Acme Kitchenettes PP-32 manual Adjusting Static Pressure Set Points

Page 26

PP-32

5.5.2.1Adjusting Static Pressure Set Points

When the high pressure set point is reached (Open at), the controller opens the vent doors according to a timer cycle. When the low pressure set point is reached (Close at), the controller closes the vent doors according to the another timer. The pressure set points can be adjusted from 0 to 0.2 inches of water (0 to 50Pa).

Select "8.Vents/Static P" from the main menu using the navigation buttons then press the right-arrow key. Note that this menu is only available if the static pressure sensor has been enabled during the installation setup (see sec 5.14.3).

Press the right-arrow key to select the "1.Set Points" menu.

Press the down-arrow key once, the

Vents/Static Press

LO static pressure set point is

Cal. SP

.000”WC

selected (Close At).

Close At:

.070”WC

 

Open At:

.090”WC

Use the adjustment buttons to

adjust the low static pressure set point (Close At) to the desired value then press the down-arrow key. The hi static pressure set point (Open At) is selected.

Use the adjustment buttons to adjust the hi static pressure set point (Open At) to the desired value.

5.5.2.2 Adjusting Vent Doors Open / Close / Off Times

When the static pressure level in the room exceeds the hi or low set points, the vent doors start opening or closing according to a cycle, as explained below:

Open Time: when the static pressure exceeds the Hi pressure set point, the vent doors open during this delay. The open time ranges from 0 to 900 seconds.

Close Time: when the static pressure drops below the Lo pressure set point, the vent doors close during this delay. The close time ranges from 0 to 900 seconds.

26KOOLMASTER PP-32 REV.01

Image 26
Contents PP-32 Page Table of Contents Auxiliary Outputs Animal AGE Clock Outputs Alarm SettingsInstallation HistoryPP-32 Precautions Do not Spray Water on the ControllerFeatures Password Protection Location of the Controls Front PanelShortcut Keys Destination Mounting Instructions ConnectionAlarm Not ground the shieldingDWR-F-1A Communication Hookup Setting the DIP Switches DIP Switch TableStatic Pressure current static pressure in the barn Room Set Point this is the target temperature in the barnCurrent Conditions Selecting a Season Controller ProgramsSelecting a Program PP-32 Adjusting the Room SET Point Minimum Ventilation Minimum Ventilation TimerAdjusting Minimum Ventilations On-Time Adjusting Minimum Ventilations Cycle Time Setting DWR-F-1As ID numbers Inlet / Vent Door SettingsInlet Settings Potentiometer Feedback from Inlets Adjusting the Air Inlet Compensation Vent Door Settings Vent Doors OperationInfluenced by Ventilation Stages Groups of Static Pressure SET PointsInfluenced by the Outside Temperature Adjusting Static Pressure Set Points Adjusting Vent Doors Open / Close / Off TimesVent Doors Timer Adjusting Stage Level for the Closing of Vent Doors 2.4 2nd Group of Pressure Set Points at Stage2.5 2nd Group of Pressure Set Points at Outside T PP-32 Tunnel Curtain Timer Mode Tunnel CurtainTunnel Curtain Controlled by the Static Pressure Vent Doors to Tunnel Tunnel to Vent DoorsAdjusting Minimum Age for Tunnel Ventilation Selecting the First Tunnel StageAdjusting Curtains Operating Times Adjusting Static Pressure Hi and Lo Set Points Adjusting Curtains Timer CycleCurtains Timer FAN Stages Settings Operation of FAN StagesAdjusting Fans Stages Timer FAN Stages TimerAdjusting Fan Stages Start/Stop Temperatures PP-32 Heater Settings Operation of Heater StagesAuxiliary Outputs Auxiliary Outputs in Heating ModeAuxiliary Outputs in Cooling Mode Adjusting Start/Stop Temperatures of Auxiliary Outputs Setting the Animal Age Animal AGEOperation of Clock Outputs 1 Clock OutputsStart Time / Stop Time Definition Operation of Clock OutputsAdjusting Clock Output Start and Stop Times Adjusting Starting Day of Clock Programs History Resetting HistoriesAverage Temperature History Relative Humidity History Individual Temperature Sensors HistoryOutside Temperature Sensor History Water Consumption History Heater Run Time HistoryPP-32 Alarm Settings Alarm LogOustide Temperature Influence on Alarms Regular Temperature Alarm DetectionSetting Alarm Limits Alarm Detection with Outside T Influence Adjusting Hi/ Lo Temperature AlarmsAdjusting Critical Temperature Adjusting the Outside Temperature InfluenceSet the Lo Alarm Limit to Off to deactivate this feature Adjusting Static Pressure AlarmsLO Static Pressure Alarm HI Static Pressure AlarmAdjusting High/Low Delays Resetting the Alam Log Adjusting the Open-Time for the Hi Static Pressure AlarmInstallation Step-by-Step Installation GuidePP-32 Password Settings Entering the Installers PasswordModifying the Installers Password Installation Setup Static Pressure Set Auxiliary Output ModeUse Static Pressure ? 10.# of Inlets16.# of Clock Outputs Use Outside Temperature Sensor ?Installer Password 17.# of Clock Programs for Clock Outputs 1Sensor Assignment Assigning Sensors to the Room T and Fan StagesAssigning Sensors to Heater Stages Assigning Sensors to Air InletsAssigning Sensors to Auxiliary Outputs √√√ Setting Time and Date Relay AssignmentRelay Assignment Example An empty template is available at the end of this manualAssigning Fan Stages Relays Timer Relays on FAN StagesTo .7.2 to set the timers on and OFF time settings Assigning Vent Doors Open / Close Relays Assigning Heater Stages RelaysAssigning Relays to Vent Doors Assigning Relays to the Tunnel Curtain Assigning Curtains Open / Close RelaysAssigning Relays to Clock Outputs Assigning Relays to Auxiliary OutputsAssigning Relays for the Lo Static Pressure Alarm Calibrating the Water Counter Setting the Temperature Curve Advanced SettingsTemperature Curve PP-32 Setting the Minimum Ventilation Curve Minimum Ventilation CurvePP-32 Adjusting Relative Humidity Set Point Humidity ControlHumidity Compensation on MIN. Ventilation RH Compensation on Minimum VentilationHumidity Compensation on Heaters Adjusting Mist or Kool-Cel ShutoffAdjusting Heater Timer Cycle PP-32 Calibrating the Relative Humidity Sensor Calibrating SensorsCalibrating Room and Outside T Sensors Calibrating the Static Pressure Level Select 8.Vents/Static P fromTest Mode Technical Specifications Factory Settings Using the Configuration Module Configuration Press +/- to start StartContact Information Sensor Assignment Template see sec Sensor AssignementInstallation Setup Installation Setup Template see secProcedure Relay Assignment Template see secOUTPUT/ Relay # Index Installer password Keys see also buttons Setup

PP-32 specifications

The Acme Kitchenettes PP-32 is a versatile and compact solution for modern living spaces, ideal for those seeking functionality without sacrificing style. This kitchenette is perfect for apartments, studios, and locations with limited space, offering a blend of convenience and elegance.

One of the standout features of the PP-32 is its efficient layout. The kitchenette is designed with a compact footprint that maximizes usability while fitting easily into small areas. It includes essential components such as a sink, cooking surface, and storage, all seamlessly integrated to provide a fully functional cooking experience. The PP-32 comes equipped with a two-burner electric cooktop, allowing you to prepare meals with ease. This cooking surface is engineered for quick heating and energy efficiency, making it perfect for busy lifestyles.

The stainless steel sink is another significant aspect of the PP-32, designed to resist tarnishing and scratches while maintaining a sleek appearance. Its integrated faucet ensures that you have the water access needed for cooking or cleaning up. Additionally, the cabinetry includes ample storage space, featuring cabinets and drawers designed to hold cooking essentials, utensils, and pantry items. This storage solution is both functional and aesthetically pleasing, with a modern finish that complements any décor.

In terms of technology, the PP-32 incorporates advanced features that enhance its usability. The kitchenette is equipped with energy-efficient lighting that brightens the workspace while keeping energy consumption low. Additionally, the inclusion of easy-to-clean surfaces ensures that maintenance is simple, allowing for a tidy living environment.

The Acme Kitchenettes PP-32 also boasts a straightforward setup process, making it easy to install even in tight areas. With its thoughtful design and modern features, this kitchenette represents an ideal solution for those who value both efficiency and style in their living spaces.

In conclusion, the Acme Kitchenettes PP-32 provides a seamless blend of functionality, technology, and contemporary design. It caters to the needs of urban dwellers and those in smaller living setups, ensuring that cooking and meal preparation becomes an enjoyable experience. Whether for personal use or in rental properties, the PP-32 stands out as a reliable and attractive kitchenette option.