Off

Off

Flashing

Off

Off

Off

On—1 beep

Yes

Battery test failure

 

 

red

 

 

 

every 5

 

("Battery condition" on

 

 

 

 

 

 

seconds

 

page 39)

 

 

 

 

 

 

 

 

 

Off

Flashing

Off

Off

Off

Off

On—1 beep

No

Low battery—No utility

 

red

 

 

 

 

every 5

 

power ("UPS is on

 

 

 

 

 

 

seconds

 

battery" on page 42)

 

 

 

 

 

 

 

 

 

Off

Off

Flashing

Off

Off

Off

On—1 beep

Yes

Batteries are

 

 

red

 

 

 

every 5

 

disconnected ("Battery

 

 

 

 

 

 

seconds

 

condition" on page 39)

Off

Red

Off

Off

Off

Off

On—1 beep

Yes

On battery—No utility

 

 

 

 

 

 

every 5

 

power ("UPS is on

 

 

 

 

 

 

seconds

 

battery" on page 42)

 

 

 

 

 

 

 

 

 

Off

Flashing

Off

Off

Flashing

Off

On—1 beep

Yes

On battery—Input

 

red

 

 

red

 

every 5

 

voltage is out of range

 

 

 

 

 

 

seconds

 

(on page 40)

 

 

 

 

 

 

 

 

 

Flashing

Flashing

Flashing

Flashing

Flashing

Flashing

On—

No

Internal UPS fault

red

red

red

red

red

red

Continuous

 

condition (on page 40)

 

 

 

 

 

 

 

 

 

Red

Off

Off

Off

Off

Off

On—

Yes

Battery condition (on

 

 

 

 

 

 

Continuous

 

page 39)

 

 

 

 

 

 

 

 

 

Flashing

Off

Off

Off

Flashing

Off

On—

Yes

REPO condition (on

red

 

 

 

green

 

Continuous

 

page 41)

Off

Off

Off

Red

Off

Off

On—1 beep

Yes

Site wiring condition

 

 

 

 

 

 

every 5

 

(on page 41)

 

 

 

 

 

 

seconds

 

 

 

 

 

 

 

 

 

 

 

Flashing

Off

Off

Off

Off

Red

On—

Yes

UPS power capacity is

red

 

 

 

 

 

Continuous

 

exceeded ("Overload

 

 

 

 

 

 

 

 

condition" on page 41)

 

 

 

 

 

 

 

 

 

For the location of individual LEDs, see "UPS front panel LED indicators (on page 8)."

Battery condition

Action:

1.Install the battery module. If the battery module is already installed, remove and reinsert the module.

2.Allow the UPS batteries to charge for 48 hours.

3.If the LED does not turn off, replace the batteries ("UPS battery replacement procedure" on page 35).

4.If the condition persists, contact an HP authorized service representative.

Bypass is out of range

The input voltage is not within ±12 percent of nominal voltage.

The UPS is receiving utility power that might be unstable or in brownout conditions. The UPS continues to supply power to the connected equipment. If conditions worsen, the UPS might switch to battery power.

Action:

1.Check the input voltage and reconfigure the UPS ("Configuring the UPS" on page 27).

2.Contact a qualified electrician to verify that the utility power is suitable for the UPS.

Troubleshooting 39