Selecting AMG Tones and Messages 5. Voice Alarm Systems

Unimode 400 Operations PN 50709:A 10/20/97 29

AMG-1 and AMG-E Tone/Message Selections (AMG-1 SW2=Off) Table 23 lists

the tone and message selections available when SW2 rocker switch2 (Tone/Message Switch) is Off.Table 23 Setting AMG Tones and Messages (AMG-1 SW2=Off)1. MPS-400 Notification Appliance Circuit 1 (NAC1) can be manually selected with an ADT-ACM16AT to produce a desired tone or can be activated through Control-by-Event by a non-alarm input.2. If selecting a VROM or VRAM, and a VROM or VRAM chip is not installed, a trouble indication appears at the AMG-1 when the message is due to begin and the AMG-1 generates the 1 kHz default tone.
AMG-1 SW2 Rocker
Switches System
Status NAC 1 (B01)
Condition Audio Tone or Message

S6 S7 S8

X X X No Alarm Off Standby
Off
Off Off
Off Off
Off No Alarm
Alarm On
X1000 Hz 0.5 sec on, 0.5 sec off
Slow whoop
Off
Off Off
Off On
On No Alarm
Alarm On
XHorn
120 ppm (March Time)
Off
Off On
On Off
Off No Alarm
Alarm On
XHorn
Yelp
Off
Off On
On On
On No Alarm
Alarm On
XYelp
Wail
On
On Off
Off Off
Off No Alarm
Alarm On
X3 slow whoops, VRAM-B plays
3 slow whoops, VRAM-A plays
On
On Off
Off O
On No Alarm
Alarm On
XVROM-B message plays VROM-A
message plays
On
On On
On Off
Off No Alarm
Alarm On
X20 ppm (Two-Stage) VROM-A and
VROM-B play
On
On On
On On
On No Alarm
Alarm On
XHorn
NFPA Uniform Code 3
Temporal pattern fast whoop
X = Indicates that switch or control point can be On or Off.