American Water Heater BCG3 Troubleshooting, Complaint Cause Remedy User, Qualified Service Agency

Models: BCG3 ABCG3

1 52
Download 52 pages 59.75 Kb
Page 34
Image 34

Troubleshooting

COMPLAINT

CAUSE

REMEDY

USER

Qualified Service Agency

*Water not hot enough

Thermostat set too low.

Set thermostat dial to a higher

 

 

 

temperature

 

 

Upper and/or lower temperature

Call qualified service agency

Check continuity and resistance (Ohms)

 

probe out of calibration.

 

of upper and lower temperature probes.

 

 

 

Replace probes if out of specification.

*Insufficient hot water

Thermostat set too low.

Set thermostat dial to a higher

 

*See WATER TEMPERATURE

 

temperature

 

CONTROL WARNING (on page

Upper and/or lower temperature

Call qualified service agency

Check continuity and resistance (Ohms)

12).

probe out of calibration.

 

of upper and lower temperature probes.

 

 

 

Replace probes if out of specification.

 

Main manual gas shutoff valve

Open main manual gas shutoff

 

 

partially closed.

valve to fullest extent.

 

 

Heater too small for demand.

Space usage to give heater time

 

 

 

to restore water temperature.

 

 

Heater recovery is slower.

Call qualified service agency

Check gas input. If incorrect, adjust gas

 

 

 

pressure or replace burner orifices.

 

Gas pressure switch doesn't close.

Call qualified service agency

Temporarily bypass the gas pressure

 

 

 

switch connections and measure

 

 

 

gas supply pressure while the unit is

 

 

 

running. If less than 5.2" WC, adjust

 

 

 

the gas supply pressure above 5.2" but

 

 

 

less than 11". If greater than 5.2" WC,

 

 

 

replace the gas pressure switch.

Water temperature too hot.

Thermostat set too high.

Set thermostat to a lower setting.

 

Heater makes sounds: sizzling.

Condensation on outside of

 

 

 

tank, normal.

 

 

Rumbling.

Sediment accumulation on

Drain a quantity of water through

Delime heater.

 

bottom of tank.

drain valve. If rumbling persists,

 

 

 

call a qualified service agency.

 

Ticking or metallic sounds.

Expansion and contraction -

 

 

 

normal.

 

 

Pounding or water hammer.

Air chambers in piping have

Drain piping system and refill.

Follow the manufacturers instructions

 

become waterlogged. Thermal

Heater must be off while this

for proper charging of the thermal

 

expansion tank damaged,

is being done. Check thermal

expansion tank.

 

improperly charged, or

expansion tank charge pressure

 

 

improperly sized.

when the water system pressure

 

 

 

is zero.

 

Combustion noises.

Too much primary air.

Call service agent.

 

 

Overfired heater; Incorrect

Call service agent.

Check and correct as necessary.

 

burners or orifice for type of gas

 

 

 

used.

 

 

Water leaks.

Drain valve not closed tightly.

If drain valve cannot be closed

 

 

 

tightly, replace.

 

 

Possible condensation if tank

Increase tank temperature

 

 

is undersized or stored water is

setting (add a mixing valve

 

 

below 110 degrees.

if setting will be above 120

 

 

 

degrees).

 

 

If leakage source cannot be

Shut off gas supply to heater

Repair or in case of suspected tank

 

corrected or identified, call

and close cold water inlet valve

leakage, be certain to confirm before

 

qualified service agency.

to heater.

replacing heater.

Gas odors.

Heater is over fired

Shut off gas supply to heater

Check for sooted flue passage.

 

 

and call a service agent.

 

 

 

Check for obstructed vent line.

 

 

 

 

 

 

Check backdraft or lack of draft

 

Possible gas leaks.

Shut off gas supply to heater

 

 

 

and call gas company at once

 