Gas Supply
WARNING
Explosion Hazard
Use a new CSA approved gas supply line. Install a shut-off valve.
Do not connect a natural gas water heater to an L.P. gas supply.
Do not connect an L.P. gas water heater to a natural gas supply.
Failure to follow these instructions can result in death, explosion, or
carbon monoxide poisoning.
Gas Requirements
IMPORTANT: Read the data plate to be sure the water heater is made for the type of gas you will be using in your home. This information will be found on the data plate located near the gas control valve/thermostat. If the information does not agree with the type of gas available, do not install or light. Call your dealer.
NOTE: An odorant is added by the gas supplier to the gas used by this water heater. This odorant may fade over an extended period of time. Do not depend upon this odorant as an indication of leaking gas.
Gas Piping
The gas piping must be installed according to all local and state codes or, in the absence of local and state codes, the “National Fuel Gas Code”, ANSI Z223.1(NFPA
Table 1 on page 7 provides a sizing reference for commonly used gas pipe materials. Consult the “National Fuel Gas Code” for the recommended gas pipe size of other materials.
Refer to Figure 3
NOTE: When installing gas piping, apply approved pipe joint compound.
1.Install a readily accessible manual
2.Install a sediment trap (if not already incorporated as part of the water heater) as shown. The sediment trap must be no less than three inches long for the accumulation of dirt, foreign material, and water droplets.
3.Install a ground joint union between the gas control valve/thermostat and the manual
4.Turn the gas supply on and check for leaks. Test all connections by brushing on an approved noncorrosive
Figure 3
Gas PipingManual Gas
Ground
Joint
Union
Check with local
utility for
minimum height
3” Minimum |
Sediment Trap
Gas Pressure
IMPORTANT: The gas supply pressure must not exceed the maximum supply pressure as stated on the water heater’s data plate. The minimum supply pressure is for the purpose of input adjustment.
Gas Pressure Testing
IMPORTANT: This water heater and its gas connection must be leak tested before placing the appliance in operation.
•If the code requires the gas lines to be tested at a pressure exceeding 14” W.C., the water heater and its manual shut- off valve must be disconnected from the gas supply piping system and the line capped.
•If the gas lines are to be tested at a pressure less than 14” W.C., the water heater must be isolated from the gas supply piping system by closing its manual
U.L. recognized fuel gas and carbon monoxide (CO) detectors are recommended in all applications and should be installed using the manufacturer’s instructions and local codes, rules, or regulations.
NOTE: Air may be present in the gas lines and could prevent the pilot from lighting on initial