Generac Power Systems 04390-1, 04456-1, 04389-1 owner manual Spark Plugs, Battery Maintenance

Page 21

Section 4 — Maintenance

Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators

Figure 4.7 — 12 kW and 15 kW Engine

Air Cleaner

Screw

Cover

Filter

4.6SPARK PLUG(S)

Reset the spark plug(s) gap or replace the spark plug(s) as necessary. See Section 4.13 for mainte- nance requirements.

1.Clean the area around the base of the spark plug(s) to keep dirt and debris out of the engine. Clean by scraping or washing using a wire brush and commercial solvent. Do not blast the spark plug(s) to clean.

2.Remove the spark plug(s) and check the condi- tion. Replace the spark plug(s) if worn or if reuse is questionable. See Section 4.13 for recom- mended inspection.

3.Check the spark plug gap using a wire feeler gauge. Adjust the gap to 0.76 mm (0.030 inch) for 7 kW and 0.50 mm (0.020 inch) for 12/15 kW by carefully bending the ground electrode (Figure 4.8).

Figure 4.8 – Setting the Spark Plug Gap

SET PLUG GAP AT 0.76 mm (.030 inch)

4.7BATTERY MAINTENANCE

The battery should be inspected per the “Service Schedule,” Section 4.13. The following procedure should be followed for inspection:

1.Inspect the battery posts and cables for tightness and corrosion. Tighten and clean as necessary.

2.Check the battery fluid level of unsealed batteries and, if necessary, fill with Distilled Water Only. Do not use tap water in batteries.

3.Have the state of charge and condition checked. This should be done with an automotive-type bat- tery hydrometer.

DANGER

Do not dispose of the battery in a fire. The battery is capable of exploding.

A battery presents a risk of electrical shock and high short circuit current. The following precautions are to be observed when working on batteries:

Remove the 5A and 15A fuses from the generator control panel.

Remove watches, rings or other metal objects;

Use tools with insulated handles;

Wear rubber gloves and boots;

Do not lay tools or metal parts on top of the battery; and

Disconnect charging source prior to connecting or dis- connecting battery terminals.

Do not open or mutilate the battery. Released

!electrolyte has been known to be harmful to the skin and eyes, and to be toxic.

The electrolyte is a dilute sulfuric acid that is

!harmful to the skin and eyes. It is electrically conductive and corrosive. The following procedures are to be observed:

Wear full eye protection and protective clothing;

Where electrolyte contacts the skin, wash it off immediately with water;

Where electrolyte contacts the eyes, flush thoroughly and immediately with water and seek medical attention; and

Spilled electrolyte is to be washed down with an acid neutralizing agent. A common practice is to use a solution of 1 pound (500 grams) bicarbonate of soda to 1 gallon (4 liters) of water. The bicar- bonate of soda solution is to be added until the evidence of reaction (foaming) has ceased. The resulting liquid is to be flushed with water and the area dried.

Generac® Power Systems, Inc. 19

Image 21
Contents Installation Authorized Dealer Location IntroductionMaintenance Post Installation Start-up AdjustmentsTroubleshooting Introduction Inside Front CoverGeneral Hazards ‹ Standards Index Electrical HazardsUNPACKING/INSPECTION Protection SystemsSystem SET LED 7 kW, Single Cylinder GH-410 Engine Your GeneratorSpecifications ‹ 1.5.1 Generator‹ 1.5.2 Engine Fuel Requirements Recommendations Reconfiguring the Fuel SystemFuel Consumption 1 7 KW, 410CC EngineLocation Transfer SwitchGenerator 2.1 7 kW, 12 kW and 15 kW UnitsBattery Battery InstallationCheck Transfer Switch Operation Before Initial START-UPElectrical Checks Checking Automatic Operation Generator Tests Under LoadAdjusting the Regulator Natural GAS only Engine Governor Adjustment1 7 KW Units 2 12 KW and 15 KW Units Voltage Regulator AdjustmentAutomatic Transfer Operation BREAK-IN Procedure‹ 3.2.3 Manual Position ‹ 3.2.1 Auto PositionManual Transfer Operation Sequence of Automatic Operation‹ 3.5.2 Transfer Back to Utility Power Source Setting the Exercise Timer‹ 3.7.1 LOW OIL Pressure Switch ‹ 3.7.2 High Temperature SwitchChecking the Engine OIL Level Approximate Crank Cycle Times‹ 3.7.4 Overspeed Changing the Engine OIL ‹ 4.3.2 OIL Change ProcedureChanging the OIL Filter ‹ 4.3.1 Engine OIL RecommendationsSpark Plugs Battery MaintenanceCooling System Adjusting GH-410/GT-990 Valve Clearance‹ 4.12.1 Removal from Service OUT of Service Procedure‹ 4.12.2 Return to Service Corrosion ProtectionSYSTEM/COMPONENT Procedure Frequency Service ScheduleProblem Cause Correction Troubleshooting GuideElectrical Data Customer Battery Utility Battery Charger Utility Connection BCR Customer Connections Neutral Exploded Views and Parts Lists Part NO.QTY. Description Exploded Views and Parts Lists QTY Description Exploded Views and Parts Lists BOX GTS Load Center Exploded Views and Parts Lists COVER, 12 Position GTS Load Center Kit Contains BUSHING, Governor Lower 138 122 KNOB, AIR Cleaner 28 31 ADAPTOR, Engine Exploded Views and Parts Lists Stator 12KW Exploded Views and Parts Lists ASSEMBLY, Connecting ROD Exploded Views and Parts Lists SCREW, Taptite M6-1.0X8 Yellow Chrome Engine only Mounting Dimensions Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators Your Warranty Rights and Obligations MANUFACTURER’S Emission Control System Warranty CoveragePURCHASER’S/OWNER’S Warranty Responsibilities Emission Related Parts Include the Following Emission Control System WarrantyThis Warranty Shall not Apply to the Following Warranty Schedule

04389-1, 04456-1, 04390-1 specifications

Generac Power Systems is synonymous with reliable and innovative power solutions for both residential and commercial applications. Among its diverse product lineup, the Generac 04390-1, 04456-1, and 04389-1 stand out due to their robust features, advanced technologies, and user-focused characteristics.

The Generac 04390-1 is a portable generator designed for versatility and efficiency. It is equipped with a powerful OHV engine that enables it to deliver up to 3500 running watts and 4375 starting watts, making it suitable for various applications, such as home backup during outages or powering tools on job sites. The generator features a built-in PowerRUSH technology, which provides a 40% more starting capacity than traditional models, allowing it to handle more demanding appliances and tools simultaneously. Additionally, its lightweight and compact design enhance portability, complemented by a sturdy handle and flat-free wheels.

Moving on to the Generac 04456-1, this model offers a greater output with 7500 running watts and 9400 starting watts. Ideal for larger homes or work environments, it is powered by a heavy-duty, 420cc engine and designed for optimal performance. The unit incorporates an electric start feature for easy operation and includes a low-oil shutdown system that protects the engine from damage, providing peace of mind to users. The reinforced roll-cage design ensures durability, while its quiet operation keeps noise levels to a minimum, making it suitable for more noise-sensitive environments.

Lastly, the Generac 04389-1 generator is particularly characterized by its dual-fuel capability, allowing users to run it on either gasoline or propane. This flexibility ensures seamless operation in various situations, with 5500 running watts on gasoline and 4950 running watts on propane. The model’s advanced engineering includes an easy-to-read fuel gauge, ensuring that users can monitor fuel levels without hassle. This generator is also equipped with a heavy-duty, full-wrap steel frame for resistance against impacts and wear, making it perfect for outdoor use.

Collectively, the Generac 04390-1, 04456-1, and 04389-1 models embody a commitment to quality and innovation. With their powerful engines, enhanced technologies, and user-friendly features, these generators provide peace of mind through reliable power solutions, catering to a multitude of needs for both residential and commercial users alike. Whether for emergency backup or regular use, Generac’s offerings ensure that power is always on hand when it’s needed the most.