Control Interface (cont’d)
DANGER
HAZARDOUS VOLTAGE
(Can Cause Severe Injury or Death)
Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.
In-Phase Monitor
ZTX ATS senses when the sources are as far out as 2 Hz or as close as .01Hz in frequency differential of each other and transfers the load to and from either source
In a typical ATS application, one source is on the utility and one source is a backup system such as a gas or diesel generator. Because sources have a slight frequency difference, sources come in and out of phase. If ZTX
In the case of both sources coming from the same source, or, one configured as WYE and the other as DELTA, the frequency difference is fixed at the same frequency or fixed but 30 degrees out of phase.
In those cases,
Turn In-Phase Monitor OFF:
1.Remove all power, (both S1 and S2) from the controller. Wait at least 20 seconds.
2.From the keypad, hold both the BYPASS and CANCEL keys down while energizing either source. If
Turn In-Phase Monitor ON:
1.Remove all power, (both S1 and S2) from the controller. Wait at least 20 seconds.
2.From the keypad, hold both the BYPASS and CANCEL keys down while energizing either source. If
Timer /
Figure 9
■ 10 | ZTX Operation and Maintenance Manual | GE Zenith Controls ■ |