Instructions For Tape Shielded Cable

2.0Prepare Cable

2.1Check to be sure cable size fits within kit size range as shown in Table 1 (page 2).

2.2Prepare cable using dimensions shown in Figure 1. Be sure to allow for depth of terminal lug. Refer to

Table 2 for semi-con cutback dimension. If necessary to prevent tape shield from unrolling, hold down edge with a single wrap of 3M™ EMI Copper Foil Shielding Tape 1181.

NOTE: Provide additional exposed conductor distance to account for growth during crimping of ALUMINUM lugs or connectors as follows:

Aluminum Connector

2 - 350

400 - 650

Growth Allowance

1/4” (6 mm)

1/2" (13 mm)

NOTE: It is imperative to remove all remnants of the semi-con layer, even if the semi-con layer comes off as one layer. There should not be any remaining black areas, or particles, on the cable insulation layer.

Kit Number

Insulation 0.D.

15 kV

25/28 kV

35 kV

Semi-con

AWG / kcmil

AWG / kcmil

AWG / kcmil

Cutback

 

 

 

 

 

 

 

 

 

0.83" - 1.21"

4/0 - 300

2/0-3/0

2 - 2/0

13.5"

7684-S-8

(21,1 - 30,7 mm)

(120 - 150 mm2)

(70 - 95 mm2)

(35 - 70 mm2)

(342,9 mm)

 

 

 

 

 

0.98" - 1.53"

350 - 500

4/0 - 250

3/0 - 4/0

13.0"

 

 

(24,9 - 38,9 mm)

(185 - 240 mm2)

(120 - 150 mm2)

(95 - 120 mm2)

(330,2 mm)

 

 

 

 

 

 

Table 2

 

Jacket Removal Length

Depth Of Terminal Lug + Growth Allowance

3” (76 mm)

Semi-Con Cutback

1 1/ 2”

 

(38 mm)

 

 

Semi-Con

Tape Shield

 

Cable Jacket

 

Figure 1

78-8117-0985-2 Rev C