Multiquip DCA45USI2 manual Generator Outputs, Generator Output Voltages

Page 26

GENERATOR OUTPUTS

GENERATOR OUTPUT VOLTAGES

A wide range of voltages are available to supply voltage for many different applications.Voltages are selected by using the voltage selector switch (Figure 13). To obtain some of the voltages as listed in Table 7 (see below) will require a

ne adjustment using the voltage regulator (VR) control knob located on the control panel.

Voltage Selector Switch

The voltage selector switch (Figure 13) is located above the output terminal panel’s Hard Wire Hook-up Panel. It has been provided for ease of voltage selection.

Generator Amperage

Table 8 shows the maximum amps the generator can provide. DO NOT exceed the maximum amps as listed..

Table 8. Generator Maximum Amps

Rated Voltage

Maximum Amps

 

 

1Ø 120 Volt

100 amps (4 wire)

108A x 2 (Zigzag)

 

1Ø 240 Volt

50 amps (4 wire)

108A (Zigzag)

 

3Ø 240 Volt

108 amps

 

 

3Ø 480 Volt

54 amps

 

 

Figure 13. Voltage Selector Switch

Voltage Selector Switch Locking Button

To lock the voltage selector switch, press and hold the red button located at the bottom of the switch. While holding the red button down, insert a pad lock into the hole next to the button to retain it in the inward locked position. When the lock is removed, the red button is spring loaded and will return to its normal outward unlocked position.

CAUTION

NEVER change the position of the voltage selector switch while the engine is running. ALWAYS place circuit breaker in the OFF position before selecting voltage.

Table 7. Voltages Available

UVWO Output

Voltage Selector Switch

Voltage Selector Switch

Terminal Lugs

3-Phase 240/139V Position

3-Phase 480/270V Position

 

 

 

 

 

 

 

Line-Line

208V

220V

240V

416V

440V

480V

 

 

 

 

 

 

 

Line-Neutral

120V

127V

139V

240V

254V

277V

 

 

 

 

 

 

 

Voltage Selector Switch Single-Phase 240/120V Position

 

 

 

 

 

 

 

 

Line-Neutral/

120V

N/A

N/A

240V

N/A

N/A

Line-Line

Line-Neutral

Line-Line

 

 

 

 

 

 

 

 

 

 

 

GFCI Receptacle Load Capability

The load capability of the GFCI receptacles is directly related to the voltage being supplied at either the output terminals or the 2 twist lock auxiliary receptacles.

Table 9 and Table 10 show what amount of current is available at the GFCI receptacles when the output terminals and twist lock receptacles are in use. Be careful that your load does not to exceed the available current capability at the receptacles.

Table 9. 1Ø GFCI Receptacle Load Capacity

KW in Use

Available Load

Twist Lock (C6369)

Current (Amps)

1Ø 240/120V

GFCI Duplex

5-20R 120V

 

26.0

0 amps/receptacle

24.8

5 amps/receptacle

23.6

10 amps/receptacle

 

 

22.4

15 amps/receptacle

 

 

21.2

20 amps/receptacle

 

 

Table 10. 3Ø Generator Maximum Amps

KVA in Use

Available Load

(UVWO Terminals)

Current (Amps)

3Ø 240/480V

GFCI Duplex

5-20R 120V

 

45.0

0 amps/receptacle

 

 

40.9

5 amps/receptacle

 

 

36.7

10 amps/receptacle

 

 

32.6

15 amps/receptacle

 

 

28.4

20 amps/receptacle

 

 

PAGE 26 — DCA45USI2 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #0 (01/12/11)

Image 26
Contents Model DCA45USI2 This Manual Must Accompany the Equipment AT ALL TimesProposition 65 Warning Nhtsa Reporting Safety DefectsAdministrator Table of Contents DCA45USI2 GeneratorParts Ordering Procedures Ordering parts has never been easierSafety Information Safety Messages Always know the location of the nearest General SafetyGenerator Safety Engine Safety Before servicing equipment Never use fuel as a cleaning agent Fuel SafetyTowing Safety From fuel vapors or if fuel is spilled on a hot enginePower Cord/Cable Safety Electrical SafetyGrounding Safety Device. All installations should beBattery Safety Environmental SafetyIsuzu BU-4JJ1T Tier SpecificationsDCA-45USI2 Dimensions DimensionsInstallation Typical Generator Grounding ApplicationMounting Outdoor InstallationIndoor Installation Generator GroundingGeneral Information Muffl er Assembly Major ComponentsGenerator Control Panel OFFPage Engine Operating Panel OFFEngine Operating Panel Terminal legs O and Ground are considered bonded grounds Output Terminal Panel FamiliarizationOutput Terminal Familiarization Removing the Plastic Face Plate Hard Wire Hookup Panel VAC Gfci ReceptaclesConnecting Loads Over Current RelayLoad Application Single Phase LoadThree Phase Load Generator Outputs Generator Output VoltagesAC Voltmeter Gauge Reading HOW to Read the AC Ammeter and AC Voltage GaugesGenerator OUTPUTS/GAUGE Reading AC Ammeter Gauge Reading3Ø-240/139 Uvwo Terminal Output Voltages Output Terminal Panel ConnectionsUvwo Terminal Output Voltages 3Ø-208V/1Ø-120V Uvwo Terminal Output Voltages3Ø-480/277V Uvwo Terminal Output Voltages 1Ø-240/120V Uvwo Terminal Output VoltagesLubrication OIL INSPECTION/SETUPCircuit Breakers Fuel CheckRefueling Procedure Only use #2 diesel fuel when refuelingCoolant ANTIFREEZE/SUMMER COOLANT/ Water Cleaning the RadiatorAIR Cleaner FAN Belt Tension Operation Freezing WeatherWiring BatteryBattery Cable Installation AlternatorStarting Generator START-UP ProcedureBefore Starting Starting ManualEngine Speed Switch High Emergency Shutdown Procedure Generator SHUT-DOWN ProceduresNormal Shutdown Procedure Place the Mpec Control Switch in the OFF/RESET positionAir Cleaner with Dust Indicator MaintenanceGeneral Inspection AIR Cleaner AIR Removal Fuel AdditionFuel Tank Inspection Replacing Oil Filter Radiator CleaningCheck OIL Level Flushing OUT Radiator and Replacing CoolantCoupler Type of hitch used on the trailer for towing Trailer MaintenanceTrailer Maintenance Hydraulic Surge Brakes Brake AdjustmentBrakes ActuatorSuspension TIRES/WHEELS/LUG NutsTire Wear/Inflation Lug Nut Torque Requirements Never use an pneumatic air gun to tighten wheel lug nutsTrailer Wiring Diagram Trailer/Towing Vehicle Wiring DiagramGenerator Wiring Diagram Generator Wiring DiagramEngine Wiring Diagram Engine Wiring DiagramController Wiring Diagram Engine ControllerTroubleshooting Generator Troubleshooting Diagnostic Lamp Method of OperationSample Parts List Explanation of Code in Remarks ColumnSuggested Spare Parts To 3 unitsGenerator Assy Rectifier Balancing WeightRotor Assy Field Assy ZNRControl BOX Assy Control BOX Push Button SwitchDiagnostic Switch EdgingControl BOX Assy Switch Cover Selector SwitchSwitch Bracket BRACKET, SensorControl BOX Assy SWITCH, Panel Light SwitchAlarm Lamp SWITCH, Engine SpeedEngine and Radiator Assy INDICATOR, AIR Cleaner AIR CleanerELEMENT, AIR Cleaner BRACKET, AIR CleanerEngine and Radiator Assy Locknut ConnectorElbow ValveOutput Terminal Assy TIE Screw Terminal PanelOutput Terminal Bolt Terminal CoverBattery Assy Battery Band BatteryBattery Sheet Battery Bolt SETMuffler Assy Exhaust Pipe MufflerHEX Head Bolt Seal ClampFuel Tank Assy Fuel Sender Unit Fuel TankFuel Tank CAP GasketEnclosure Assy Environmental Tank BaseAcoustic Sheet Front FrameEnclosure Assy Door Handle ASS Y Rear DoorWindow Plate Roof PanelRubber Seals Assy Seal Rubber Nameplate and Decals Assy M1550000804 M1550000204M1550000703 M1550001504Terms and Conditions of Sale Parts Freight PolicyPage HERE’S HOW to GET Help

DCA45USI2 specifications

The Multiquip DCA45USI2 is a robust and versatile generator that caters to a wide array of power needs across various applications. Designed for both commercial and industrial use, this generator stands out due to its powerful output, durability, and advanced technology.

The DCA45USI2 offers a maximum output of 45 kVA, making it suitable for both demanding construction sites and as a backup power source for critical equipment in emergencies. It operates with a reliable Yanmar diesel engine, known for its fuel efficiency and longevity, ensuring that users can count on consistent performance over extended periods. The unit is built to provide high-quality electrical output, ensuring that sensitive equipment is protected from surges and fluctuations.

One of the standout features of the DCA45USI2 is its sound attenuation technology. Enclosed within a sturdy yet compact frame, this generator is designed to minimize noise levels, making it an ideal choice for urban environments or noise-sensitive applications. The insulation materials used are specifically chosen to absorb sound waves while still allowing for efficient ventilation.

In terms of ease of use, the DCA45USI2 is equipped with a user-friendly control panel that provides comprehensive monitoring capabilities. This includes advanced protective features, such as low oil pressure shutdown, high-temperature shutdown, and overload protection, ensuring that the generator operates safely at all times. The digital display offers real-time information on vital operating parameters, enabling operators to swiftly respond to any issues that may arise.

Another key characteristic of the DCA45USI2 is its portability. Weighing in at a manageable level for its size and capacity, it features heavy-duty wheels and a lifting eye which allow for easy transportation across job sites. This adaptability is crucial for rental companies and contractors who require a reliable source of power on-the-go.

Overall, the Multiquip DCA45USI2 embodies a blend of power, efficiency, and convenience. Its advanced engineering and thoughtful design cater to the needs of various industries, making it a preferred choice among professionals who demand reliability and performance from their equipment. Whether for construction, emergency response, or temporary power solutions, the DCA45USI2 proves to be a formidable ally in getting the job done efficiently and effectively.