UPS model

Utility voltage

Available settings utility

Dedicated

Line cord

 

frequency (Hz)

voltage (VAC)

branch circuit

 

 

 

 

rating (A)

 

 

 

 

 

 

R5500 XR INTL

50/60

200/208, 220, 230*,

32

Nondetachable power

 

 

240

 

cord with 32 A IEC-309

 

 

 

 

plug

 

 

 

 

 

UPS output specifications

UPS model

Load

Circuit

Output receptacles

Maximum current

 

segment

breaker

 

 

 

 

 

 

 

 

 

R5500 XR NA/JPN

1

15 A¹

2 x IEC-320-C19

15

A per receptacle²

 

 

 

 

 

 

 

 

 

2 x IEC-320-C13

10

A per receptacle

 

 

 

 

 

 

 

 

1 x L6-30R

Up to full UPS power rating

 

 

 

 

 

 

 

2

15 A¹

2 x IEC-320-C19

15

A per receptacle²

 

 

 

 

 

 

 

 

 

2 x IEC-320-C13

10

A per receptacle

 

 

 

 

 

 

R5500 XR INTL

1

15 A¹

2 x IEC-320-C19

15

A per receptacle²

 

 

 

 

 

 

 

 

 

2 x IEC-320-C13

10

A per receptacle

 

 

 

 

 

 

 

 

1 x IEC-309-32A

Up to full UPS power rating

 

 

 

 

 

 

 

2

15 A¹

2 x IEC-320-C19

15

A per receptacle²

 

 

 

 

 

 

 

 

 

2 x IEC-320-C13

10

A per receptacle

 

 

 

 

 

 

¹ NOTE: The circuit breakers protect the C19 and C13 outlets.

²NOTE: If an extension bar is connected to a C19 receptacle, the maximum current for each C13 receptacle on the extension bar is 10 A. The total maximum current for the extension bar is 12 A.

Power protection specifications

UPS model

VA

Nominal power

Nominal voltage

 

 

 

rating (W)

setting

 

 

 

 

 

R5500

XR NA/JPN

5000

4500

200/208, 220,

 

 

 

 

230, 240

 

 

 

 

 

R5500

XR INTL

6000

5400

220, 230, 240

 

 

 

 

 

 

 

5000

4500

200/208

 

 

 

 

 

Voltage specifications

Configuration setting (VAC)

Available nominal output voltage (VAC)

 

 

200/208

204

 

 

220

220

 

 

230

230

 

 

240

240

 

 

Specifications 44

Page 44
Image 44
HP R5500 manual UPS output specifications, Power protection specifications, Voltage specifications