Acme Kitchenettes PP-32 manual Test Mode

Page 88

PP-32

5.15.5 Test Mode

A test mode allows you to simulate temperature changes and verify the controller's performance. In test mode, the temperature sensor inputs are turned off, allowing the user to change the temperature used by the controller to operate the stages. The controller operates as before using the new temperature settings.

Adjusting Room Temperature

When the room temperature is adjusted, the controller bypasses the tem- perature sensor inputs and uses the new value as a reference. The test mode is deactivated after 15 minutes of inactivity.

Set the function to "23.Test Mode" from the main menu using the navigation buttons then press the right-arrow key. The On/Off status of the test mode displayed.

Press to activate the test mode.

Press the down-arrow key to select the room temperature.

Use the adjustment buttons to set the room temperature to the desired value.

Test Mode

Mode On

Temp: 69.5 °F

Static Pressure .015

Fan Stage: Min.V

Program: (a)

The controller then displays the fan stage that is activated, in accordance with the selected temperature. It also displays the current program in use and the static pressure readings (if a static pressure sensor is used). These values are displayed as readings, they cannot be modified.

88KOOLMASTER PP-32 REV.01

Image 88
Contents PP-32 Page Table of Contents Alarm Settings InstallationAuxiliary Outputs Animal AGE Clock Outputs HistoryPP-32 Precautions Do not Spray Water on the ControllerFeatures Password Protection Location of the Controls Front PanelShortcut Keys Destination Mounting Instructions ConnectionAlarm Not ground the shieldingDWR-F-1A Communication Hookup Setting the DIP Switches DIP Switch TableCurrent Conditions Room Set Point this is the target temperature in the barnStatic Pressure current static pressure in the barn Selecting a Program Controller ProgramsSelecting a Season PP-32 Adjusting the Room SET Point Adjusting Minimum Ventilations On-Time Minimum Ventilation TimerMinimum Ventilation Adjusting Minimum Ventilations Cycle Time Inlet Settings Potentiometer Feedback from Inlets Inlet / Vent Door SettingsSetting DWR-F-1As ID numbers Adjusting the Air Inlet Compensation Vent Door Settings Vent Doors OperationInfluenced by Ventilation Stages Groups of Static Pressure SET PointsInfluenced by the Outside Temperature Adjusting Static Pressure Set Points Adjusting Vent Doors Open / Close / Off TimesVent Doors Timer Adjusting Stage Level for the Closing of Vent Doors 2.4 2nd Group of Pressure Set Points at Stage2.5 2nd Group of Pressure Set Points at Outside T PP-32 Tunnel Curtain Timer Mode Tunnel CurtainTunnel Curtain Controlled by the Static Pressure Vent Doors to Tunnel Tunnel to Vent DoorsAdjusting Minimum Age for Tunnel Ventilation Selecting the First Tunnel StageAdjusting Curtains Operating Times Adjusting Static Pressure Hi and Lo Set Points Adjusting Curtains Timer CycleCurtains Timer FAN Stages Settings Operation of FAN StagesAdjusting Fan Stages Start/Stop Temperatures FAN Stages TimerAdjusting Fans Stages Timer PP-32 Heater Settings Operation of Heater StagesAuxiliary Outputs in Cooling Mode Auxiliary Outputs in Heating ModeAuxiliary Outputs Adjusting Start/Stop Temperatures of Auxiliary Outputs Setting the Animal Age Animal AGEClock Outputs Start Time / Stop Time DefinitionOperation of Clock Outputs 1 Operation of Clock OutputsAdjusting Clock Output Start and Stop Times Adjusting Starting Day of Clock Programs Average Temperature History Resetting HistoriesHistory Outside Temperature Sensor History Individual Temperature Sensors HistoryRelative Humidity History Water Consumption History Heater Run Time HistoryPP-32 Alarm Settings Alarm LogSetting Alarm Limits Regular Temperature Alarm DetectionOustide Temperature Influence on Alarms Alarm Detection with Outside T Influence Adjusting Hi/ Lo Temperature AlarmsAdjusting Critical Temperature Adjusting the Outside Temperature InfluenceAdjusting Static Pressure Alarms LO Static Pressure AlarmSet the Lo Alarm Limit to Off to deactivate this feature HI Static Pressure AlarmAdjusting High/Low Delays Resetting the Alam Log Adjusting the Open-Time for the Hi Static Pressure AlarmInstallation Step-by-Step Installation GuidePP-32 Password Settings Entering the Installers PasswordModifying the Installers Password Installation Setup Auxiliary Output Mode Use Static Pressure ?Static Pressure Set 10.# of InletsUse Outside Temperature Sensor ? Installer Password16.# of Clock Outputs 17.# of Clock Programs for Clock Outputs 1Sensor Assignment Assigning Sensors to the Room T and Fan StagesAssigning Sensors to Heater Stages Assigning Sensors to Air InletsAssigning Sensors to Auxiliary Outputs √√√ Setting Time and Date Relay AssignmentRelay Assignment Example An empty template is available at the end of this manualTo .7.2 to set the timers on and OFF time settings Timer Relays on FAN StagesAssigning Fan Stages Relays Assigning Relays to Vent Doors Assigning Heater Stages RelaysAssigning Vent Doors Open / Close Relays Assigning Relays to the Tunnel Curtain Assigning Curtains Open / Close RelaysAssigning Relays to Clock Outputs Assigning Relays to Auxiliary OutputsAssigning Relays for the Lo Static Pressure Alarm Calibrating the Water Counter Temperature Curve Advanced SettingsSetting the Temperature Curve PP-32 Setting the Minimum Ventilation Curve Minimum Ventilation CurvePP-32 Adjusting Relative Humidity Set Point Humidity ControlHumidity Compensation on MIN. Ventilation RH Compensation on Minimum VentilationAdjusting Heater Timer Cycle Adjusting Mist or Kool-Cel ShutoffHumidity Compensation on Heaters PP-32 Calibrating Room and Outside T Sensors Calibrating SensorsCalibrating the Relative Humidity Sensor Calibrating the Static Pressure Level Select 8.Vents/Static P fromTest Mode Technical Specifications Factory Settings Using the Configuration Module Configuration Press +/- to start StartContact Information Sensor Assignment Template see sec Sensor AssignementInstallation Setup Installation Setup Template see secProcedure Relay Assignment Template see secOUTPUT/ Relay # Index Installer password Keys see also buttons Setup

PP-32 specifications

The Acme Kitchenettes PP-32 is a versatile and compact solution for modern living spaces, ideal for those seeking functionality without sacrificing style. This kitchenette is perfect for apartments, studios, and locations with limited space, offering a blend of convenience and elegance.

One of the standout features of the PP-32 is its efficient layout. The kitchenette is designed with a compact footprint that maximizes usability while fitting easily into small areas. It includes essential components such as a sink, cooking surface, and storage, all seamlessly integrated to provide a fully functional cooking experience. The PP-32 comes equipped with a two-burner electric cooktop, allowing you to prepare meals with ease. This cooking surface is engineered for quick heating and energy efficiency, making it perfect for busy lifestyles.

The stainless steel sink is another significant aspect of the PP-32, designed to resist tarnishing and scratches while maintaining a sleek appearance. Its integrated faucet ensures that you have the water access needed for cooking or cleaning up. Additionally, the cabinetry includes ample storage space, featuring cabinets and drawers designed to hold cooking essentials, utensils, and pantry items. This storage solution is both functional and aesthetically pleasing, with a modern finish that complements any décor.

In terms of technology, the PP-32 incorporates advanced features that enhance its usability. The kitchenette is equipped with energy-efficient lighting that brightens the workspace while keeping energy consumption low. Additionally, the inclusion of easy-to-clean surfaces ensures that maintenance is simple, allowing for a tidy living environment.

The Acme Kitchenettes PP-32 also boasts a straightforward setup process, making it easy to install even in tight areas. With its thoughtful design and modern features, this kitchenette represents an ideal solution for those who value both efficiency and style in their living spaces.

In conclusion, the Acme Kitchenettes PP-32 provides a seamless blend of functionality, technology, and contemporary design. It caters to the needs of urban dwellers and those in smaller living setups, ensuring that cooking and meal preparation becomes an enjoyable experience. Whether for personal use or in rental properties, the PP-32 stands out as a reliable and attractive kitchenette option.