12.4Remove constant force spring. Carefully bend shield wires back upon cable jacket 1 1/2" (38 mm). Cut excess shield wire and discard (Figure 17).

 

Depth of Terminal Lug + Growth Allowance

 

[A] + 3” (76 mm)

1 1/2

(38 mm)

 

Semi-Conductive Jacket

 

Fold Back Shield Wires

Figure 17

12.5 Remove semi-conductive jacket to dimension shown in Figure 18.

NOTE: To ease jacket removal, install constant force spring as shown in Figure 18 and ring cut 80% through jacket. Remove jacket sections by pulling against constant force spring. DO NOT BELL SEMI-CON JACKET. Remove constant force spring.

NOTE: It is imperative to remove all remnants of the semi-conductive jacket, even if the semi-conductive jacket comes off as one layer. There should not be any remaining black areas, or particles, on the cable insulation layer.

 

 

Depth of Terminal Lug + Growth Allowance

 

 

 

[A]

1 1/2

(38 mm)

1 1/2

(38 mm)

 

 

 

Semi-Conductive Jacket

 

 

Cut Line

 

 

Constant Force Spring

 

 

Fold Back Shield Wires

Figure 18

14

78-8117-0985-2 Rev C

Page 14
Image 14
3M 7684-S-8 manual Remove semi-conductive jacket to dimension shown in Figure