b)Any conversion required must be performed by your dealer or a qualified licensed plumber or gas service company. Please provide the service person with this manual before work is started on the cooktop. (Gas conversions are the responsibility of the dealer or end user.)
c)This cooktop can be used with NATURAL or LP/PROPANE gas. It is shipped from the factory adjusted for use with NATURAL gas.
d)Manifold pressure should be checked with a manometer; NATURAL gas requires 4.0” W.C.P. and LP/PROPANE requires 11.0” W.C.P (see figure 5.4).
Incoming line pressure upstream from the regulator must be 1” W.C.P. higher than the manifold pressure in order to check the regulator.
The regulator used on this cooktop can withstand a maximum input pressure of 1/2 PSI (14.0” W.C.P). If the line pressure is in excess of that amount, a step- down regulator will be required.
| To cooktop |
Screw | Manifold |
| |
| test point |
| pressure |
| 1/8” NPT |
Unscrew |
|
| To mains |
| connection |
| Fig. 5.4 |
e)The appliance, its individual
f)The appliance must be isolated from the gas supply piping system by closing its individual manual
3. Flexible Connections:
If local codes permit, CSA
15