Page 11
Image 11
PRESSURE ADJUSTMENT

PRESSURE ADJUSTMENT

The Well-X1utilizes a simple cut-in/cut-out adjustment. Before setting the desired operating range, refer to the chart below to ensure the Well-X1's Maximum Acceptance is not exceeded. Adjust the precharge as shown on page 12.

CAUTION! Exceeding Maximum Acceptance will reduce tank life and cause irreparable damage.

Step 1: Find the Maximum Acceptance for the installed Well-X1model.

MODEL

MAXIMUM

ACCEPTANCE

 

WX1-202

.57

WX1-203

.35

WX1-250

.77

WX1-251

.55

WX1-302

.54

Step 2: Ensure the desired operating range does not exceed that model's Maximum Acceptance.

CUT-OUT PRESSURE

 

 

20

25

30

35

40

45

50

55

60

65

70

75

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

.28

.38

.45

.50

.55

.59

.62

.65

.67

.69

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

 

.25

.34

.40

.46

.50

.54

.57

.60

.63

.65

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PRESSURE

20

 

 

.22

.30

.37

.42

.46

.50

.64

.57

.59

.61

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25

 

 

 

.20

.27

.34

.39

.43

.47

.50

.53

.56

.58

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

 

 

 

 

.18

.25

.31

.36

.40

.44

.47

.50

.53

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

35

 

 

 

 

 

.17

.23

.29

.34

.38

.41

.45

.48

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IN

40

 

 

 

 

 

 

.16

.22

.27

.31

.35

.39

.42

 

 

 

 

 

 

 

 

 

 

 

 

 

 

45

 

 

 

 

 

 

 

.14

.20

.25

.30

.33

.37

CUT-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

 

 

 

 

 

 

 

 

.13

.19

.24

.28

.32

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

55

 

 

 

 

 

 

 

 

 

.13

.18

.22

.26

 

60

 

 

 

 

 

 

 

 

 

 

.12

.17

.21

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

 

 

 

 

 

 

 

 

 

 

 

.12

.16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

70

 

 

 

 

 

 

 

 

 

 

 

 

.11

1.To enter the programming mode, press and hold the MODE button until LO appears. This is the cut-in setting. Factory default will be 40 psi.

2.Use the s and t arrows to raise or lower the cut- in setting. Adjustment can be made within 10 psig or as wide as 55 psig of the cut-out setting to 60 psig. If this range is exceeded, the display will cease to change even though the button is being pressed.

Minimum setting is 10 psig.

PRESS AND HOLD TO UNLOCK AND SET CUT-IN

t

t

11