GE ZTX manual System Voltage Settings, Voltage / Frequency Selection Jumper Settings

Page 8

Installation (cont’d)

DANGER

HAZARDOUS VOLTAGE

(Can Cause Severe Injury or Death)

Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.

System Voltage Settings

Voltage / Frequency Selection Jumper Settings

ZTX controller boards are preconfigured to the system voltages specified at the time of order. Exact system volt- ages are normally set at the factory, however, depend- ing on the actual application and system nominal volt- age, ZTX control boards are capable of being adjusted slightly, to meet different source characteristics for voltage as well as frequency. (See Table 5)

Figure 6 (on right) shows the variations each of the 3 basic types of controllers can be adjusted to within its nominal voltage range. Position Jumpers JP1 and JP2, as needed for voltage. Position JP3 for frequency.

As with any other Jumper setting, always remove power completely from the controller before making changes.

240/480

JP1

JP2

A B 208/416

JP1

JP2

A B

50Hz

JP3

A B

120/380

JP1

JP2

A B 220/440

JP1

JP2

A B

60Hz

JP3

A B

Note: Do not change voltage Jumper positions

without consulting service or technical support.Figure 6 Arbitrarily changing voltage jumpers can adversely

affect ATS operation.

Type 1

 

Type 2

 

Type 3

 

 

Type 4

 

Frequency

120V

208 - 240VAC

380 - 416VAC

440 - 480VAC

 

 

JP1

JP2

 

JP1

JP2

 

JP1

JP2

 

JP1

JP2

 

JP3

B

B

208

A

B

380

B

B

440

B

A

50 Hz

A

-

-

220

B

A

416

A

B

480

A

A

60 Hz

B

-

-

240

A

A

-

-

-

-

-

-

-

-

Table 5

6

ZTX Operation and Maintenance Manual (72R-1000)

GE Zenith Controls

Image 8
Contents GE Zenith Controls Introduction Authorized ServiceTable of Contents Installation Can Cause Severe Injury or DeathInstallation cont’d Power ConnectionsGE Zenith Controls Control ConnectionsInstallation cont’d Functional Test Cover or close the cabinet doorSystem Voltage Settings Voltage / Frequency Selection Jumper SettingsIndicator LEDs Control InterfaceUsing the Keypad Controls Control Interface cont’dAutomatic Generator Exerciser Selecting Exerciser with or without Load TransferIn-Phase Monitor Turn In-Phase Monitor OFFExample Systems Total Coverage SystemTypical Diagrams Replacement Parts StandardTransition 40 to 200 AmpsReplacement Parts cont’d Standard Transition 225 to 400 AmpsTroubleshooting Symptom Possible Cause Corrective ActionGE Zenith Controls