Troubleshooting
DANGER
HAZARDOUS VOLTAGE
(Can Cause Severe Injury or Death)
Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.
Service must be performed by qualified personnel.
Symptom | Possible Cause | Corrective Action |
S1 or S2 Available LED not lit | Sources either fully or partially unacceptable | Check for under voltage |
| S1 or S2 breakers open | Check for missing phase (s) |
|
| Check for under frequency |
|
|
|
ATS will not retransfer Load | T - Timer has not expired |
|
back to Utility | Automatic Exerciser is in process |
|
| S1 Utility fully or partially unacceptable |
|
|
|
|
ATS does not transfer Load to S2 | S2 Generator fully or partially unacceptable | Set |
(generator) | Motor loads on system creating enough back- | ATS Fail setpoint |
| EMF to keep missing phase from falling below |
|
| Fail setpoint. |
|
|
|
|
S2 Generator will not start | X1 or X2 not connected | Check Generator Start wiring |
|
|
|
S2 Generator will not shut down | U - Timer not expired | Wait for U timer to expire |
| Automatic Exerciser in process |
|
|
|
|
All LEDs off | Keypad connector unplugged at Controller |
|
| Both source breakers open |
|
|
|
|
ATS will not transfer | Turn on | |
| Frequency difference between S1 and | Adjust Generator governor to hold |
| S2 greater than 2Hz. | freqency closer to Utility |
|
|
|
ATS will not retain a | Battery dead or missing | Replace battery with a fresh industrial |
Set Automatic Exerciser |
| grade Alkaline battery |
|
|
|
Both sources locked in frequency or one | Turn | |
| source greater than 20° out of phase |
|
|
|
|
S1 and S2 LEDs Blinking | Phase Rotation | Rewire sources to be same rotation |
|
|
|
S1 Position LED Blinking | SN limit switch bad or intermittent | Check connection or SN limit switch |
|
|
|
S2 Position LED Blinking | SE Limit switch bad or intermittent | Check connection or SE limit switch |
|
|
|
Both S1 and S2 Positioin | Solenoid bad or disconnected | Requires CANCEL key to clear - |
LEDs Blinking | ATS contactor in | check Solenoid |
|
| Requires CANCEL key to clear - |
|
| Check both limit switches |
|
|
|
|
| Table 9 |
■ GE Zenith Controls | ZTX Operation and Maintenance Manual | 15 ■ |