Multiquip operation manual GA-3.6RZ3 Operating Instructions, Before Starting

Page 16

GA-3.6RZ3 — OPERATING INSTRUCTIONS

Before Starting

1.Be sure to disconnect the electrical load and switch the main circuit breaker to the “OFF” position prior to starting the engine.

2.Never start the engine with the main circuit breaker “ON”.

3.Check the lubricating oil level prior to starting the engine. Make sure the generator is level. The oil level must be maintained between two notches on the dipstick.

4.When there is not enough lubricating oil, fill the crankcase with high grade motor oil. Use a high quality detergent oil classified SC, SD or SE. (See Table 3 on page 13)

CAUTION:

zNEVER start the engine when the oil level is below the lower mark on the dipstick.

zCheck the fuel level on the fuel gauge. When fuel is low, fill the fuel tank with clean fresh unleaded automotive gasoline.

zIf gasoline spillage occurs, completely wipe up the spilled gasoline.

Starting

1.Open the fuel cock located below the fuel tank.The fuel starts to flow when the fuel cock lever is turned downward.

2.Place the idle control switch in the “ON” (up) position.

3.Close the choke. Adjust the opening of the choke valve according to operating conditions. When the engine is warm or the air temperature is high, close the choke valve halfway or open it all the way.

4.Confirm that the main circuit breaker on the generator control box is “OFF”.

5.Set the operation switch to the “ON” position and grasp the starting knob and slowly pull it out. The resistance becomes hardest at a certain position, corresponding to the compression point. Rewind the rope a little from that point and pull out sharply.

6.If the engine fails to start, repeat the procedure.

CAUTION: z DO NOT pull the starter rope all the way to the end.

zDO NOT release the starter knob after pulling. Allow it to rewind as soon as

Warm up

1.When the engine starts, open the choke slowly.

2.Run the engine at low speed for 3 minutes without load until the engine warms up.

3.Turn the idle control switch to the "OFF" (down) position and check the voltage by referring to the voltmeter on the control box.

CAUTION:

DO NOT change the engine speed control lever which has been set at the factory prior to shipping.

1.Check the generator for abnormal noise and smells.Then connect the load to the receptacles of the generator.

2.Switch the main circuit breaker to the “ON” position and turn the idle control switch to the “ON” (down) position for normal (load) engine operation.

Operation

Check the voltage by referring to the voltmeter on the control box. When the voltmeter indicates 120 volts, 120 volts from the 120V receptacle can be obtained. Refer to Figure 1, Controls and Indicators, item 5 on page 10.

Stopping the Engine

CAUTION:

NEVER stop the engine suddenly while running at high speeds.

1.Remove the load from the generator. Place the circuit breaker in the “OFF” position. Refer to Figure 1, item 3 on page 10. Run the engine (no-load) with the idle control switch set to the ON position for three to five minutes, then stop the engine.

2.Turn the START/STOP switch to the “STOP” position.

3.Close the fuel cock.

PAGE 16 — GA-3.6RZ3 A.C. GENERATOR— PARTS & OPERATION MANUAL — REV. #3 (09/03/04)

Image 16
Contents Multiquip Page Heres HOW to GET Help Table of Contents Parts Ordering Procedures UPS Ground Service at no charge for freightRules for Safe Operation Maintenance SafetyEmergencies Operation and Safety Decals Machine Safety DecalsSpecifications GA-3.6RZ3 General Information GA-3.6RZ3 Controls and Indicators Controls and IndicatorsOutdoor Installation GA-3.6RZ3 InstallationIndoor Installation GA-3.6RZ3 PRE-SETUP General Inspection Prior to OperationCircuit Breaker GroundLubrication Oil FuelPower Outlets Start SwitchFull Power Switch GA-3.6RZ3 InstrumentationGA-3.6RZ3 Load Application GA-3.6RZ3 Operating Instructions Before StartingGA-3.6RZ3 Maintenance Spark Plug GapGA-3.6RZ3 Preparation for Long -TERM Storage Generator StorageGA-3.6RZ3 -WIRING Diagram Generator EngineGA-3.6RZ3 -TROUBLESHOOTING Engine Engine Troubleshooting Symptom Possible Problem SolutionGA-3.6RZ3 -TROUBLESHOOTING Engine GA-3.6RZ3 -TROUBLESHOOTING Generator GA-3.6RZ3 -TROUBLESHOOTING Generator GA-3.6RZ3 Explanation of Code in Remarks Column Items Found In the Items Number ColumnGA-3.6RZ3 Suggested Spare Parts To 5 Units To 10 UnitsGA-3.6RZ3 Generator Assy Bearing GA-3.6RZ3 Control BOX Assy Replaces GA-3.6RZ3 Pipe Frame Assy Bracket GA-3.6RZ3 Name Plate and Decals See Decal Illustrations on Robin EH-25 Engine Crankcase Assy Part Name QTY Remarks Robin EH-25 Engine Crankshaft & Piston Assy NUT Robin EH-25 Engine Intake & Exhaust Assy Tappet Robin EH-25 Engine Governor Assy Governor ROD Robin EH-25 Engine Cooling & Starting Assy Label Trade Mark Robin EH-25 Engine Carburetor Assy Hose Clamp Robin EH-25 Engine Ignition Coil ASSY. and Spark Plug FLY Wheel Robin EH-25 Engine Fuel Strainer Robin EH-25 Engine Fuel Strainer Terms and Conditions of Sale Parts FreightpolicyPage Denyo Manufacturing CO., Japan Multiquip INC