American Water Heater 318935-003 All Air from Outdoors, Louvers and Grilles, Minimum Free Area

Models: 318935-003

1 36
Download 36 pages 60.84 Kb
Page 9
Image 9
All Air from Outdoors

All Air from Outdoors

Outdoor fresh air can be provided to a confined area either directly or by the use of vertical and horizontal ducts. The fresh air can be taken from the outdoors or from crawl or attic spaces that freely communicate with the outdoors. Attic or crawl spaces cannot be closed and must be properly ventilated to the outside.

Ductwork must be of the same cross-sectional area as the free area of the opening to which they connect. The minimum dimension of rectangular air ducts cannot be less than three inches.

The size of each of the two openings is determined by the method in which the air is to be provided. Refer to Table 3 to calculate the minimum free area for each opening. Figures 6, 7, and 8 are typical examples of each method.

Louvers and Grilles

In calculating free area for ventilation and combustion air supply openings, consideration must be given to the blocking effect of protection louvers, grilles, and screens. These devices can reduce airflow, which in turn may require larger openings to achieve the required minimum free area. Screens must not be smaller than 1/4” mesh. If the free area through a particular design of louver or grille is known, it should be used in calculating the specified free area of the opening. If the design and free area are not known, it can be assumed that most wood louvers will allow 20 - 25% of free area while metal louvers and grilles will allow 60 - 75% of free area.

Louvers and grilles must be locked open or interconnected with the equipment so that they are opened automatically during equipment operation.

Keep louvers and grilles clean and free of debris or other obstructions.

Table 3

Minimum Free Area of Permanent Openings for Ventilation and Combustion Air Supply - All Air from Outdoors Only.

Based on the total BTU/HR input rating for all utilizing equip- ment within the confined space.

 

Minimum Free Area

Reference

Opening Source

Per Opening (sq. in.)

Drawing

* Direct to outdoors

1sq.in,per4000BTU/HR

Figure 6

Vertical ducts

1sq.in,per4000BTU/HR

Figure 7

Horizontal ducts

1sq.in,per2000BTU/HR

Figure 8A

Single Opening

1sq.in,per3000BTU/HR

Figure 8B

Example: A water heater with an input rate of 50,000 BTU/HR using horizontal ducts would require each opening to have a minimum free area of 25 square inches.

Minimum free area = 50,000 BTU/HR x 1 sq. in. / 2000 BTU/HR = 25 Sq. Inches.

*These openings connect directly with the outdoors through a ventilated attic, a ventilated crawl space, or through an outside wall.

Consult the local codes of your area for specific ventilation and combustion air requirements.

 

Gable vent

 

to outdoors

 

Install above

 

insulation

Confined

Outlet

Space

air to attic

 

1 Sq. inch per

 

4000 BTU/HR

Alternate

Inlet air

from the

Air Inlet

crawl

 

space

1 sq. inch per

Open

4000 BTU/HR

Foundation

 

Vent

Figure 6

All Air from Outdoors; Inlet Air from Ventilated

Crawl Space/Outlet Air to Ventilated Attic

 

Gable vent

 

to outdoors

 

Install above

 

insulation

Confined

Outlet air

to attic

Space

1 Sq. inch per

 

4000 BTU/HR

 

Inlet air duct

 

1 sq. inch per

 

4000 BTU/HR

Figure 7

12” maximum

All Air from Outdoors

 

Through Ventilated Attic

 

 

1 sq. inch

 

per

 

2000 BTU/HR

Confined

Outlet

Space

 

 

Outdoor

 

Air Ducts

 

Inlet

Figure 8A

1 sq. Inch

All Air from Outdoors

per

Using Horizontal Ducts

2000 BTU/HR

9

Page 9
Image 9
American Water Heater 318935-003 All Air from Outdoors, Louvers and Grilles, Minimum Free Area, Reference