Combustion Air Supply and Ventilation
WARNING
Carbon Monoxide Hazard Water heater must be vented to outdoors.
Vent must be installed by a qualified person using the installation instructions.
Examples of a qualified person include: gas technicians,
authorized gas company personnel, and authorized service persons.
Failure to follow these instructions can result in death or carbon monoxide poisoning.
IMPORTANT: Air for combustion and ventilation must not come from a corrosive atmosphere. Any failure due to corrosive elements in the atmosphere is excluded from warranty coverage.
The following types of installation (not limited to the following) will require outdoor air for combustion due to chemical exposure and may reduce but not eliminate the presence of corrosive chemicals in the air:
•beauty shops
•photo processing labs
•buildings with indoor pools
•water heaters installed in laundry, hobby, or craft rooms
•water heaters installed near chemical storage areas
Combustion air must be free of
Combustion and ventilation air requirements are determined by the location of the water heater. The water heater may be located in either an open (unconfined) area or in a confined area or small enclosure such as a closet or small room. Confined spaces are areas with less than 50 cubic feet for each 1,000 BTU/HR of the total input for all
7