APC SUA1500X93, 120VAC, 750XL, 1500VA, 230VAC, 1000XL user manual User Configurable Items

Models: 750XL 230VAC SUA1500X93 1500VA 1000XL 120VAC

1 18
Download 18 pages 19.67 Kb
Page 8
Image 8
3:USER CONFIGURABLE ITEMS

3:USER CONFIGURABLE ITEMS

NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE OR OPTIONAL SMART SLOT

ACCESSORY CARDS.

FUNCTION

FACTORY

USER SELECTABLE CHOICES

DESCRIPTION

DEFAULT

 

 

 

 

 

Automatic Self-Test

Every 14 days

Every 7 days

This function sets the inter-

 

(336 hours)

(168 hours),

 

val at which the UPS will

 

 

On Startup Only, No Self-

execute a self-test. Refer to

 

 

Test

 

your software manual for

 

 

 

 

details.

 

 

 

 

 

UPS ID

UPS_IDEN

Up to eight characters to

Use this field to uniquely

 

 

define the UPS

identify the UPS, (ie. server

 

 

 

 

name or location) for net-

 

 

 

 

work management purposes.

 

 

 

 

Date of Last Battery Re-

Manufacture

Date of Battery Replacement

Reset this date when you

placement

Date

mm/dd/yy

 

replace the battery module.

 

 

 

 

 

 

 

 

 

Minimum Capacity Be-

0 percent

15, 30, 45, 50, 60, 75, 90

The UPS will charge its

fore Return from Shut-

 

percent

 

batteries to the specified

down

 

 

 

percentage before return

 

 

 

 

from a shutdown.

 

 

 

 

Voltage Sensitivity

 

Brightly lit: UPS is set to

To change the UPS sensitiv-

The UPS detects and

 

high sensitivity (default).

ity, press the voltage sensi-

 

 

 

tivity button

(rear panel).

reacts to line voltage

 

Dimly lit:

UPS is set to

 

Use a pointed object (such as

distortions by transferring

 

medium sensitivity.

 

a pen) to do so.

 

to battery operation to

 

Off:

Low battery

 

 

 

 

protect the connected

 

You can change the sensitiv-

equipment. Where power

 

warning interval is about

ity level through Power-

quality is poor, the UPS

 

eight minutes.

Chute software.

 

may frequently transfer to

 

 

 

 

 

battery operation. If the

 

 

 

 

 

connected equipment can

 

 

 

 

 

operate normally under

 

 

 

 

 

such conditions, reduce

 

 

 

 

 

the sensitivity setting to

 

 

 

 

 

conserve battery capacity

 

 

 

 

 

and service life.

 

 

 

 

 

 

 

 

 

Alarm Control

Enable

Mute, Disable

User can mute an ongoing

 

 

 

 

alarm or disable all existing

 

 

 

 

alarms permanently.

 

 

 

 

Shutdown Delay

90 seconds

0, 180, 270, 360, 450, 540,

Sets the interval between the

 

 

630 seconds

 

time when the UPS receives

 

 

 

 

a shutdown command and

 

 

 

 

actual shutdown.

 

 

 

 

 

 

 

 

6

 

 

 

Page 8
Image 8
APC SUA1500X93, 120VAC, 750XL, 1500VA, 230VAC, 1000XL user manual User Configurable Items