Available settings

Parameter

Associated LED

Explanation (when LED is illuminated)

 

 

 

 

Wiring Fault Setting

Wiring Fault

Utility (green)

Audible alarm sounds when ground is

 

 

 

 

missing or line and neutral connections are

 

 

 

 

reversed

 

 

 

 

 

ERM Setting

0

ERMs

0% to 25% load

UPS is configured for no attached ERMs

 

 

 

(green)

(factory default)

 

1

ERM

26% to 50%

UPS is configured for 1 attached ERM

 

 

 

load (green)

 

 

 

 

 

 

 

2

ERMs

51% to 75%

UPS is configured for 2 attached ERMs

 

 

 

load (green)

 

 

 

 

 

 

To change the UPS configuration parameters:

1.Place the UPS in Configure mode (on page 27).

The LEDs associated with the currently configured parameters illuminate. A flashing green cursor indicates where you are in the configuration process as you scroll through the available settings.

2.To change the nominal voltage, press the On button to advance the cursor to the LED associated with the appropriate nominal voltage parameter. The selected voltage configuration LED flashes.

3.Press the Standby button to select the nominal voltage configuration. The LED associated with the old input voltage parameter turns off, and the LED associated with the new input voltage parameter illuminates solid green.

NOTE: Only one nominal utility voltage can be configured. When setting voltage configuration parameters, selecting an On value for any one parameter automatically sets the other possibilities to Off.

4.To enable the Wiring Fault parameter, press the On button to advance the cursor to the Utility LED, then press the Standby button. The LED illuminates solid green. This parameter is disabled by default, and should only be enabled for line-to-neutral connections. Enabling this feature for line-to-line power sources causes a false alarm.

5.To configure the UPS for the number of connected ERMs, press the On button to advance the cursor to the load LED associated with the number of ERMs attached to the UPS.

6.Press the Standby button to select the appropriate ERM configuration. The associated LED illuminates solid green.

7.To save the configuration settings and exit Configure mode, press the Test/Alarm Reset button.

NOTE: Configure mode times out after 2 minutes. If the Test/Alarm Reset button has not been pressed, any new selections are not saved.

Testing the LEDs

To test the LEDs, press and hold the Test/Alarm Reset button for 3 seconds.

Silencing an audible alarm

To silence an alarm, press the Test/Alarm Reset button ("UPS front panel controls" on page 7).