GE ZTX manual Control Interface, Indicator LEDs

Page 9

Control Interface

DANGER

HAZARDOUS VOLTAGE

(Can Cause Severe Injury or Death)

Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.

Indicator LEDs

A S1

(Utility) Available Green LED.

When on, indicates source is acceptable.

B S1

(Utility) Position Green LED.

When on, indicates ATS is connected to Utility

CS2 (Generator) Available Red LED. When on, indicates source is acceptable.

D

S2 (Generator) Position Red LED.

When on, indicates ATS is connected to Generator.

E

Timing/In-phase Amber LED.

When blinking, indicates the ATS is timing a Delay

 

 

When on steady, indicates the ATS is waiting for both

 

 

sources to synchronize with each other.

D

C

E

 

 

A

 

 

B

 

 

Figure 7

F

G

H

I

Pushbuttons

 

 

 

 

F

TEST - Pressed and held for 1 second Simulates

 

 

 

 

 

a power outage, starts the Generator and

 

 

 

 

 

transfers the ATS to S2.

 

 

 

 

G

EXER SET - Sets an Automatic Exerciser

 

 

 

 

H

BYPASS TIMER - Pressed while E is blinking

 

 

 

 

 

bypasses any remaining countdown Timer

 

 

 

 

I

CANCEL - Depending on the current state of ATS

 

 

 

 

 

operation, ends specific functions or indications

GE Zenith Controls

ZTX Operation and Maintenance Manual (72R-1000)

7

Image 9
Contents GE Zenith Controls Authorized Service Table of ContentsIntroduction Can Cause Severe Injury or Death InstallationPower Connections Installation cont’dControl Connections GE Zenith ControlsInstallation cont’d Cover or close the cabinet door Functional TestVoltage / Frequency Selection Jumper Settings System Voltage SettingsControl Interface Indicator LEDsControl Interface cont’d Using the Keypad ControlsSelecting Exerciser with or without Load Transfer Automatic Generator ExerciserTurn In-Phase Monitor OFF In-Phase MonitorTotal Coverage System Example SystemsTypical Diagrams StandardTransition 40 to 200 Amps Replacement PartsStandard Transition 225 to 400 Amps Replacement Parts cont’dSymptom Possible Cause Corrective Action TroubleshootingGE Zenith Controls