Generac Power Systems 004917-3 owner manual Generator Location, Generator Mounting Support

Page 11

Section 2 — Installation

QUIETSOURCELiquid-cooled 30 kW Generators

Only qualified, competent installation contractors or electricians thoroughly familiar with applicable codes, standards and regulations should install this standby electric power system. The installation must comply strictly with all codes, standards and regula- tions pertaining to the installation.

After the system has been installed, do nothing ! that might render the installation in noncompli-

ance with such codes, standards and regula- tions.

NOTE:

For more information about the installation of a standby system, order Engine-Generator Standby Electric Power Systems Installer’s Guide and Reference Manual (part #046622) from the Generac Authorized Service Dealer.

‹2.1.1 NFPA STANDARDS

The following published standards booklets pertain- ing to standby electric systems are available form the National Fire Protection Association (NFPA), Batterymarch Park, Quincy, MA 02269:

NOTE:

It is essential to use the latest version of any stan- dard to ensure correct and current information.

NFPA No. 37, STATIONARY COMBUSTION ENGINES AND GAS TURBINES.

NFPA No. 76A, ESSENTIAL ELECTRICAL SYS-

TEMS FOR HEALTH CARE FACILITIES.

NFPA No. 220, STANDARD TYPES OF BUILDING CONSTRUCTION

NFPA No. 68, GUIDE FOR EXPLOSION VENTING

NFPA No. 70, NATIONAL ELECTRICAL CODE.

NFPA No. 30, FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE.

NFPA No. 10, INSTALLATION, MAINTENANCE AND USE OF PORTABLE FIRE EXTINGUISHERS.

‹2.1.2 OTHER PUBLISHED STANDARDS

In addition to NFPA standards, the following infor- mation pertaining to the installation and use of standby electric systems is available:

NOTE:

It is essential to use the latest version of any stan- dard to ensure correct and current information.

Article X, NATIONAL BUILDING CODE, available from the American Insurance Association, 85 John Street, New York, N.Y. 10038.

AGRICULTURAL WIRING HANDBOOK, obtainable from the Food and Energy Council, 909 University Avenue, Columbia, MO, 65201.

ASAE EP-364.2, INSTALLATION AND MAINTE-

NANCE OF FARM STANDBY ELECTRIC POWER, available from the American Society of Agricultural Engineers, 2950 Niles Road, St. Joseph, MI 49085.

A52.1, AMERICAN NATIONAL STANDARD FOR CHIMNEYS, FIREPLACES AND VENTING SYS- TEMS, available from the American National Standard Institute, 1430 Broadway, New York, N.Y. 10018.

2.2GENERATOR LOCATION

Install the generator set, in its protective enclosure outdoors, where adequate cooling and ventilating air always is available. Consider these factors:

Install the unit where air inlet and outlet openings will not become obstructed by leaves, grass, snow, etc. If prevailing winds will cause blowing or drift- ing, consider using a windbreak to protect the unit.

Install the generator on high ground where water levels will not rise and endanger it.

This genset must be installed on a level surface. The base frame must be level within 1/2 inch all around.

Allow sufficient room on all sides of the generator for maintenance and servicing. A good rule is to allow five feet of space on all sides.

Where strong prevailing winds blow from one direction, face the generator air inlet openings into the prevailing winds.

Install the generator as close as possible to the transfer switch. This reduces the length of wiring and conduit.

Install the generator as close as possible to the fuel supply, to reduce the length of piping. HOWEVER, REMEMBER THAT LAWS OR CODES MAY REG- ULATE THE DISTANCE.

2.3GENERATOR MOUNTING AND

SUPPORT

Retain the generator compartment to a concrete slab with 1/4-inch masonry type anchor bolts. Be sure the bolts are long enough to retain the compartment. The slab should be at least six inches thick and should extend beyond the enclosure to a distance of at least three inches on all sides. See Section 6 for generator major dimensions.

2.4BASIC STANDBY ELECTRIC

SYSTEM

Figure 2.1 shows a schematic diagram of a basic standby electric system. Both the UTILITY power supply and the STANDBY (GENERATOR) output are connected to an approved transfer switch. The trans- fer switch is required by electrical code and serves the following functions:

Generac® Power Systems, Inc. 9

Image 11
Contents Installation Introduction Authorized Service Dealer Location‹ Operation and Maintenance ‹ HOW to Obtain ServiceTable of Contents General Hazards Electrical Hazards Generator AC Connection Systems Transfer SwitchGenerator Automatic System OperationGenerator Fuel System ‹ 1.7.2 High Coolant Temperature Switch‹ 1.7.1 LOW OIL Pressure Switch ‹ 1.7.3 LOW Coolant Level SwitchLifting the Generator Unpacking‹ 1.10.2 Engine Specifications SpecificationsReconfiguring the Fuel System ‹ 1.10.1 Generator SpecificationsCoolant Recommendations Torque SpecificationsBefore Installation Engine OIL Recommendations‹ 2.1.1 Nfpa Standards Generator LocationGenerator Mounting Support Basic Standby Electric SystemGenerator AC Neutral Connections Emergency Circuit Isolation MethodTotal Circuit Isolation Method Grounding the Generator‹ 2.9.2 GTS-TYPE ATS Transfer Switch Signal ConnectionsBattery Installation ‹ 2.9.1 PRE-PACKAGED ATSPreparation Before START-UP ‹ 2.11.7 Electrical System Using a Standard GTS Transfer Switch‹ 3.2.1 AUTO/OFF/MANUAL Switch Control Console Components‹ 3.2.4 4 AMP Inline Fuse Manual Transfer START-UP Engine Governor Adjustments‹ 3.2.2 Fault Indicator LED ‹ 3.2.5 SET Exercise Time SwitchWeekly Exercise Cycle Retransfer and ShutdownAutomatic Operation Cooling System Overload Protection for Engine DC Electrical SystemChecking Fluid Levels ‹ 4.5.3 Exercise System ‹ 4.5.2 Check Battery‹ 4.4.3 Engine Coolant ‹ 4.5.1 Check Engine OIL Level‹ 4.5.13 Coolant Change Miscellaneous Maintenance‹ 4.5.11 Changing the Engine AIR Cleaner ‹ 4.6.1 Cleaning the Generator‹ 4.6.4 Battery Replacement ‹ 4.6.2 Battery‹ 4.6.3 Battery Maintenance Service Maintenance Interval Information Scheduled MaintenanceLevel Maintenance Level Problem Cause Correction Troubleshooting PointsCustomer Connection PCB J2 BCW LOS WLS HCT Starter Carrier Bolt Hold Down Battery Boot Battery CableBattery Post Cover Baclk Battery Post Cover RED +Detail Duct Discharge RH AL Assy GRD Wire 99HSBASSEMBLY,BASE-DOOR Ground Wire Duct Intake MID ALGenerac Power Systems, Inc Cover Front Panel HSB Assy 2A 12V UL BatteryControl BOX HSB Decal AVR Cover61 24 Bracket DC ALT 3.0L Ford Wire SET 3.0L Ford notNot SHOWN-USED to Hold OIL Drain Assembly Coil Ignition 3.0L FordFrame Side Support Radiator HSB Tank Coolant RecoveryRadiator R-IN,L-OUT Venturi 3.0L Ford HSBTo B Washer Flat 5/16 Zinc Weldment Mounting BaseFlange Fuel Inlet Assy Regulator 3.0L NG or LPVLocktight Rotor 39030AD1 HSB Tecum Rotor 390 15KW 1P Direct HSB 2.5L FordRotor 390 20KW 1P Direct HSB 2.5L Ford Rotor 390 25KW 1P Direct HSB 2.5L FordPipe Muffler OUT Exhaust Flange 2 PipeOUT Washer Lock 3/8 SSWasher Flat M5 Element AIR CleanerCover AIR Cleaner Tube AIR Intake 3.0L FordInstallation Diagram Quietsource Liquid-cooled 30 kW Generators This Warranty Shall not Apply to the Following