Multiquip DCA125SSIU manual Load Application, Single Phase Load, Three Phase Load

Page 25

LOAD APPLICATION

SINGLE PHASE LOAD

Always be sure to check the nameplate on the generator and equipment to insure the wattage, amperage, frequency, and voltage requirements are satisfactorily supplied by the generator for operating the equipment.

Generally, the wattage listed on the nameplate of the equipment is its rated output. Equipment may require 130—150% more wattage than the rating on the nameplate, as the wattage is infl uenced by the effi ciency, power factor and starting system of the equipment.

NOTICE

If wattage is not given on the equipment’s name plate, approximate wattage may be determined by multiplying nameplate voltage by the nameplate amperage.

WATTS = VOLTAGE x AMPERAGE

The power factor of this generator is 0.8. See Table 5 below when connecting loads.

Table 5. Power Factor By Load

 

Type of Load

 

 

Power Factor

Single-phase induction motors

 

 

0.4-0.75

 

 

 

 

Electric heaters, incandescent lamps

 

1.0

 

Fluorescent lamps, mercury lamps

 

0.4-0.9

Electronic devices, communication

 

1.0

 

equipment

 

 

 

 

 

 

 

 

 

 

 

 

Common power tools

 

 

 

0.8

 

 

 

 

 

 

 

 

 

 

Table 6. Cable Selection (60 Hz, Single Phase Operation)

 

 

 

 

 

 

 

 

Current

Load in Watts

Maximum Allowable Cable Length

 

 

 

 

 

 

 

 

in

At 100

At 200

#10 Wire

#12 Wire

#14 Wire

 

#16 Wire

Amperes

 

Volts

Volts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.5

300

600

1000 ft.

600 ft.

375 ft.

 

250 ft.

 

 

 

 

 

 

 

 

 

5

600

1200

500 ft.

300 ft.

200 ft.

 

125 ft.

 

 

 

 

 

 

 

 

 

7.5

900

1800

350 ft.

200 ft.

125 ft.

 

100 ft.

 

 

 

 

 

 

 

 

 

10

1200

2400

250 ft.

150 ft.

100 ft.

 

 

 

 

 

 

 

 

 

 

 

15

1800

3600

150 ft.

100 ft.

65 ft.

 

 

 

 

 

 

 

 

 

 

 

20

2400

4800

125 ft.

75 ft.

50 ft.

 

 

 

 

 

 

 

 

 

 

 

 

CAUTION: Equipment damage can result from low voltage

 

 

 

 

 

 

 

 

 

 

THREE PHASE LOAD

When calculating the power requirements for 3-phase power use the following equation:

NOTICE

If 3Ø load (kVA) is not given on the equipment nameplate, approximate 3Ø load may be determined by multiplying voltage by amperage by 1.732.

NOTICE

Motors and motor-driven equipment draw much greater current for starting than during operation.

An inadequate size connecting cable which cannot carry the required load can cause a voltage drop which can burn out the appliance or tool and overheat the cable. See Table 6.

When connecting a resistance load such as an incandescent lamp or electric heater, a capacity of up to the generating set’s rated output (kW) can be used.

When connecting a fl uorescent or mercury lamp, a capacity of up to the generating set’s rated output (kW) multiplied by 0.6 can be used.

When connecting an electric drill or other power tools, pay close attention to the required starting current capacity.

When connecting ordinary power tools, a capacity of up to the generating set’s rated output (kW) multiplied by 0.8 can be used.

DANGER

Before connecting this generator to any building’s electrical system, a licensed electrician must install an isolation (transfer) switch. Serious damage to the building’s electrical system may occur without this transfer switch.

DCA125SSIU 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #3 (01/13/11) — PAGE 25

Image 25
Contents This Manual Must Accompany the Equipment AT ALL Times Model DCA125SSIUProposition 65 Warning Administrator Reporting Safety DefectsDCA125SSIU Generator Table of ContentsOrdering parts has never been easier Parts Ordering ProceduresSafety Messages Safety InformationGenerator Safety General Safety Always know the location of the nearest Before servicing equipment Engine SafetyTowing Safety Fuel Safety Never use fuel as a cleaning agent From fuel vapors or if fuel is spilled on a hot engineGrounding Safety Electrical SafetyPower Cord/Cable Safety Device. All installations should beEnvironmental Safety Battery SafetyDCA-125SSIU SpecificationsDimensions DimensionsTypical Generator Grounding Application InstallationIndoor Installation Outdoor InstallationMounting Generator GroundingGeneral Information Major Components AssemblyOwing from the U,V, and W Output Terminal Lugs to the load Generator Control PanelPage Engine Operating Panel Engine Operating PanelFuel Gauge Indicates amount of diesel fuel available Engine Speed Switch This switch controls the speedOutput Terminal Familiarization Output Terminal Panel FamiliarizationTerminal legs O and Ground are considered bonded grounds 240V Twist-Lock Auxiliary Receptacles VAC Gfci ReceptaclesOver Current Relay Connecting LoadsThree Phase Load Single Phase LoadLoad Application Generator Output Voltages Generator OutputsReading Voltage Generator OUTPUTS/GAUGE ReadingReading Amperage Uvwo Terminal Output Voltages Output Terminal Panel Connections3Ø-240/139 Uvwo Terminal Output Voltages 3Ø-208V/1Ø-120V Uvwo Terminal Output Voltages1Ø-240/120V Uvwo Terminal Output Voltages 3Ø-480/277V Uvwo Terminal Output VoltagesCircuit Breakers INSPECTION/SETUPLubrication OIL Fuel CheckOnly use #2 diesel fuel when refueling Refueling ProcedureAIR Cleaner FAN Belt Tension Cleaning the RadiatorCoolant ANTIFREEZE/SUMMER COOLANT/ Water Operation in Freezing WeatherBattery Cable Installation BatteryWiring AlternatorPlace the engine speed switch in the LOW down position Generator START-UP Procedure ManualBefore Starting Starting ManualFrequency Meter Starting Auto Mode Generator START-UP Procedure Auto ModeNormal Shutdown Procedure Generator SHUT-DOWN ProceduresEmergency Shutdown Procedure Never stop the engine suddenly except in an emergencyGeneral Inspection AIR Cleaner MaintenanceAir Cleaner with Dust Indicator Fuel Tank Inspection Fuel AdditionAIR Removal Check OIL Level Radiator CleaningReplacing Oil Filter Flushing OUT Radiator and Replacing CoolantBattery Charger and Jacket Water Heater Power Connections Trailer Maintenance Trailer MaintenanceCoupler Type of hitch used on the trailer for towing Brakes Brake AdjustmentHydraulic Surge Brakes ActuatorTire Wear/Inflation TIRES/WHEELS/LUG NutsSuspension Start all wheel lug nuts by hand Lug Nut Torque RequirementsTighten each lug nut in 3 separate passes as defi ned Never use an pneumatic air gun to tighten wheel lug nutsTrailer/Towing Vehicle Wiring Diagram Trailer Wiring DiagramGenerator Wiring Diagram Generator Wiring DiagramEngine Wiring Diagram Engine Wiring DiagramController Wiring Diagram Controller Wiring DiagramTroubleshooting Generator Troubleshooting Engine Controller Method of Operation Troubleshooting Diagnostic LampPage Explanation of Code in Remarks Column Sample Parts ListTo 3 units Suggested Spare PartsGenerator Assy 8131070013 C01100010028131611014 8131015003Control BOX Assy 0330000210 M32130017020330000280 0330000180Control BOX Assy 5825500290 00271060168970119490 M3213500604Control BOX Assy M9220100004 00271050100080200007 0602122272Engine and Radiator Assy 8980527130 M3923200134M3303200603 0010310025Engine and Radiator Assy 0269200600 0602021070M3323500004 0016910025Output Terminal Assy M9220100304 M3230700003M9220100404 0039316000Battery Assy M9310500404 0602220198M9103000504 0602220921Muffler Assy M3333001403 M33301009021141451840 M3333200004Fuel Tank Assy 0605505070 M33630020020605501076 0605516090Enclosure Assy M1413400004 M3413002402M3423002702 M3493114303Enclosure Assy M3443600104 M34432007030037906000 36A 0041206000Enclosure Assy M3453700004 060080032066A M9116100004 M9110100304Rubber Seals Assy 0228900880 02292011000228900990 0228901050Nameplate and Decals Assy M35000300A M3550003003M9520100304 M92010030Nameplate and Decals Assy M9500500104 M9500500004M9510200002 060050090Freight Policy Terms and Conditions of Sale PartsPage HERE’S HOW to GET Help
Related manuals
Manual 88 pages 9.93 Kb

DCA125SSIU specifications

The Multiquip DCA125SSIU is a robust and versatile diesel generator that is designed to meet the power needs of various applications, from construction sites to events and emergency situations. With a power output of 125 kVA, this generator combines efficiency and reliability, making it an ideal choice for professionals who demand optimal performance in challenging environments.

One of the primary features of the DCA125SSIU is its industrial-grade a diesel engine. This engine not only delivers impressive power but also emphasizes fuel efficiency. The generator is equipped with advanced fuel management technologies that help minimize consumption while maximizing output, making it cost-effective for long-term use.

In terms of durability, the DCA125SSIU is built with a sturdy enclosure that protects it from environmental factors. The weather-resistant design ensures that it operates effectively in a variety of weather conditions, ensuring reliable performance when needed the most. Additionally, its compact size allows for easy transport and storage, which is particularly beneficial for contractors and rental companies.

The DCA125SSIU features a user-friendly control panel that provides essential information at a glance. This panel includes gauges for monitoring key parameters such as voltage, frequency, and hours of operation. It also has an automatic voltage regulator (AVR) that maintains consistent voltage output, safeguarding connected equipment from potential damage caused by power fluctuations.

Safety is a priority with the DCA125SSIU, as it is equipped with several emergency shutdown features. These include low oil pressure, high temperature, and overload protection, ensuring that the generator operates safely under all conditions. Further enhancing its operational reliability, the generator comes with a built-in fuel tank that allows for extended runtime, reducing the frequency of refueling during use.

In summary, the Multiquip DCA125SSIU is a powerful, durable, and efficient diesel generator that meets the diverse power needs of various industries. Its combination of a high-performance engine, user-friendly control panel, robust safety features, and fuel efficiency makes it an exceptional choice for anyone looking for a reliable power solution. Whether for temporary power during events, backup for critical systems, or support at construction sites, the DCA125SSIU is engineered to perform.