Multiquip operation manual GA-3.6RZ3 Installation, Outdoor Installation, Indoor Installation

Page 11

Outdoor Installation

Install the generator in a location where it will not be exposed to rain or sunshine. Make sure that the generator is on secure level ground so that it cannot slide or shift around. Also install the generator in a manner so that the exhaust will not be discharged in the direction of nearby homes.

The installation site must be relatively free from moisture and dust. All electrical equipment should be protected from excessive moisture.Failure to do will result in deterioration of the insulation and will result in short circuits and grounding.

Foreign materials such as dust, sand, lint and abrasive materials have a tendency to cause excessive wear, not only to the engine parts, but also to the alternator parts.

GA-3.6RZ3 — INSTALLATION

Indoor Installation

Exhaust gases from gasoline engines are extremely poisonous. Whenever an engine is installed indoors the exhaust fumes must be vented to the outside. The engine should be installed at least two feet from any outside wall. Using an exhaust pipe which is too long or too small can cause excessive back pressure which will cause the engine to heat excessively and possibly burn the valves.

Eliminate the danger of deadly carbon monoxide gas. Remember that exhaust fumes from any gasoline engine are very poisonous if discharged in a closed room, but harmless if allowed to mix with the outside air.If the generator is installed indoors, you must make provisions for venting the engine exhaust to the outside of the building.

CAUTION :CAUTION :

Pay close attention to ventilation when operating the generator inside tunnels and caves. The engine exhaust contains noxious elements.

An electric shock is apt to happen when vibrators are used. Pay close attention to handling when operating vibrators and always use rubber boots and gloves to insulate the body from a short circuit.

GA-3.6RZ3 A.C. GENERATOR — PARTS & OPERATION MANUAL — REV. #3 (09/03/04) — PAGE 11

Image 11
Contents Multiquip Page Heres HOW to GET Help Table of Contents UPS Ground Service at no charge for freight Parts Ordering ProceduresEmergencies Maintenance SafetyRules for Safe Operation Machine Safety Decals Operation and Safety DecalsSpecifications GA-3.6RZ3 General Information Controls and Indicators GA-3.6RZ3 Controls and IndicatorsIndoor Installation GA-3.6RZ3 InstallationOutdoor Installation Ground GA-3.6RZ3 PRE-SETUPGeneral Inspection Prior to Operation Circuit BreakerFuel Lubrication OilGA-3.6RZ3 Instrumentation Power OutletsStart Switch Full Power SwitchGA-3.6RZ3 Load Application Before Starting GA-3.6RZ3 Operating InstructionsSpark Plug Gap GA-3.6RZ3 MaintenanceGenerator Storage GA-3.6RZ3 Preparation for Long -TERM StorageGenerator Engine GA-3.6RZ3 -WIRING DiagramEngine Troubleshooting Symptom Possible Problem Solution GA-3.6RZ3 -TROUBLESHOOTING EngineGA-3.6RZ3 -TROUBLESHOOTING Engine GA-3.6RZ3 -TROUBLESHOOTING Generator GA-3.6RZ3 -TROUBLESHOOTING Generator Items Found In the Items Number Column GA-3.6RZ3 Explanation of Code in Remarks ColumnTo 5 Units To 10 Units GA-3.6RZ3 Suggested Spare PartsGA-3.6RZ3 Generator Assy Bearing GA-3.6RZ3 Control BOX Assy Replaces GA-3.6RZ3 Pipe Frame Assy Bracket GA-3.6RZ3 Name Plate and Decals See Decal Illustrations on Robin EH-25 Engine Crankcase Assy Part Name QTY Remarks Robin EH-25 Engine Crankshaft & Piston Assy NUT Robin EH-25 Engine Intake & Exhaust Assy Tappet Robin EH-25 Engine Governor Assy Governor ROD Robin EH-25 Engine Cooling & Starting Assy Label Trade Mark Robin EH-25 Engine Carburetor Assy Hose Clamp Robin EH-25 Engine Ignition Coil ASSY. and Spark Plug FLY Wheel Robin EH-25 Engine Fuel Strainer Robin EH-25 Engine Fuel Strainer Freightpolicy Terms and Conditions of Sale PartsPage Denyo Manufacturing CO., Japan Multiquip INC