Operation

 

 

 

 

 

 

 

 

 

 

 

Indicator

Indicator Title

Description

 

 

LED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bypass

The Bypass LED illuminates indicating that the UPS is in bypass mode.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Utility power is sent directly to connected equipment during bypass mode

 

 

 

 

 

 

 

 

 

 

operation. Bypass mode operation is the result of an internal UPS fault, an

 

 

 

 

 

 

 

 

 

 

overload condition, or a user initiated command through an accessory. Bat-

 

 

 

 

 

 

 

 

 

 

tery operation is not available while the UPS is in bypass mode.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fault

The UPS detects an internal fault.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Overload

The connected equipment is drawing more than the UPS power rating

 

 

 

 

 

 

 

 

 

 

allows.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace Battery/Bat-

The battery is disconnected or must be replaced.

 

 

 

 

 

 

 

 

 

tery Disconnected

 

 

 

 

 

 

 

 

 

 

 

 

Display Panel Functions

 

 

 

 

 

 

 

 

 

 

 

 

Feature

Feature Title

Function

 

Button

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power On

Press this button to turn on the UPS. Continue reading for additional

 

 

 

 

 

 

 

 

 

 

capabilities.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power Off

Press this button to turn off the UPS output.

 

 

 

 

 

 

 

 

 

 

NOTE: The battery will continue to charge and the fans will continue to run

while the UPS is connected to the utility.

Cold Start

When there is no utility power and the UPS is off, press and hold the

 

button to power up the UPS and connected equipment.

 

The UPS will emit two beeps. During the second beep, release the button.

Self-Test

Automatic: The UPS performs a self-test automatically when tuned on, and

 

every two weeks thereafter (by default). During the self-test, the UPS

 

briefly operates the connected equipment On Battery.

 

Manual: Press and hold the

button for a few seconds to initiate the self-

 

test.

 

On Battery Operation

The UPS switches to battery operation automatically if the utility power fails. While running On Bat- tery, an alarm beeps four times every 30 seconds.

Press the button to silence this alarm. If the utility power does not return, the UPS continues to supply power to the connected equipment until the battery is fully discharged.

When 2 minutes of run time remain, the UPS emits a continuous beeping. If PowerChute is not being used, files must be manually saved and the computer must be turned off before the UPS fully dis- charges the battery.

Refer to www.apc.com for information on battery runtimes. The UPS battery runtime differs based on usage and environment.