3.3.1
Installation | is |
|
Air humidity and ambient temperature
The boiler room must be
Air humidity and ambient temperature specifications
Air humidity and ambient temperature
Air humidity | max. 93% RV at +25°C |
|
|
Ambient temperature | Functional: 0 < T < 60°C |
|
|
3.3.2Appliance maximum floor load
In connection with the appliance's weight, take account of the maximum floor loading, refer to the table.
Weight specifications related to maximum floor load
Weight of the appliance filled with water
BFC 28 | 394 kg |
|
|
BFC 30, BFC 50, BFC 60 | 582 kg |
|
|
3.3.3Water composition
The appliance is intended for heating drinking water. The drinking water must comply with the regulations governing drinking water for human consumption. The table gives an overview of the specifications.
Water specifications
Water composition
Hardness | > 1.00 mmol/l: |
(alkaline earth ions) | • German hardness> 5.6° dH |
| • French hardness > 10.0° fH |
| • English hardness > 7.0° eH |
|
|
Conductivity | > 125 µS/cm |
|
|
Acidity (pH value) | 7.0 < pH value < 9.5 |
|
|
|
|
Note
If the water specifications deviate from those stated in the table, then the tank protection cannot be guaranteed (16 "Warranty (certificate)").
3.3.4Working clearances
For access to the appliance, it is recommended that the following clearances are observed (see figure):
•AA: around the appliance's control column and cleaning openings: 100 cm.
•BB: all sides of the appliance: 50 cm.
•Above the appliance (room to replace the anodes):
-100 cm if using fixed anodes, or
-50 cm if using flexible anodes.
18 | Instruction manual BFC |