3Com Router 6000 Family
Installation Manual
Chapter 8
Installing B68 Cabinets
3Com Corporation
8-12
1) Anchor strip retaining nut 2) Anchor strip 3) Cabinet foot
4) Insulating washer of the anchor strip 5) M12×35 bolt 6) Φ12 spring washer
7) Φ12 big flat washer 8) Insulation washer 9) Expansion tube
10) Expansion nut
Figure 8-14 Fix anchor strips

III. Fixing the retaining nuts of the anchor strips

Fasten the retaining nut on the anchor strip as shown in area B in Figure 8-14.

8.2.7 Testing Insulation

Switch the multimeter to Mohm range and measure the resistance between the fastening bolts
M12×70 and the anchor strips.
If the resistance is larger than five Mohm, you can finish installation. If not, remove all anchor
strip parts, check that the insulation washers are installed and without damage, reinstall, and
measure insulation until the requirement is satisfied. Figure 8-15 and Figure 8-16 illustrate how
to install a single and two cabinets on the concrete floor respectively.