•When communicating with outdoors by means of vertical ducts, each opening shall have a free area of not less than one square inch per 4,000 Btu per hour (551 mm2/kW) (35 square inches per gallon of oil consumed per hour) of total input rating of all appliances in the enclosure.
•If horizontal ducts are used, each opening shall have a free area of not less than one square inch per 2,000 Btu per hour (1,101 mm 2 /kW) (70 square inches per gallon of oil consumed per hour) of total input of all appliances in the enclosure, fig. 6.
TABLE 4 SUGGESTED VENT CONNECTOR SIZES
Model Number | Outlet Diameter | |
Inches | (mm) | |
6 | 152.4 | |
8 | 203.2 | |
8 | 203.2 | |
8 | 203.2 | |
8 | 203.2 | |
10 | 254 |
*These models are factory supplied with a flue reducer which should be installed on the top cover.
In venting systems where a continuous or intermittent back (positive) draft is found to exist, the cause must be determined and corrected. In some cases, a special vent cap may be required.
If the back draft cannot be corrected by normal methods or if a suitable draft cannot be obtained, additional make up air must be provided to the room to assure proper venting and combustion.
Note: A negative draft must be maintained in the vent piping.
The barometric draft regulator must be installed in the same room as the heater, fig. 6. Locate the regulator as close as possible to the heater and at least 18" (452 mm) from a combustible ceiling or wall. A manually operated damper should not be placed in the chimney connector.
FIGURE 6
FLUE GAS VENTING
In the absence of any local codes, regulations, or vent pipe or chimney manufacturer's recommendations, for oil fired equipment, follow the suggestions below for designing and installing a venting system.
For these water heaters, it is recommended that an adequate chimney be used for venting the flue gases. Type B, double wall, vent pipe should be used as the vent connector pipe. However, where no chimney is available, vent pipe may be used to construct a vent.
Where an existing chimney or vent is to be used, be sure that the chimney or vent has adequate capacity for the number and sizes of appliances being vented through it. Inspect the chimney or vent and remove all soot or other obstructions which will retard free draft.
VENT CONNECTOR AND DRAFT REGULATOR | CHIMNEY |
PROPER VENT CONNECTOR INSTALLATION
FIGURE 7
The chimney or vent connector diameter should be the same size as the heater flue outlet, see Table 4. A minimum rise of 1/4" per foot (21 mm/M) of horizontal connector length must be maintained between the heater and chimney opening, fig. 7. The connector length should be kept as short as possible.
The
TABLE 5 - USUAL CHIMNEY SIZES FOR UNITS
| Oil |
| Equivalent | Output |
| Square & Rectangle |
|
|
|
|
| ||||||
| Firing |
| Heat Input | Heat |
| Stack |
| Round Stack | Minimum | ||||||||
Model | Rate |
| Rate |
| Rate |
| Dimension | Diameter |
| Height | |||||||
Number | (GPH) |
| (LPH) | Btuh |
| kW | Btuh |
| kW | Inches |
| mm | Inches | mm | Feet |
| Metres |
1.42 |
| 5.38 | 199,000 |
| 58 | 159,200 |
| 47 | 8 1/2 X 8 1/2 |
| 216 x 216 | 9 | 228.6 | 20 |
| 6.1 | |
1.75 |
| 6.62 | 245,000 |
| 72 | 196,000 |
| 57 | 8 1/2 X 8 1/2 |
| 216 x 216 | 9 | 228.6 | 20 |
| 6.1 | |
2.25 |
| 8.52 | 315,000 |
| 92 | 252,000 |
| 74 | 8 1/2 X 13 |
| 216 x 330 | 10 | 254 | 30 |
| 9.1 | |
2.75 |
| 10.41 | 385,000 |
| 113 | 308,000 |
| 90 | 8 1/2 X 13 |
| 216 x 330 | 10 | 254 | 30 |
| 9.1 | |
3.25 |
| 12.30 | 455,000 |
| 133 | 364,000 |
| 107 | 13 X 13 |
| 330 x 330 | 12 | 304.8 | 35 |
| 10.7 | |
5.0 |
| 18.93 | 700,000 |
| 205 | 560,000 |
| 164 | 13 X 18 |
| 330 x 457 | 14 | 355.6 | 40 |
| 12.2 |
6