PRESSURE ADJUSTMENT
The
CAUTION! Exceeding Maximum Acceptance will reduce tank life and cause irreparable damage.
Step 1: Find the Maximum Acceptance for the installed
MODEL | MAXIMUM | |
ACCEPTANCE | ||
| ||
.57 | ||
.35 | ||
.77 | ||
.55 | ||
.54 |
Step 2: Ensure the desired operating range does not exceed that model's Maximum Acceptance.
CUT-OUT PRESSURE
|
| 20 | 25 | 30 | 35 | 40 | 45 | 50 | 55 | 60 | 65 | 70 | 75 | 80 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 10 | .28 | .38 | .45 | .50 | .55 | .59 | .62 | .65 | .67 | .69 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 15 |
| .25 | .34 | .40 | .46 | .50 | .54 | .57 | .60 | .63 | .65 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
PRESSURE | 20 |
|
| .22 | .30 | .37 | .42 | .46 | .50 | .64 | .57 | .59 | .61 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
25 |
|
|
| .20 | .27 | .34 | .39 | .43 | .47 | .50 | .53 | .56 | .58 | |
|
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 30 |
|
|
|
| .18 | .25 | .31 | .36 | .40 | .44 | .47 | .50 | .53 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 35 |
|
|
|
|
| .17 | .23 | .29 | .34 | .38 | .41 | .45 | .48 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
IN | 40 |
|
|
|
|
|
| .16 | .22 | .27 | .31 | .35 | .39 | .42 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
45 |
|
|
|
|
|
|
| .14 | .20 | .25 | .30 | .33 | .37 | |
CUT- |
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
50 |
|
|
|
|
|
|
|
| .13 | .19 | .24 | .28 | .32 | |
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 55 |
|
|
|
|
|
|
|
|
| .13 | .18 | .22 | .26 |
| 60 |
|
|
|
|
|
|
|
|
|
| .12 | .17 | .21 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 65 |
|
|
|
|
|
|
|
|
|
|
| .12 | .16 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 70 |
|
|
|
|
|
|
|
|
|
|
|
| .11 |
1.To enter the programming mode, press and hold the MODE button until LO appears. This is the
2.Use the s and t arrows to raise or lower the cut- in setting. Adjustment can be made within 10 psig or as wide as 55 psig of the
Minimum setting is 10 psig.
PRESS AND HOLD TO UNLOCK AND SET
t
t
11