at the end of this manual Relay Assignment ExampleTo .7.2 to set the timers on and OFF time settings Timer Relays on FAN StagesAssigning Fan Stages Relays Assigning Relays to Vent Doors Assigning Heater Stages RelaysAssigning Vent Doors Open / Close Relays Assigning Curtains Open / Close Relays Assigning Relays to the Tunnel CurtainAssigning Relays to Auxiliary Outputs Assigning Relays to Clock OutputsAssigning Relays for the Lo Static Pressure Alarm Calibrating the Water Counter Temperature Curve Advanced SettingsSetting the Temperature Curve PP-32 Minimum Ventilation Curve Setting the Minimum Ventilation CurvePP-32 Humidity Control Adjusting Relative Humidity Set PointRH Compensation on Minimum Ventilation Humidity Compensation on MIN. VentilationAdjusting Heater Timer Cycle Adjusting Mist or Kool-Cel ShutoffHumidity Compensation on Heaters PP-32 Calibrating Room and Outside T Sensors Calibrating SensorsCalibrating the Relative Humidity Sensor Select 8.Vents/Static P from Calibrating the Static Pressure LevelTest Mode Technical Specifications Factory Settings Using the Configuration Module Start Configuration Press +/- to startContact Information Sensor Assignement Sensor Assignment Template see secInstallation Setup Template see sec Installation SetupRelay Assignment Template see sec ProcedureOUTPUT/ Relay # Index Installer password Keys see also buttons Setup

PP-32 specifications

The Acme Kitchenettes PP-32 is a versatile and compact solution for modern living spaces, ideal for those seeking functionality without sacrificing style. This kitchenette is perfect for apartments, studios, and locations with limited space, offering a blend of convenience and elegance.

One of the standout features of the PP-32 is its efficient layout. The kitchenette is designed with a compact footprint that maximizes usability while fitting easily into small areas. It includes essential components such as a sink, cooking surface, and storage, all seamlessly integrated to provide a fully functional cooking experience. The PP-32 comes equipped with a two-burner electric cooktop, allowing you to prepare meals with ease. This cooking surface is engineered for quick heating and energy efficiency, making it perfect for busy lifestyles.

The stainless steel sink is another significant aspect of the PP-32, designed to resist tarnishing and scratches while maintaining a sleek appearance. Its integrated faucet ensures that you have the water access needed for cooking or cleaning up. Additionally, the cabinetry includes ample storage space, featuring cabinets and drawers designed to hold cooking essentials, utensils, and pantry items. This storage solution is both functional and aesthetically pleasing, with a modern finish that complements any décor.

In terms of technology, the PP-32 incorporates advanced features that enhance its usability. The kitchenette is equipped with energy-efficient lighting that brightens the workspace while keeping energy consumption low. Additionally, the inclusion of easy-to-clean surfaces ensures that maintenance is simple, allowing for a tidy living environment.

The Acme Kitchenettes PP-32 also boasts a straightforward setup process, making it easy to install even in tight areas. With its thoughtful design and modern features, this kitchenette represents an ideal solution for those who value both efficiency and style in their living spaces.

In conclusion, the Acme Kitchenettes PP-32 provides a seamless blend of functionality, technology, and contemporary design. It caters to the needs of urban dwellers and those in smaller living setups, ensuring that cooking and meal preparation becomes an enjoyable experience. Whether for personal use or in rental properties, the PP-32 stands out as a reliable and attractive kitchenette option.