6.Connect the Major and Minor alarm wire pairs to the appropriate terminals on the external alarm system.
7.Dress and secure cable per standard industry practice.
4.12DC Power Connections
The HU is powered by ± 21 to 60 VDC power (nominal ± 24 or ± 48 VDC). The power is fed to the HU through a
1.Obtain one pair of #18 AWG (1.00 mm) red and black insulated copper wire for use as the power wiring.
2.Terminate one end of each wire with a fork terminal as shown in Figure 20.
3.Connect the power wires to the power terminal strip at the rear of the HU.
4.Route the free ends of the wires to the fuse panel and locate the terminals that will be used for the power feed. Refer to the user manual provided with the fuse panel for specific information.
5.Remove the fuse from the circuit that will power the HU.
+ (BLACK) | – (RED) |
FORK | #18 AWG |
TERMINALS | |
| (1.0 mm) |
| COPPER |
| WIRE |
Figure 20. DC Power Connections
Page 21