Read Status Options 4. Read Status
Unimode 400 Operations PN 50709:A 10/20/97 17
Table 13 contains descriptions of the fields shown in Figure 12: Table 13 Default Read Status Values for a DetectorRead Status for a Zone Address
Note: Press L to read a point
or zone with next highest
address; or press M to read a
point or zone with next lowest
address.
From the Read Point screen, press z, then enter the zone address (01-99) Figure 13 shows the default Read Status display for a zone:
Figure 13 Read Status Display for a Zone Address
Field Description
SMOKE (PHOTO) Type code of the detector.
DETECTOR ADDR 101 Default custom label: 101 (1=loop 1; 01=address 01).
Z03 Default zone selection:
Zone 01 (Heat detectors)
Zone 02 (Ion detectors)
Zone 03 (Photo detectors)
Zone 05 (Multi detectors)
You can change zones as well as add four more zones for each
detector’s CBE.
AL:5 The Alarm sensitivity level, with 9 the least sensitive Alarm
level and 1 the most sensitive Alarm level.
PA:0 Shows the Pre-Alarm level setting—a number between 0 and
9—as follows:
0 – no Pre-Alarm.
1 – most sensitive Pre-Alarm level.
9 – least sensitive Pre-Alarm level.
*V * The asterisk (*) indicates the cooperative multidetector mode:
A combines the detector's alarm decision with the next address
above.
B combines the detector's alarm decision with the next address
below.
C combines the detector's alarm decision with the next address
above and the next address below.
V – indicates Alarm Verification (V=on, *=off).
OFF SOFTWARE ZONE FLOOR 5 MAIN BLDG
Z04
Zone status (ON or OFF)
Zone number