Section 2 — Post Installation Start-up and Adjustments

Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators

If this procedure or the equipment are not available, locate the nearest Generac Guardian Dealer and they can perform the adjustments.

NOTE:

A service fee may be charged for this adjustment.

2.7ENGINE GOVERNOR ADJUSTMENT

If both AC frequency and voltage are correspondingly high or low, adjust the engine governor as follows:

2.7.1 7 KW UNITS

1.Loosen the governor clamp bolt (Figures 2.3).

2.Hold the governor lever at its wide open throttle position, and rotate the governor shaft clockwise as far as it will go. Then, tighten the governor lever clamp bolt to 70 inch-pounds (8 N-m).

3.Start the generator; let it stabilize and warm up at no-load.

4.Connect a frequency meter across the generators AC output leads.

5.Turn the speed adjust nut to obtain a frequency reading of 63 Hertz.

6.When frequency is correct at no load, check the AC voltage reading. If voltage is incorrect, the volt- age regulator may require adjustment.

Figure 2.3 — Engine Governor Adjustment

Idle Spring

Governor

Shaft

(Rotate

Clockwise)

Governor Clamp Bolt

No Load Idle

Adjustment Screw

 

2.7.2 12 KW AND 15 KW UNITS

1.Loosen governor clamp bolt (See Figure 2.3).

2.Completely remove the idle spring.

3.With governor arm at wide open throttle position, rotate governor shaft fully clockwise. Tighten clamp bolt to 84 inch-pounds.

4.Start unit and apply full load. Use full load speed adjust screw (Figure 2.4) to adjust frequency to 58 Hz.

5.Remove load, stop engine, loosen the idle adjust screw and reconnect the idle spring.

Figure 2.4 — Full Load Speed Adjust Screw

Full Load Speed Adjust Screw

6.Using a hand, push the governor arm to the closed throttle position. Make sure the idle spring does not stretch at all.

7.Restart the unit.

8.Slowly turn the idle adjust screw to adjust the no- load idle frequency to 63-63.5 Hz (with door open).

9.The governor is now set.

2.7.3 ADDITIONAL CORROSION PROTECTION

Periodically spray all engine linkage parts and brack- ets with corrosion inhibiting spray such as WD-40 or a comparable product.

2.8VOLTAGE REGULATOR

ADJUSTMENT

With the frequency between 62-63 Hertz, slowly turn the slotted potentiometer (Figure 2.5) until line volt- age reads 247-252 volts.

Figure 2.5 – Voltage Adjustment Potentiometer

Generac® Power Systems, Inc. 13

Image 15
Contents Installation Authorized Dealer Location IntroductionIntroduction Inside Front Cover Post Installation Start-up AdjustmentsMaintenance TroubleshootingGeneral Hazards ‹ Standards Index Electrical HazardsUNPACKING/INSPECTION Protection SystemsBreaker for Bedrooms 7 kW, Single Cylinder GH-410 Engine GeneratorSpecifications ‹ 1.5.1 Generator‹ 1.5.2 Engine Fuel Consumption Reconfiguring the Fuel SystemSystem SET LED Fuel Requirements RecommendationsGenerator Transfer SwitchLocation 2 12KW and 15KW, 990CC EnginesBattery Battery InstallationCheck Transfer Switch Operation Before Initial START-UPElectrical Checks Checking Automatic Operation Generator Tests Under LoadAdjustment Screw Adjusting the Regulator Natural GAS only2 12 KW and 15 KW Units Engine Governor AdjustmentVoltage Regulator Adjustment 1 7 KW Units‹ 3.2.2 OFF Position BREAK-IN ProcedureAutomatic Transfer Operation ‹ 3.2.1 Auto PositionSequence of Automatic Operation Manual Transfer Operation‹ 3.7.2 High Temperature Switch Setting the Exercise Timer‹ 3.5.2 Transfer Back to Utility Power Source ‹ 3.7.1 LOW OIL Pressure SwitchChecking the Engine OIL Level Approximate Crank Cycle Times‹ 3.7.4 Overspeed ‹ 4.3.1 Engine OIL Recommendations ‹ 4.3.2 OIL Change ProcedureChanging the Engine OIL Changing the OIL FilterSpark Plugs Battery MaintenanceCooling System Adjusting GH-410/GT-990 Valve ClearanceCorrosion Protection OUT of Service Procedure‹ 4.12.1 Removal from Service ‹ 4.12.2 Return to ServiceBe performed by the nearest Guardian Authorized Dealer Service ScheduleProblem Cause Correction Troubleshooting GuideElectrical Data Customer Battery Utility Battery Charger Utility Connection BCR SW1 Exploded Views and Parts Lists QTY Description Exploded Views and Parts Lists Circuit Breaker 40A X 2P Exploded Views and Parts Lists BOX GTS Load Center Exploded Views and Parts Lists COVER, 12 Position GTS Load Center 140 Sleeve Exploded Views and Parts Lists KNOB, AIR Cleaner 28 31 ADAPTOR, Engine Exploded Views and Parts Lists Stator 12KW Exploded Views and Parts Lists PIN, Piston D20 Exploded Views and Parts Lists SCREW, Taptite M6-1.0X8 Yellow Chrome Engine only Mounting Dimensions Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators Your Warranty Rights and Obligations MANUFACTURER’S Emission Control System Warranty CoveragePURCHASER’S/OWNER’S Warranty Responsibilities Emission Related Parts Include the Following Emission Control System WarrantyWarranty Schedule