American Power Conversion SURTA1500XLJ, SURTA2000XL Problem and/or Possible Cause, Solution

Models: SURTA2000XL SURTA1500XLJ SURTA1500XL

1 16
Download 16 pages 49.04 Kb
Page 13
Image 13
Bypass LED is illuminated (Refer to “Display Panel Indicators” on page 6.)

Troubleshooting

Problem and/or Possible Cause

Solution

Bypass and Overload LEDs are illuminated and the UPS emits a sustained alarm tone (Refer to “Display Panel Indicators” on page 6.)

The UPS is overloaded.

The connected equipment exceeds the specified “maximum load” as defined in Specifications on the APC web site, www.apc.com.

The alarm remains on until the overload is removed. Disconnect nonessen- tial equipment from the UPS to eliminate the overload condition.

The UPS continues to supply power in the bypass mode and the circuit breaker does not trip; the UPS will not provide power from batteries in the event of a utility voltage interruption.

Bypass LED is illuminated (Refer to “Display Panel Indicators” on page 6.)

The bypass has been turned on through an accessory.

If bypass is the chosen mode of operation, ignore the illuminated LED.

Fault LED is illuminated (Refer to “Display Panel Indicators” on page 6.)

Internal UPS fault.

Do not attempt to use the UPS. Turn the UPS off and have it serviced immediately.

Fault and Overload LEDs illuminated and UPS emits a sustained alarm tone (Refer to “Display Panel Indicators” on page 6.)

The UPS has ceased sending power to connected equipment.

The connected equipment exceeds the specified “maximum load” as defined in Specifications on the APC web site, www.apc.com.

Disconnect nonessential equipment from the UPS to eliminate the over- load condition.

Press the

button, then the

button to restore power to connected

equipment.

 

 

The Replace Battery/Battery Disconnected LED is illuminated (Refer to “Display Panel Indicators” on page 6.)

Battery is disconnected.

Check that the battery connectors are fully engaged.

flashes and a short beep is emitted

 

every two seconds to indicate the bat-

 

tery is disconnected.

 

 

 

Weak battery.

Allow the battery to recharge for 24 hours and perform a self-test. If the

 

problem persists after recharging, replace the battery.

 

 

Failure of a battery self-test.

Allow the battery to recharge for 24 hours. Perform the self-test procedure

flashes and a short beep is emitted

to confirm the replace battery condition. The alarm stops and the LED

for one minute. The UPS repeats the

clears if the battery passes the self-test.

alarm every five hours.

If the battery fails again, it must be replaced. UPS output is maintained

 

during the self-test.

 

 

Smart-UPS RT SURTA1500XL/SURTA1500XLJ/SURTA2000XL Uninterruptible Power Supply User Manual

13

Page 13
Image 13
American Power Conversion SURTA1500XLJ, SURTA2000XL user manual Problem and/or Possible Cause, Solution