5. Voice Alarm Systems Selecting AMG Tones and Messages

30 Unimode 400 Operations PN 50709:A 10/20/97

AMG-1 and AMG-E Tone/Message Selections (AMG-1 SW2=On) Table 24 lists

the tone and message selections available when SW2 rocker switch 2 (Tone/Message Switch) is On.Table 24 Setting AMG Tones and Messages (AMG-1 SW2=On)1. You can manually select MPS-400 Notification Appliance Circuit 1 (NAC1) with an ADT-ACM-16AT to produce a desired tone or it can be activated through Control-by-Event by a non-alarm input.2. If selecting a VROM or VRAM that is not installed, a trouble will be generated at the AMG-1 and the AMG-1 generates the 1 kHz default tone.3. Boston Code (order VROM-109, which must be installed in VROM-B position) – 900 Hz alert tone pulsed to produce one round of code 4 at approximately one second intervals, followed by female voice message:

Attention please. The signal tone you have just heard indicates a report of an emergency in this

building. If your floor evacuation signal sounds after this message, walk to the nearest stairway and leave

the floor. While the report is being verified, occupants on other floors should await further instructions.”

This message repeats. The evacuation signal is a slow-whoop tone—an ascending tone that starts at approximately 600 Hz and ends at approximately1100 Hz—with a duration of approximately 3.5 seconds and an interruption between tones of approximately 0.5 second.

AMG-1 SW2 Rocker

Switches System

Status NAC 1 (B01)

Condition Audio Tone or Message

S6 S7 S8

XX XNo Alarm Off Standby
Off
Off Off
Off Off
Off No Alarm
Alarm On
Off Horn1000 Hz 1/2 sec on, 1/2 sec off for
5min. then slow whoop
Off
Off
Off
Off
Off
Off
On
On
On
No Alarm
Alarm
Alarm
On
Off
On
Horn
20 ppm for 5 min., then 120 ppm
120 ppm (March Time)
Off
Off
Off
On
On
On
Off
Off
Off
No Alarm
Alarm
Alarm
On
Off
On
VROM-B
444, pause, VROM-A
Boston Code
Off
Off
Off
On
On
On
On
On
On
No Alarm
Alarm
Alarm
On
Off
On
VROM-B
Fast whoop
3 fast whoops, pause, VROM-A
On
On
On
Off
Off
Off
Off
Off
Off
No Alarm
Alarm
Alarm
On
Off
On
Beep
Fast whoop
3 fast whoops, pause, VROM-A and
VROM-B
On
On
On
Off
Off
Off
On
On
On
No Alarm
Alarm
Alarm
On
Off
On
Beep
3 slow whoops, pause, VROM-A
3 slow whoops, pause, VROM-A and
VROM-B
On
On
On
On
On
On
Off
Off
Off
No Alarm
Alarm
Alarm
On
Off
On
Wail
3 hi-low tones, pause, VROM-A
3 hi-low, pause, VROM-A and VROM-B
On
On
On
On
On
On
On
On
On
No Alarm
Alarm
Alarm
On
Off
On
Hi-low
20 ppm (Two-Stage)
3 Slow whoops, pause, VROM-A
X = Indicates that Switch or Control Point can be On or Off.