NOTE: Balance must be maintained when moving circuit locations from main electrical distribution panel to emergency load center. Circuit breaker positions alternate buss bars vertically. Circuits sharing a neutral wire should either be moved together to adjacent positions in emergency load center or not moved. If you are unsure of proper procedure or if your installation differs from that described in this guide, consult a licensed professional at this time.

10a. Remove the main electrical distribution panel cover. Remove appropriate size knockout from the bottom or side of the main panel. (A 2-foot flexible conduit is pre-wired from the transfer switch with built-in load center). Remove threaded lock nut from conduit coupling. Feed all wires through knockout into main panel. Slip lock nut over wires and tighten securely onto conduit coupling.

10a Connection of Emergency Circuits

NOTE: Circuits to be moved must be protected by same size breaker. For example, a 15 amp 120V circuit in emergency load center will replace a 15 amp 120V circuit in main panel.

10b Connection of Emergency Circuits

UL approved wire nuts are included with installation kit.

SECTION 5 - INSTALLATION GUIDE FOR GENERATOR READY KIT

10b. In your main panel, remove the black (hot) wire from a circuit breaker that protects a circuit you want to have powered in the event of a power failure. Wire nut the black wire to the matching circuit lead wire from the emergency circuit breaker from load center in the transfer switch. (All circuit wires are color coded and labeled for easy identification). Repeat this process with remaining circuits to be powered by the generator. White wires (neutral) in your main distribution panel should remain connected to neutral bar. It is not necessary to move them. The emergency load center in the transfer switch supplies the following circuits: (5) 15A/120V, (3) 20A/120V, (1) 20A/240V and (1) 30A/240V.

11 Install 70 AMP Circuit Breaker

70

11.Install the 70 Amp double pole circuit breaker that you have purchased into main electrical distribution panel. This circuit breaker must be compatible with your main electrical distribution panel. It may be necessary to reposition remaining circuit breakers or remove circuit breakers that have been disconnected to accommodate the insertion of the 70 Amp double pole circuit breaker. Connect white wire to the main distribution panel neutral bar. Connect solid green wire to main electrical panel ground bar. Connect the black and red wires to the 70 Amp double pole circuit breaker. Replace electrical distribution panel cover.

YOUR GUARDIAN®

GENERATOR READY KIT

IS NOW INSTALLED!

23

Image 25
Contents Owner’s Manual Installation Guide For Generator Ready Kit Introduction General Hazards Important Safety InstructionsExplosion Hazards Electrical HazardsFire Hazards Accessory BOX AssemblyUnpacking Assembling the Wheel KITHandle Assembly Battery ConnectionKnow the Generator Operation1 AC, 20 AMP, Duplex Receptacle Cord Sets and Connection Plugs2 120V AC, 20 AMP, Gfci Receptacle Provided. This receptacle can not recharge 6 Volt batteries 5 12 Volt DC, 10 AMP ReceptacleConnecting Electrical Loads HOW to USE the GeneratorDON’T Overload the Generator Grounding the GeneratorBefore Starting the Generator Wattage Reference GuideAdding Engine OIL Adding Gasoline To Start the EngineAutomatic Idle Control Stopping the EngineCold Weather OPERATION/ DE-ICER LOW OIL Pressure Shutdown SystemTo recharge 12 Volt batteries, proceed as follows Charging a BatteryProduct Specifications Maintenance ScheduleGenerator Specifications Engine SpecificationsEngine Maintenance Checking OIL Level Generator MaintenanceTo Clean the Generator General RecommendationsClean Spark Arrestor Screen Service AIR CleanerReplacing the Spark Plug To adjust valve clearance Adjusting Valve ClearanceLong Term Storage GeneralOther Storage Tips Fuel TankSymptom Cause Solution TroubleshootingGenerator Ready KIT Plan the Location of Your Generator Safety and to discourage tampering Your Guardian Generator Ready KIT Is NOW Installed Operation of Generator with Generator Ready KIT Transfer to Generator Power Source When Utility Power Fails Interconnection Drawing Residential Portable Generator System Wiring Diagram Drawing No E0228 Schematic Drawing No E0229-A Section Part NO. QTY Description Detail a QTY Description Part NO#.QTY Generator Drawing No D4488-D QTY. Description 47,48 Heatsink Part NO. QTY. DescriptionFrame, Handle & Wheel Kit Drawing No E0695-A Special L/WASH QTY DescriptionCalifornia Emission Control Warranty Statement Emission Control System Warranty This Warranty Shall not Apply to the Following Warranty Schedule