Section 2 – Operation

Residential Portable Generator System

2.3 HOW TO USE THE GENERATOR

If you have any problems operating your generator, please call the generator helpline at 1-800-333-1322.

2.3.1 GROUNDING THE GENERATOR

The National Electrical Code requires that the frame and external electrically conductive parts of this generator be properly connected to an approved earth ground. Local electrical codes may also require proper grounding of the unit. For that purpose, generally, connecting a No. 10 AWG (American Wire Gauge) stranded copper wire to the grounding wing nut and to an earth-driven copper or brass grounding rod (electrode) provides adequate protection against electrical shock. However, local codes may vary widely. Consult with a local electrician for grounding requirements in your area.

Figure 13 - Grounding the Generator

Generator Ground Lug

Proper grounding of the generator will help prevent electrical shock in the event of a ground fault condition in the generator or in connected electrical devices. Proper grounding also helps dissipate static electricity, which often builds up in ungrounded devices.

2.3.2 CONNECTING ELECTRICAL LOADS

DO NOT connect 240 Volt loads to 120 Volt receptacles. DO NOT connect 3-phase loads to the generator. DO NOT connect 50 Hz loads to the generator.

Let engine stabilize and warm up for a few minutes after starting.

Plug in and turn on the desired 120 or 240 Volt AC, single phase, 60 Hz electrical loads.

Add up the rated watts (or amps) of all loads to be connected at one time. This total should not be greater than (a) the rated wattage/amperage capacity of the generator or (b) circuit breaker rating of the receptacle supplying the power. See "Don't Overload the Generator" below.

2.4DON’T OVERLOAD THE GENERATOR

Overloading a generator in excess of its rated wattage capacity can result in damage to the generator and to connected electrical devices. Observe the following to prevent overloading the unit:

Add up the total wattage of all electrical devices to be connected at one time. This total should NOT be greater than the generator's wattage capacity.

The rated wattage of lights can be taken from light bulbs. The rated wattage of tools, appliances and motors can usually be found on a data plate or decal affixed to the device.

If the appliance, tool or motor does not give wattage, multiply volts times ampere rating to determine watts (volts x amps = watts).

Some electric motors, such as induction types, require about three times more watts of power for starting than for running. This surge of power lasts only a few seconds when starting such motors. Make sure you allow for this high starting wattage when selecting electrical devices to connect to your generator:

1.Figure the watts needed to start the largest motor.

2.Add to that figure the running watts of all other connected loads.

The Wattage Reference Guide on page 10 is provided to assist you in determining how many items your generator can operate at one time. (Note: All figures are approximate. See data plate on appliance for wattage requirements.)

9

Image 11
Contents Owner’s Manual Installation Guide For Generator Ready Kit Introduction General Hazards Important Safety InstructionsFire Hazards Electrical HazardsExplosion Hazards Assembling the Wheel KIT AssemblyAccessory BOX UnpackingHandle Assembly Battery ConnectionKnow the Generator Operation2 120V AC, 20 AMP, Gfci Receptacle Cord Sets and Connection Plugs1 AC, 20 AMP, Duplex Receptacle Provided. This receptacle can not recharge 6 Volt batteries 5 12 Volt DC, 10 AMP ReceptacleGrounding the Generator HOW to USE the GeneratorConnecting Electrical Loads DON’T Overload the GeneratorAdding Engine OIL Wattage Reference GuideBefore Starting the Generator Adding Gasoline To Start the EngineLOW OIL Pressure Shutdown System Stopping the EngineAutomatic Idle Control Cold Weather OPERATION/ DE-ICERTo recharge 12 Volt batteries, proceed as follows Charging a BatteryEngine Specifications Maintenance ScheduleProduct Specifications Generator SpecificationsGeneral Recommendations Generator MaintenanceEngine Maintenance Checking OIL Level To Clean the GeneratorReplacing the Spark Plug Service AIR CleanerClean Spark Arrestor Screen To adjust valve clearance Adjusting Valve ClearanceFuel Tank GeneralLong Term Storage Other Storage TipsSymptom Cause Solution TroubleshootingGenerator Ready KIT Plan the Location of Your Generator Safety and to discourage tampering Your Guardian Generator Ready KIT Is NOW Installed Operation of Generator with Generator Ready KIT Transfer to Generator Power Source When Utility Power Fails Interconnection Drawing Residential Portable Generator System Wiring Diagram Drawing No E0228 Schematic Drawing No E0229-A Section Part NO. QTY Description Detail a QTY Description Part NO#.QTY Generator Drawing No D4488-D QTY. Description 47,48 Heatsink Part NO. QTY. DescriptionFrame, Handle & Wheel Kit Drawing No E0695-A Special L/WASH QTY DescriptionCalifornia Emission Control Warranty Statement Emission Control System Warranty This Warranty Shall not Apply to the Following Warranty Schedule