Generac Power Systems 04390-1, 04456-1 Before Initial START-UP, Check Transfer Switch Operation

Page 12

Section 2 — Post Installation Start-up and Adjustments

Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators

Where electrolyte contacts the eyes, flush thoroughly and immediately with water and seek medical attention; and

Spilled electrolyte is to be washed down with an acid neutralizing agent. A common practice is to use a solution of 1 pound (500 grams) bicarbonate of soda to 1 gallon (4 liters) of water. The bicar- bonate of soda solution is to be added until the evidence of reaction (foaming) has ceased. The resulting liquid is to be flushed with water and the area dried.

Lead-acid batteries present a risk of fire because they generate hydrogen gas. The following procedures are to be followed:

DO NOT SMOKE when near the battery;

DO NOT cause flame or spark in battery area; and

Discharge static electricity from your body before touching the battery by first touching a grounded metal surface.

Be sure the Auto/Off/Manual switch is set to ! the OFF position before connecting the battery

cables. If the switch is set to AUTO or MANUAL, the generator can crank and start as soon as the battery cables are connected.

Be sure the utility power supply is turned off and the 5A and 15A fuses are removed from the generator control panel, or sparking may occur at the battery posts as the cables are attached and cause an explosion.

2.1BEFORE INITIAL START-UP

Before starting, complete the following:

1.Set the generator’s main circuit breaker to its OFF (or open) position.

2.Set the generator's Auto/Off/Manual switch to the OFF position.

3.Turn OFF the utility power supply to the transfer switch using the means provided (such as the utility main line circuit breaker).

4.Turn OFF all loads connected to the transfer switch terminals T1 and T2.

5.Check the engine crankcase oil level and, if nec- essary, fill to the dipstick FULL mark with the recommended oil. Do not fill above the FULL mark.

6.Check the fuel supply. Gaseous fuel lines must have been properly purged and leak tested in accor- dance with applicable fuel-gas codes. All fuel shut- off valves in the fuel supply lines must be open.

Never operate the engine with the oil level

!below the “Add” mark on the dipstick. Doing this could damage the engine.

10 Generac® Power Systems, Inc.

2.2CHECK TRANSFER SWITCH

OPERATION

Refer to Section 3.5, of the owner’s manual for man- ual operation procedures.

DANGER

Do not attempt manual transfer switch opera- tion until all power voltage supplies to the transfer switch have been positively turned off. Failure to turn off all power voltage supplies will result in extremely hazardous and possibly fatal electrical shock.

2.3ELECTRICAL CHECKS

Complete electrical checks as follows:

1.Set the generator's main circuit breaker to its OFF (or open) position.

2.Set the generator's Auto/Off/Manual switch to the OFF position.

3.Turn OFF all loads connected to the transfer switch terminals T1 and T2.

4.Turn on the utility power supply to the transfer switch using the means provided (such as a utili- ty main line circuit breaker).

DANGER

The transfer switch is now electrically “hot.” Contact with “hot” parts will result in extreme- ly hazardous and possibly fatal electrical shock. Proceed with caution.

5.Use an accurate AC voltmeter to check utility power source voltage across transfer switch ter- minals N1 and N2. Nominal line-to-line voltage should be 240 volts AC.

6.Check utility power source voltage across termi- nals N1 and the transfer switch neutral lug; then across terminal N2 and neutral. Nominal line-to- neutral voltage should be 120 volts AC.

7.When certain that utility supply voltage is com- patible with transfer switch and load circuit rat- ings, turn OFF the utility power supply to the transfer switch.

8.On the generator panel, set the Auto/Off/Manual switch to MANUAL. The engine should crank and start.

9.Let the engine warm up for about five minutes to allow internal temperatures to stabilize. Then, set the generator’s main circuit breaker to its ON (or closed) position.

DANGER

Proceed with caution! Generator power voltage is now supplied to the transfer switch. Contact with live transfer switch parts will result in dangerous and possibly fatal electrical shock.

Image 12
Contents Installation Introduction Authorized Dealer LocationPost Installation Start-up Adjustments MaintenanceTroubleshooting Introduction Inside Front CoverGeneral Hazards Electrical Hazards ‹ Standards IndexUNPACKING/INSPECTION Protection SystemsSystem SET LED Your Generator 7 kW, Single Cylinder GH-410 EngineSpecifications ‹ 1.5.1 Generator‹ 1.5.2 Engine Reconfiguring the Fuel System Fuel Requirements RecommendationsFuel Consumption 1 7 KW, 410CC EngineTransfer Switch LocationGenerator 2.1 7 kW, 12 kW and 15 kW UnitsBattery Installation BatteryCheck Transfer Switch Operation Before Initial START-UPElectrical Checks Generator Tests Under Load Checking Automatic OperationAdjusting the Regulator Natural GAS only Engine Governor Adjustment1 7 KW Units Voltage Regulator Adjustment 2 12 KW and 15 KW UnitsBREAK-IN Procedure Automatic Transfer Operation‹ 3.2.3 Manual Position ‹ 3.2.1 Auto PositionSequence of Automatic Operation Manual Transfer OperationSetting the Exercise Timer ‹ 3.5.2 Transfer Back to Utility Power Source‹ 3.7.1 LOW OIL Pressure Switch ‹ 3.7.2 High Temperature SwitchChecking the Engine OIL Level Approximate Crank Cycle Times‹ 3.7.4 Overspeed ‹ 4.3.2 OIL Change Procedure Changing the Engine OILChanging the OIL Filter ‹ 4.3.1 Engine OIL RecommendationsBattery Maintenance Spark PlugsAdjusting GH-410/GT-990 Valve Clearance Cooling SystemOUT of Service Procedure ‹ 4.12.1 Removal from Service‹ 4.12.2 Return to Service Corrosion ProtectionService Schedule SYSTEM/COMPONENT Procedure FrequencyTroubleshooting Guide Problem Cause CorrectionElectrical Data Customer Battery Utility Battery Charger Utility Connection BCR Customer Connections Neutral Exploded Views and Parts Lists Part NO.QTY. Description Exploded Views and Parts Lists QTY Description Exploded Views and Parts Lists BOX GTS Load Center Exploded Views and Parts Lists COVER, 12 Position GTS Load Center Kit Contains BUSHING, Governor Lower 138 122 KNOB, AIR Cleaner 28 31 ADAPTOR, Engine Exploded Views and Parts Lists Stator 12KW Exploded Views and Parts Lists ASSEMBLY, Connecting ROD Exploded Views and Parts Lists SCREW, Taptite M6-1.0X8 Yellow Chrome Engine only Mounting Dimensions Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators Your Warranty Rights and Obligations MANUFACTURER’S Emission Control System Warranty CoveragePURCHASER’S/OWNER’S Warranty Responsibilities Emission Control System Warranty Emission Related Parts Include the FollowingWarranty Schedule This Warranty Shall not Apply to the Following

04389-1, 04456-1, 04390-1 specifications

Generac Power Systems is synonymous with reliable and innovative power solutions for both residential and commercial applications. Among its diverse product lineup, the Generac 04390-1, 04456-1, and 04389-1 stand out due to their robust features, advanced technologies, and user-focused characteristics.

The Generac 04390-1 is a portable generator designed for versatility and efficiency. It is equipped with a powerful OHV engine that enables it to deliver up to 3500 running watts and 4375 starting watts, making it suitable for various applications, such as home backup during outages or powering tools on job sites. The generator features a built-in PowerRUSH technology, which provides a 40% more starting capacity than traditional models, allowing it to handle more demanding appliances and tools simultaneously. Additionally, its lightweight and compact design enhance portability, complemented by a sturdy handle and flat-free wheels.

Moving on to the Generac 04456-1, this model offers a greater output with 7500 running watts and 9400 starting watts. Ideal for larger homes or work environments, it is powered by a heavy-duty, 420cc engine and designed for optimal performance. The unit incorporates an electric start feature for easy operation and includes a low-oil shutdown system that protects the engine from damage, providing peace of mind to users. The reinforced roll-cage design ensures durability, while its quiet operation keeps noise levels to a minimum, making it suitable for more noise-sensitive environments.

Lastly, the Generac 04389-1 generator is particularly characterized by its dual-fuel capability, allowing users to run it on either gasoline or propane. This flexibility ensures seamless operation in various situations, with 5500 running watts on gasoline and 4950 running watts on propane. The model’s advanced engineering includes an easy-to-read fuel gauge, ensuring that users can monitor fuel levels without hassle. This generator is also equipped with a heavy-duty, full-wrap steel frame for resistance against impacts and wear, making it perfect for outdoor use.

Collectively, the Generac 04390-1, 04456-1, and 04389-1 models embody a commitment to quality and innovation. With their powerful engines, enhanced technologies, and user-friendly features, these generators provide peace of mind through reliable power solutions, catering to a multitude of needs for both residential and commercial users alike. Whether for emergency backup or regular use, Generac’s offerings ensure that power is always on hand when it’s needed the most.