Section 3 — Operation

Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators

‹3.5.2 TRANSFER BACK TO UTILITY POWER SOURCE

When utility power has been restored, transfer back to that source and shut down the generator. This can be accomplished as follows:

1.Set the generator’s main circuit breaker to its OFF (or open) position.

2.Let the engine run for a minute or two at no-load to stabilize the internal temperatures.

3.Set the generator’s Auto/Off/Manual switch to its OFF (or open) position. The engine should shut down.

4.Check that utility power supply to the transfer switch is turned OFF.

DANGER

Do not attempt to activate the transfer switch manually until all power voltage supplies

to the switch have been positively turned off. Failure to turn off all power voltage supplies may result in extremely hazardous and possibly fatal electrical shock.

5.Use the manual transfer handle inside the trans- fer switch to move the main contacts back to their “Utility” position, i.e., loads connected to the util- ity power source (Figure 3.2).

NOTE:

The exerciser will only work in the AUTO mode and will not work unless this procedure is performed. The exerciser will need to be reset every time the 12-volt battery is disconnected and then reconnected. The exerciser WILL NOT work if dip switch 2 on the controller printed circuit board (Remote Not Auto) is ON.

3.7PROTECTION SYSTEMS

‹3.7.1 LOW OIL PRESSURE SWITCH

This switch (Figure 3.3) has normally closed contacts that are held open by engine oil pressure during cranking and operating. Should oil pressure drop below the 8 psi range, switch contacts close, and the engine shuts down. The unit should not be restarted until oil is added. The Auto/Off/Manual switch must then be turned to OFF and then back to AUTO.

‹3.7.2 HIGH TEMPERATURE SWITCH

This switch’s contacts (Figure 3.3) close if the tem- perature should exceed approximately 140º C (284º F), initiating an engine shutdown. The generator will automatically restart and the LED on the generator control panel will reset once the temperature has returned to a safe operating level.

6.Turn ON the utility power supply to the transfer switch using the means provided.

7.Set the system to automatic operation as outlined in “Automatic Transfer Operation,” Section 3.3.

3.6SETTING THE EXERCISE TIMER

This generator is equipped with an exercise timer. Once it is set, the generator will start and exercise once every seven days, on the day of the week and at the time of day the following sequence is completed. During this exercise period, the unit runs for approx- imately 12 minutes and then shuts down. Transfer of loads to the generator output does not occur during the exercise cycle.

A switch on the control panel (see Figure 3.1) permits selection of the day and time for the system to exer- cise. At the chosen time, perform the following sequence to select the desired day and time of day the system will exercise.

1.Verify that the Auto/Off/Manual switch is set to AUTO.

2.Hold down the “Set Exercise Time” switch until the generator starts (approximately 10 seconds) and then release.

3.The generator will start and run for approximate- ly 12 minutes and then shut down on its own. The exerciser will then be set to run at that time of day every week.

16 Generac® Power Systems, Inc.

Figure 3.3 – Low Oil Pressure and

High Temperature Switches

Low Oil Switch

High Temp Switch

Loosen

Oil

Drain

Hose

Oil Filter

‹3.7.3 OVERCRANK

This feature prevents the generator from damaging itself when it continually attempts to start and anoth- er problem, such as no fuel supply, prevents it from starting. The unit will crank and rest for a preset time limit. Then, it will stop cranking, and the LED on the generator control panel will light indicating an over- crank failure. The Auto/Off/Manual switch will need to be set to OFF and then back to AUTO to reset the generator control board.

Image 18
Contents Installation Introduction Authorized Dealer LocationTroubleshooting Post Installation Start-up AdjustmentsMaintenance Introduction Inside Front CoverGeneral Hazards Electrical Hazards ‹ Standards IndexUNPACKING/INSPECTION Protection SystemsSystem SET LED Your Generator 7 kW, Single Cylinder GH-410 EngineSpecifications ‹ 1.5.1 Generator‹ 1.5.2 Engine Fuel Consumption Reconfiguring the Fuel SystemFuel Requirements Recommendations 1 7 KW, 410CC EngineGenerator Transfer SwitchLocation 2.1 7 kW, 12 kW and 15 kW UnitsBattery Installation BatteryCheck Transfer Switch Operation Before Initial START-UPElectrical Checks Generator Tests Under Load Checking Automatic OperationAdjusting the Regulator Natural GAS only Engine Governor Adjustment1 7 KW Units Voltage Regulator Adjustment 2 12 KW and 15 KW Units‹ 3.2.3 Manual Position BREAK-IN ProcedureAutomatic Transfer Operation ‹ 3.2.1 Auto PositionSequence of Automatic Operation Manual Transfer Operation‹ 3.7.1 LOW OIL Pressure Switch Setting the Exercise Timer‹ 3.5.2 Transfer Back to Utility Power Source ‹ 3.7.2 High Temperature SwitchChecking the Engine OIL Level Approximate Crank Cycle Times‹ 3.7.4 Overspeed Changing the OIL Filter ‹ 4.3.2 OIL Change ProcedureChanging the Engine OIL ‹ 4.3.1 Engine OIL RecommendationsBattery Maintenance Spark PlugsAdjusting GH-410/GT-990 Valve Clearance Cooling System‹ 4.12.2 Return to Service OUT of Service Procedure‹ 4.12.1 Removal from Service Corrosion ProtectionService Schedule SYSTEM/COMPONENT Procedure FrequencyTroubleshooting Guide Problem Cause CorrectionElectrical Data Customer Battery Utility Battery Charger Utility Connection BCR Customer Connections Neutral Exploded Views and Parts Lists Part NO.QTY. Description Exploded Views and Parts Lists QTY Description Exploded Views and Parts Lists BOX GTS Load Center Exploded Views and Parts Lists COVER, 12 Position GTS Load Center Kit Contains BUSHING, Governor Lower 138 122 KNOB, AIR Cleaner 28 31 ADAPTOR, Engine Exploded Views and Parts Lists Stator 12KW Exploded Views and Parts Lists ASSEMBLY, Connecting ROD Exploded Views and Parts Lists SCREW, Taptite M6-1.0X8 Yellow Chrome Engine only Mounting Dimensions Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators Your Warranty Rights and Obligations MANUFACTURER’S Emission Control System Warranty CoveragePURCHASER’S/OWNER’S Warranty Responsibilities Emission Control System Warranty Emission Related Parts Include the FollowingWarranty Schedule This Warranty Shall not Apply to the Following

04389-1, 04456-1, 04390-1 specifications

Generac Power Systems is synonymous with reliable and innovative power solutions for both residential and commercial applications. Among its diverse product lineup, the Generac 04390-1, 04456-1, and 04389-1 stand out due to their robust features, advanced technologies, and user-focused characteristics.

The Generac 04390-1 is a portable generator designed for versatility and efficiency. It is equipped with a powerful OHV engine that enables it to deliver up to 3500 running watts and 4375 starting watts, making it suitable for various applications, such as home backup during outages or powering tools on job sites. The generator features a built-in PowerRUSH technology, which provides a 40% more starting capacity than traditional models, allowing it to handle more demanding appliances and tools simultaneously. Additionally, its lightweight and compact design enhance portability, complemented by a sturdy handle and flat-free wheels.

Moving on to the Generac 04456-1, this model offers a greater output with 7500 running watts and 9400 starting watts. Ideal for larger homes or work environments, it is powered by a heavy-duty, 420cc engine and designed for optimal performance. The unit incorporates an electric start feature for easy operation and includes a low-oil shutdown system that protects the engine from damage, providing peace of mind to users. The reinforced roll-cage design ensures durability, while its quiet operation keeps noise levels to a minimum, making it suitable for more noise-sensitive environments.

Lastly, the Generac 04389-1 generator is particularly characterized by its dual-fuel capability, allowing users to run it on either gasoline or propane. This flexibility ensures seamless operation in various situations, with 5500 running watts on gasoline and 4950 running watts on propane. The model’s advanced engineering includes an easy-to-read fuel gauge, ensuring that users can monitor fuel levels without hassle. This generator is also equipped with a heavy-duty, full-wrap steel frame for resistance against impacts and wear, making it perfect for outdoor use.

Collectively, the Generac 04390-1, 04456-1, and 04389-1 models embody a commitment to quality and innovation. With their powerful engines, enhanced technologies, and user-friendly features, these generators provide peace of mind through reliable power solutions, catering to a multitude of needs for both residential and commercial users alike. Whether for emergency backup or regular use, Generac’s offerings ensure that power is always on hand when it’s needed the most.