American Water Heater 318935-003 Chimney Connection, Vertical Exhaust Gas Vent

Models: 318935-003

1 36
Download 36 pages 60.84 Kb
Page 11
Image 11
Chimney Connection

Chimney Connection

IMPORTANT: Before connecting a vent to a chimney, make sure the chimney passageway is clear and free of obstructions. The chimney must be cleaned if previously used for venting solid fuel appliances or fireplaces. Also consult local and state codes for proper chimney sizing and application or, in the absence of local and state codes, the “National Fuel Gas Code”, ANSI Z223.1(NFPA 54)-current edition.

The connector must be installed above the extreme bottom of the chimney to prevent potentially blocking the flue gases.

The connector must be firmly attached and sealed to prevent it from falling out.

To aid in removing the connector, a thimble or slip joint may be used.

The connector must not extend beyond the inner edge of the chimney as it may restrict the space between it and the opposite wall of the chimney (Figure 10).

Do not terminate the vent connector in a chimney that has not been certified for this purpose. Some local codes may prohibit the termination of vent connectors in a masonry chimney.

Vertical Exhaust Gas Vent

Vertical exhaust gas vents must be installed with U.L. listed type B vent pipe according to the vent manufacturer’s instructions and the terms of its listing.

It must be connected to the water heater’s draft hood by a listed vent connector or by directly originating at the draft hood opening.

Vertical gas vents must terminate with a listed cap or other roof assembly and be installed according to their manufacturer’s instructions.

Gas vents must be supported to prevent damage, joint separation, and maintain clearances to combustible materials (Figures 11 and 12).

IMPORTANT: This gas vent must be terminated in a vertical position to facilitate the removal of the burnt gases.

An unused chimney flue or masonry enclosure may be used as a passageway for the installation of a gas vent (Figure 12).

Common (combined) venting is allowable with vertical type B vent systems and lined masonry chimneys as long as proper draft for the water heater is established under all conditions of operation.

IMPORTANT: Do not common vent this water heater with any power vented appliance.

Figures 10-12 are examples of vent pipe system installations and may or may not be typical for your specific application. Consult the “National Fuel Gas Code”, NFPA 54, ANSI Z223.1-current edition and the guidelines set forth by prevailing local codes.

Listed Lined

Chimney

2 ft. minimum above any

object within10 ft.

Vertical Exhaust Gas VentManual backgroundManual background horizontally 3 ft. minimum Manual backgroundManual backgroundManual background

Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background*

Support Manual background Strap Manual background

Slope up Manual background

1/4 in. Manual background per ft. Manual background minimum Manual background

2 ft. minimum above any 3 ft. minimumobject within10 ft.

horizontally

Support Strap

Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background*

**Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background

Vent connector slope up

1/4 in. per ft.

 

 

minimum

 

Figure 12

 

 

LISTED VENT CAP

Venting Through

 

 

 

a Chimney

MAINTAIN MANUFACTURER’S

 

SPECIFIED MINIMUM CLEARANCE

**MAINTAIN

with Type B

 

 

SPECIFIED

Double Wall

 

 

CLEARANCE

Vent Pipe.

SUPPORT

 

 

 

 

 

 

STRAP

 

 

*MAINTAIN

 

 

CLEARANCE

SEAL

 

 

 

 

VENT

 

 

VENT CONNECTOR

CONNECTOR

 

UNUSED CHIMNEY

SLOPE UP

 

 

FLUE OR MASONRY

1/4 IN. PER FT.

 

 

ENCLOSURE

MINIMUM

 

 

 

*Maintain vent pipe clearance requirements to local, state and/or the “National Fuel Gas Code”, ANSI Z223.1(NFPA 54)-current edition.

**NFPA 211, Standard for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances states that these chimneys are intended to be installed in accordance with the installation instructions provided with each chimney support assembly. Minimum air space clearance to combustible materials should be maintained as marked on the chimney sections.

11

Page 11
Image 11
American Water Heater 318935-003 installation instructions Chimney Connection, Vertical Exhaust Gas Vent