Appendix A Specifications
A.1 Analog Input
Table A.1: Analog Input
Channels | 8 differential |
Input type | mV, V, and mA |
Input range | J, K, T, E, R, S and B Thermocouple |
| |
| 0~500mV, 0~1V, 0~2.5V, 0~20mA, |
| 4~20mA |
Sampling rate | 10 samples/s(total) |
Accuracy | ±0.1% or better (voltage and current input) |
Zero drift | ±0.3 uV / °C |
|
|
Span drift | ±25 ppm / °C |
|
|
CMR @ 50/60 Hz | 92 dB |
|
|
Input impedance | 1.8 M |
A.2 Accuracy for Thermocouple:
Table A.2: Accuracy for Thermocouple
Input Range | Typical Accuracy | Maximum Error |
J thermocouple 0 to 760 °C | ±1.0 °C | ±1.5 °C |
|
|
|
K thermocouple 0 to 1370 °C | ±1.0 °C | ±1.5 °C |
|
|
|
T thermocouple | ±1.0 °C | ±1.5 °C |
E thermocouple 0 to 1000 °C | ±1.0 °C | ±1.5 °C |
R thermocouple 500 to 1750 °C | ±1.2 °C | ±2.5 °C |
|
|
|
S thermocouple 500 to 1750 °C | ±1.2 °C | ±2.5 °C |
|
|
|
B thermocouple 500 to 1800 °C | ±2.0 °C | ±3.0 °C |
|
|
|
NOTE: Due to the location of the CJC sensor, the measurement will have a 1°C max. difference in channels.
34 |